Wire Network Connection
Ethernet Port Lights
Adjust BACnet Network Settings
Command Unit Operation
-
Enable Unit
Control Occupancy -
Reset Alarms
-
Global Alarm Notification
-
Control Temperature Setpoint (optional)
Object | Object Name | Object Description | Active Text | Inactive Text |
---|
Variable Type
BV-2| System_Enable| Master system enable/disable point.| Enabled| Disabled
BV-3| BMS_Occupancy_Command| Occupancy Command| Unoccupied| Occupied
BV-4| Reset_All_Alarms| Alarm Reset Command| Reset| Normal
BV-19| Global_Alarm| Alarm Notification (any alarm by default)| Alarm| Normal
AV-1| Temperature_Setpoint| Sets the active temperature set-point based on
mode of operation (space setpoint, return setpoint or supplysetpoint). Not
applicable for outside reset.| Default = 72°FMin = 50°F; Max = 100°F
Reference Guide for BACnet Integration
Please read and save these instructions for future reference. The information
in this guide assumes the controller was already configured with BACnet based
on the original sales configuration. If the controller does not have BACnet
enabled, please contact the equipment representative to get the neces sary
licensing and configuration files to allow BACnet communicationto be used.
MUA_01.001 Rev 2
Document Date: 01/2023
Basic Unit Integration
Below are the basic integration functions available on all equipment regardless of control mode. Some features are unit configuration dependent (heating type, cooling type, etc.). The controller’s BMS points list is static regardless of configuration to accommodate field configuration changes, however, not all points are applicable every unit. Once the required sensors are installed in the equipment, the only mandatory requirements to make the unit operational are to enable the unit, if it hasn’t been enabled manually at the controller, and to command occupancy as desired.
| Object| Variable| Description| Active Text| Inactive
Text
---|---|---|---|---|---
| Unit Enable/Disable Operation
| If desired, the unit can be enabled and disabled by the BMS system. In
disabled mode, certain safety sequences may operate to protect thebuilding
and/or equipment but general heating, cooling and ventilation operation will
not function.
| BV-2| System_Enable| Master system enable/disable command| Enabled| Disabled
| Unit Occupancy Control
| By default, the unit occupancy is expected to be commanded by the BMS
occupancy point. Alternatively, the unit occupancy can be controlled by an
internal schedule, set to always unoccupied, always occupied or controlled by
a digital input by changing the occupancy mode selection at the controller. If
the controller is configured for warm-up/cool-down mode, after the occupancy
command is received the unit will run in unoccupied recirculation mode until
reaching the occupied temperature setpoint or the warm-up/cool down time
expires (default 30 minutes)at which point the controller will enter normal
occupied mode operation.
| BV-3| BMS_Occupancy_Command| Building Occupancy Command| Unoccupied|
Occupied
| Alarms
| The following points allow the notification of any alarm and the last alarm
triggered to be read, as well as active alarms that to be manuallyreset
remotely. See the unit’s full BMS points list if specific alarm monitoring or
trending is desired.
| BV-4| Reset_All_Alarms| Alarm Reset Command| Reset| Normal
| BV-19| Global_Alarm| Global Alarm| Alarm| Normal
| IV-9| LatestAlm| Most recent active alarm| See Alarm Table (0 = No Active
Alarm)
| Monitoring Unit Operation
| Unit status
| AV-41| Unit_Status_Mode| Unit Operation Mode/State| See Status Mode Table
| Fans and Dampers
| BI-1| Exhaust_Fan_1_Status_Digital_Input| Exhaust Fan 1 Status| Active|
Inactive
| BI-2| Supply_Fan_1_Status_Digital_Input| Supply Fan 1 Status| Active|
Inactive
| AV-62| Outside_Airflow_Mask| Percentage of Outside Airflow| Real (%)
| AV-63| Supply_Fan_Speed_Analog_Output| Supply Fan Speed Analog Output| Real
(%)
| Cooling
| IV-15(Bit 20)| Cooling_is_On| Indicates that the unit is cooling| Active|
Inactive
| AV-43| Cooling_1_Ramp_Capacity| Cooling Ramp 1 Status Value| Real (%)
| Heating
| IV-15(Bit 21)| Heating_is_On| Indicates that the unit is heating| Active|
Inactive
| AV-46| Heating_Capacity| Heating Ramp| Real (%)
| Filters
| IV-13(Bit 3)| Filter_Alarm_Digital_Input| Filter Alarm Digital Input
Status| Alarm| Normal
| Refrigeration Systems
| IV-10(Bit 3)| Compressor_1_Enable_Digital_Output| Compressor 1 Enable
Digital Output| Active| Inactive
| IV-10(Bit 4)| Compressor_2_Enable_Digital_Output| Compressor 2 Enable
Digital Output| Active| Inactive
| AV-64| Modulating_Compressor_Analog_Output_BMS| Modulating Compressor Analog
Output| Real (%)
Object| Variable| Description| Active Text| Inactive
Text|
Chilled Water Systems|
AV-58| Chilled_Water_1_Valve_Analog_Output| Chilled Water 1 Valve Analog
Output| Real (%)|
Evaporative Cooling Systems|
IV-10(Bit 16)| Evap_Valve_Enable_Digit_Output| Evaporative Cooling Valve
Enable| Active| Inactive|
IV-10(Bit 17)| Evap_Pump_Enable_Digit_Output| Evaporative Cooling Pump
Enable| Active| Inactive|
Hot Water Systems|
AV-60| Hot_Water_Valve_1_Analog_Output| Hot Water Valve 1 Analog Output| Real
(%)|
IG Furnaces|
IV-10(Bit 7)| Furnace_1_Stage_1_Digital_Output| Furnace 1 Stage 1 Digital
Output| Active| Inactive|
IV-10(Bit 8)| Furnace_1_Stage_2_Digital_Output| Furnace 1 Stage 2 Digital
Output| Active| Inactive|
IV-10(Bit 9)| Furnace_2_Stage_1_Digital_Output| Furnace 2 Stage 1 Digital
Output| Active| Inactive|
IV-10(Bit 10)| Furnace_2_Stage_2_Digital_Output| Furnace 2 Stage 2 Digital
Output| Active| Inactive|
IV-10 (Bit 11)| Furnace_3_Stage_1_Digital_Output| Furnace 3 Stage 1 Digital
Output| Active| Inactive|
AV-61| Mod_Gas_Furnace_1_Analog_Output| Mod Gas Furnace 1 Analog Output| Real
(%)|
Electric Post-Heat|
IV-10 (Bit 15)| Electric_Heater_Start_Stop_Digital_Output| Electric Heater
Digital Output| |
AV-59| Electric_Heater_1_Analog_Output| Electric Heater 1 Analog Output| Real
(%)|
Direct Gas Burner|
IV-10 (Bit 14)| Direct_Gas_Heating_Enable_Digital_Output| Direct Gas Enable
Digital Output| Active| Inactive|
Sensor Values (when equipped)|
AI-1| Space_Temp_Analog_Input| Space Air Temperature| Real (°F)|
AI-2| Supply_Temp_Analog_Input| Supply(discharge) Air Temperature| Real (°F)|
AI-3| Outside_Air_Temp_Analog_Input| Outside Air Temperature| Real (°F)|
AI-9| Space_Static_Pressure_Analog_Input| Space Static Pressure| Real (“wc)|
AI-10| Supply_Duct_Static_Pressure_Analog_Input| Supply Duct Static Pressure|
Real (“wc)|
AI-11| Space_CO2_1_Analog_Input| Space 1 CO2 ppm| Real (ppm)|
AI-12| Return_CO2_Analog_Input| Return CO2 ppm| Real (ppm)|
AV-56| OAD_CFM_BMS| Outdoor Air Damper CFM| Real (cfm)|
Active Setpoints|
AV-42| Supply_Temperature_Calculated_Setpoint| Active Supply Temperature
Setpoint| Real (°F)|
Unpacking Integer Words to Binary Values
Binary values can be combined to create an integer word. By doing this, more information is available to the BMS in a smaller number of points and less network traffic. These integer words need to be “unpacked” once the BMS receives the value.
Object Variable Description Reference Table
Packed Integer Words
IV-10| Digital_Output_Word| Digital Output Enables| Bit Packed Word – See
Binary Tables
IV-11| Cooling_Alarm_Word| Cooling Device Alarms| Bit Packed Word – See
Binary Tables
IV-12| Device_Offline_Word| Device Communication Alarms| Bit Packed Word – See
Binary Tables
IV-13| Device_Alarm_Word| Device Alarms| Bit Packed Word – See Binary Tables
IV-14| Heating_Alarm_Word| Heating Device Alarms| Bit Packed Word – See
Binary Tables
IV-15| Unit_Status_Word| Unit Status Word| Bit Packed Word – See Binary
Tables
To unpack the integer word into the binary values, the integer needs to be converted to a binary number. The integers in the program are 32-bit, meaning up to 32 binary values are packed into the integer. Each bit can either be a 0 (Inactive) or a 1 (Active).
The BMS front end may have a solution already intact to pull individual bits from an integer. A “read bit” function looks to return what value a certain bit is in an integer. Bit number are 0-31 in a 32-bit integer with 0 being the lowest bit and the furthest to the right in the binary notation of the number. Bit 31 would be the largest bit and the furthest to the left in binary notation.
If the front end does not have a “read bit” or “bit extract” function, the binary value of individual bits can be determined by continually dividing the quotient of the integer by 2, the remainder of the division is the value of the bit (0 or 1). A function called Modulo or “mod” and is commonly used to return the remainder of integer division.
Equation: x = (round down(a/2b ) )mod 2
- x is Boolean value for bit b, where 0 is inactive and 1 is active.
- a is the integer word value
- b is the bit of the binary number used as an exponent
- The result of a/2b should round down to a whole number, truncating the decimal. For example, 5/21 is 2.5, however, only the 2 is used.
Example:
If the Device_Offline_Word (IV-12) is a decimal value of 11, the binary value
would be 1011. This binary value would mean that Space Thermostats 1, 2, and 4
are offline. The rest of the bits in the binary number would be a Boolean
value of 0. (Please see Binary Tables.)
- Bit 0 = 11/20 mod 2… this results in a Boolean of 1 or Active for bit 0.
- Bit 1 = 11/21 mod 2… this results in a Boolean of 1 or Active for bit 1.
- Bit 2 = 11/22 mod 2… this results in a Boolean of 0 or Inactive for bit 2.
- Bit 3 = 11/23 mod 2… this results in a Boolean of 1 or Active for bit 3.
Bit| 31| 30| 29| 28| 27| 26| 25|
24| 23| 22| 21| 20| 19| 18| 17|
16| 15| 14| 13| 12| 11| 10| 9| 8|
7| 6| 5| 4| 3| 2| 1| 0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Val| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0| 0|
0| 0| 0| 0| 1| 0| 1| 1
Modifying Equipment Operation
In addition to commanding unit occupancy, some system level sequences may require feedback from the BMS. Common BMS adjusted sequences include items like supply air temperature reset control, demand control ventilation for multiple zones, and duct static pressure reset.
HEATING AND COOLING OPERATION SETPOINTS
| Object| Variable| Description| Active Text| Inactive
Text
---|---|---|---|---|---
| Adjusting Temperature Setpoints
| Controller Provided Sequences – Occupied Mode
| The controller has several stand-alone supply air temperature control modes
with setpoints that can be modified by the BMS. These modes include a static
supply air temperature setpoint (no-reset) or allows for the supply air
temperature setpoint to be reset based on outside air temperature,
spacetemperature, or return air temperature.
| IV-1| Temperature_Reset_Mode| Commands the reset mode during
occupiedoperation.| 1 = No Reset, 2 = Space Reset3 = Return Reset, 4 = Outside
Reset
| __ AV-1| __ Temperature_Setpoint| Sets the temperature setpoint
based on mode of operation (space setpoint, return setpoint or supply
setpoint).Not applicable for outside reset.| __ Real, Default = 72°FMin
= 50°F; Max = 120°F
| __ AV-2| __ Temperature_Heat_Cool_Deadband| Heat/Cool Setpt
Deadband when Space or Return reset control is active.Htg Setpt = Temp Setpt –
Deadband /2 Clg Setpt = Temp Setpt – Deadband /2| Real, Default = 4°F Min =
0.1°F; Max = 20°F[Space/Return Heating = 70°F, Space/Return Cooling = 74°F]
| Controller Provided Sequences – Unoccupied Mode
| When the unoccupied mode of operation is set to night setback temperature,
normal operation with unoccupied setpoints, or recirculation withunoccupied
setpoints, the following setpoints control unoccupied heating and cooling
operation. If night setback is selected as the Unoccupied Mode of operation,
the reset mode will not be available to change at the controller and should be
set to Space Reset(2).
| IV-2| Temperature_Reset_Mode_Unoccupied| Commands the reset mode during
occupiedoperation.| 1 = No Reset, 2 = Space Reset3 = Return Reset, 4 = Outside
Reset
| __ AV-3| __ Temperature_Setpoint_Unoccupied| Sets the
temperature setpoint based on mode of operation (space setpoint, return
setpoint or supply setpoint).Not applicable for outside reset.| __ Real,
Default = 72.5°FMin = 50°F; Max = 120°F
| Object| Variable| Description| Active Text Inactive
Text
| __**AV-4| __**_Temperature_Heat_Cool_DeadbandUnoccupied|
Heat/Cool Setpt Deadband when Space or Return reset control is active.Unooc
Clg Setpt = Deadband /2 + Temp Setpt Unocc Htg Setpt = Deadband /2 – Temp
Setpt| Real, Default = 15°F Min = 0.1°F; Max = 40°F [Space/Return
Heating = 65°F, Space/Return Cooling = 80°F]
BMS Controlled Sequences|
BMS control over reset write to temp setpoint and have mode in No reset.|
AIRFLOW OPERATION SETPOINTS
Object| Variable| Description| Active Text| Inactive
Text
---|---|---|---|---
Airflow Setpoints
Airflow operation of supply fan, exhaust fan, and mixing dampers may use
setpoints from duct pressure, space pressure, CO2 sensors, or airflow
measuring stations to properly control airflow in an application. The Outside
Air Damper Minimum Setpoint Occupied applies to all units withmodulating
outside air dampers. The setpoint is used to establish an absolute minimum
position for ventilating the space while allowing other control modes to open
the damper further as necessary. Outdoor and recirculating air dampers operate
inversely using the same signal.
AV-16| Space_Static_Pressure_Setpoint| Space Static Pressure Setpoint| Default
= 0.05”wcMin = -0.5”wc; Max = 0.5”wc
AV-17| Supply_Duct_Static_Pressure_Setpoint| Supply Duct Static Pressure
Setpoint| Default = 1.0”wcMin = 0”wc; Max = 5”wc
AV-18| Space_CO2_Setpoint| Space CO2 Setpoint| Default = 1,000 ppmMin = 0 ppm;
Max = 5,000 ppm
AV-19| Outside_Air_Damper_Minimum_Setpoint_Occ| Outside Air Damper Minimum
Setpoint Occupied| Default = 35%Min = 0%; Max = 100%
BMS Watchdog Enabled Control
BMS WATCHDOG
When directly commanding fans speeds, damper positions, or sending sensor
values, the unit controller requires the BMS Watchdog point to be written to
on a recurring basis. This tells the unit controller that the BMS is still
actively communicating.
Object| Variable| Description| Active Text| Inactive
Text
---|---|---|---|---
BMS Watchdog
The BMS Watchdog must be written to True (1) regularly to verify communication
is established between the unit controller and the BMS headend system. If the
BMS Watchdog value remains False(0) for longer than the Timeout Delay (15
minutes, adjustable), an alarm is generated and thecontroller falls back to
local control and sensor values, as applicable, instead of using BMS commanded
values.
BV-1| BMS_Watchdog| BMS Watchdog command| Active| Inactive
BV-20| BMS_Watchdog_Active| Status of the BMS watchdog ping.| Active| Inactive
CONTROLLING AIRFLOW DEVICES
If desired, the speeds and positions of airflow devices can be controlled directly using BACnet commandable points. To control the devices via the BMS, the BMS Watchdog requirements must be satisfi.
Object| Variable| Description| Active Text| | Inactive
Text
---|---|---|---|---|---
Fan Controls
Fan speeds can be controlled directly though BMS points. The binary points
enable the BMS to take control and the analog values command thespeeds as a
percentage between the allowed minimum and maximum values set in the
controller.
Supply Fan
BV-14| SF_Control_Source_BMS| Allows the BMS to control supply fan speed| BMS|
Local
AV-38| SF_Control_Signal_BMS| Supply Fan Command Speed| Real (%)*Min=50%;
Max=100%
Outdoor Air/Recirculation Air Damper Control
The outdoor air damper position can be controlled directly by the BMS to
adjust the mixture of outdoor air and recirculation air on units configured
forrecirculation. Minimum and maximum values for occupied and unoccupied mode
set at the unit controller are enforced.
BV-15| OAD_Control_Source_BMS| Allows the BMS to control OAD position| BMS|
Local
AV-39| OAD_Control_Signal_BMS| Outside Air Damper Control Signal via BMS| Real
(%)Min=0%; Max=100%
SENDING SENSOR VALUES
Sensor values required for sequence operation can be sent to the controller
over dedicated BMS points in place of a sensor wired to the controller (local
sensor). When values are communicated to the controller over BMS, the BMS
Watchdog must be satisfied. If the watchdog isn’t satisfied, the controller
reverts to the local sensor (if installed and valid) to control the unit or
falls back to local control until the BMS watchdog is satisfied.
Object| Variable| Description| Active Text| Inactive
Text
---|---|---|---|---
BMS Writeable Sensor Values
To write the sensor values over BMS, first command the controller to use the
BMS value using the corresponding binary value and then use thecorresponding
analog value to send the sensor value.
Sensor Sources
BV-6| Outside_Temp_Source_BMS| Outside Temp Source Selection| BMS| Local
BV-9| Space_1_CO2_Source_BMS| Space 1 CO2 Source Selection| BMS| Local
BV-10| Return_CO2_Source_BMS| Return CO2 Source Selection| BMS| Local
BV-12| Space_Static_Source_BMS| Space Static Source Selection| BMS| Local
BV-13| Space_Temp_Source_BMS| Space Temp Source Selection| BMS| Local
Sensor Values
AV-30| Outside_Temp_from_BMS| Outside Temp from BMS| Real (°F)
AV-33| Space_1_CO2_from_BMS| Space 1 CO2 from BMS| Real (ppm)
AV-34| Return_CO2_from_BMS| Return CO2 from BMS| Real (ppm)
AV-36| Space_Static_from_BMS| Space Static from BMS| Real (“wc)
AV-37| Space_Temp_from_BMS| Space Temp from BMS| Real (°F)
Advanced BACnet Settings
Additional settings can be accessed in the BACnet Advanced Settings menu
includingBACnet Broadcast Management Device (BBMD) configuration, relinquish
default settings, Change of Value (COV) increments and restoring binary text
value
BBMD CONFIGURATION
To configure the controller to operate with a BACnet Broadcast Management
Device (BBMD) on IP networks, go to the advanced BACnet settings menu and
enter the IP
address of the BBMD, foreign device configuration, and time to live setting.
COV INCREMENTS
BACnet COV is an optional portion of BACnet that supports providing new
values/information only after an increase or decrease of the value is at least
the listed
COV increment. The controller’s COV increments are based on the unit of
measure. All variables with the same unit of measure share the same COV
increment value. Valuescan be adjusted on this screen, or by writing to the
COV increment property of any BACnet object.
RELINQUISH DEFAULT SETTINGS
When the Return to Default function is enabled, the present value will not
overwrite
the relinquish default value and on a loss of power the controller will boot
with last
saved default values instead of last written values. This must also be enabled
for the BACnet Comm Loss relinquish default to work.
When the Enable Relinquish Default function is enabled any value in the
priority array
for binary values or analog values will be cleared if a communication loss is
detected. All commandable points will revert to the relinquish default value.
Communication loss is determined based on the BMS Watchdog. The watchdog
function must be enabled. The function will execute 5 minutes after the
watchdog status goes inactiv
This may be desired if the BMS is running a reset routine on the setpoints and
would
like to revert to a default state if communication is lost. It is recommended
to be used
with return to default enabled, and a known relinquish default is saved. When
this box is checked by a user, the controller will write the present value of
variables to the relinquish default for all binary and analog value BACnet
objects that are commandable. The function operates in the background and
takes approximately30 seconds to complete.
This is desired to save any Test and Balance settings adjusted locally on the
controller to be the BACnet relinquish default values. Alternatively, these
values could be read and written to the relinquish default variables by the
BMS system.
BINARY TEXT
If for any reason, the state text is missing from binary objects, checking
this box will cause the controller to re-write the active and inactive text
values.
MUA Reference Table
STATUS MODE TABLE
The following analog values can appear in the point to tell the building
automation the current mode of operation of the unit. Values may rotate every
three seconds.
Status Mode Table (AV-41)
Analog Value| Mode| Analog Value| Mode|
Analog Value| Mode
0| Off/Standby| 10| System On| 21| Cooling
1| Unoccupied Start| 11| Soft Shutdown| 22| Heating
2| Occupied Start| 12| System Disabled| 30| Overrides
3| Opening Dampers| 13| Remote Off| 31| Expansion Offline
5| Dampers Open| 14| System Shutdown Alarm| 32| Occupancy Overridden
6| Fan Start Delay| 18| Unit Off Flow Active| 33| Max Vent Sequence Active
7| Exhaust Fan Start| 19| Fans Only| 35| Morning Sequence Active
8| Supply Fan Start| 20| Economizing| 36| Winter Ramp Active
9| Startup Delay| | | |
ALARM TABLE
This table displays the latest alarm that is active in the unit controller.
Alarm Table – Latest Alarm (IV-9)
0| No Active Alarms| 27| IG Furnace 1 Combust Fan High Pressure Switch
1| Supply Fan Run Status Not Proven| 28| IG Furnace 1 Ignition Controller
Alarm
2| Exhaust Fan Run Status Not Proven| 29| IG Furnace 1 Pressure Switch Fault
Alarm
3| Filters are Dirty Replace Filters| 30| IG Furnace 1 Combust Fan Proving
Alarm
4| Cond Drain Pan Full Check Drain| 31| IG Furnace 1 Max Retries
5| High Supply Duct Static Pressure| 32| IG Furnace 1 High Limit Trip
6| Outside Air Temp Sensor Value Not Valid| 33| IG Furnace pCOe 1 Offline
7| Space Temperature Sensor Value Not Valid| 34| IG Furnace 1 IC Fault Check
IC->pCOe Wiring
8| Supply Air Temperature Sensor Value Not Valid| 35| IG Furnace 1 Combustion
Fan Alarm
9| Outside Air GreenTrol Offline or Flow Error| 36| IG Furnace pCOe 2 Offline
10| Hi/Low Pressure Switch Circuit A| 37| IG Furnace 2-No Flame Alarm After 3
Tries
11| Hi/Low Pressure Switch Circuit B| 38| IG Furnace 2 Max Retries
12| Space CO2 Sensor Value Not Valid| 39| IG Furnace 2 Ignition Controller
Alarm
13| Return CO2 Sensor Value Not Valid| 40| IG Furnace 3-No Flame Alarm After 3
Tries
14| Space Static Pressure Sensor Value Not Valid| 41| IG Furnace 3 Max Retries
15| Supply Duct Stat Press Sensor Value Not Valid| 42| IG Furnace 3 Ignition
Controller Alarm
16| Supply Air Temperature Low Limit Shutdown| 43| DG Flame Safeguard General
Reference
17| Supply Air Temperature High Limit Shutdown| 44| DG Flame Safeguard Manual
Reset at FSG
18| Space High Static Pres Shutdown| 45| DG Pilot Flame Alarm Did Not Prove
19| BMS Offline Watchdog is FALSE| 46| DG Heating Safety Check Circuit
20| BACnet License Not Installed| 47| DG Flame Safeguard Check Functionality
21| Space Thermostat 1 Sensor Offline| 48| DG Burner Differential Check
Pressure
22| Space Thermostat 2 Sensor Offline| 51| Multi Devices per Ch Contact Tech
Support
23| Space Thermostat 3 Sensor Offline| 52| Comp Maintenance Alarm Run Hours
Setpoint Reached
24| Space Thermostat 4 Sensor Offline| 54| Non-Volatile Memory Er Contact Tech
Support
25| IG Furnace 1-No Flame Alarm After 3 Tries| 55| Cooling Exp Board pCOe 3
Offline
26| IG Furnace 1 – Large No Flame After 3 Tries| 59| Exp Board 4 Status Board
is Offline
BIT-PACKED INTEGER WORD TABLES
The following tables are used to unpack integer words into Boolean values.
Digital Output Table (IV-10)
Bit| Digital_Output_Word| Bit| Digital_Output_Word|
Bit| Digital_Output_Word
0| Supply Fan Start| 11| Furnace 3 Start| 22|
1| Exhaust Fan Start| 12| | 23|
2| Exhaust Relief Enable| 13| Damper Actuator Power Enable| 24|
3| Compressor 1 Start| 14| Direct Gas Start| 25|
4| Compressor 2 Start| 15| Electric Heat Start| 26|
5| Condenser Fan Start| 16| Evaporative Cooling Valve Enable| 27|
6| | 17| Evaporative Cooling Pump Enable| 28|
7| Furnace 1 Start| 18| | 29|
8| Furnace 1 Stage 2 Start| 19| | 30|
9| Furnace 2 Start| 20| | 31|
10| Furnace 2 Stage 2 Start| 21| | |
Cooling Alarm Table (IV-11)
Bit| Cooling_Alarm_Word| Bit| Cooling_Alarm_Word|
Bit| Cooling_Alarm_Word
0| Circuit A High/Low Pressure Switch Alarm| 11| | 22|
1| Circuit B High/Low Pressure Switch Alarm| 12| | 23|
2| | 13| | 24|
3| | 14| | 25|
4| | 15| | 26|
5| | 16| | 27|
6| | 17| | 28|
7| | 18| | 29|
8| | 19| | 30|
9| | 20| | 31|
10| | 21| | |
Device Offline Table (IV-12)
Bit| Device_Offline_Word| Bit| Device_Offline_Word|
Bit| Device_Offline_Word
0| Space T-Stat 1 Offline| 11| | 22|
1| Space T-Stat 2 Offline| 12| | 23|
2| Space T-Stat 3 Offline| 13| | 24|
3| Space T-Stat 4 Offline| 14| | 25|
4| IG Furnace Controller 1 Offline| 15| | 26|
5| IG Furnace Controller 2 Offline| 16| | 27|
6| Cooling Controller Offline| 17| | 28|
7| GreenTrol Outside Air Offline| 18| | 29|
8| BMS Offline Alarm| 19| | 30|
9| Permanent Memory – Too Many Writes| 20| | 31|
10| | 21| | |
Device Alarms Table (IV-13)
Bit| Device_Alarm_Word| Bit| Device_Alarm_Word| Bit|
Device_Alarm_Word
0| Supply Fan Alarm| 11| Supply High Duct Static Alarm| 22|
1| Exhaust Fan Alarm| 12| Supply Duct Static Sensor Alarm| 23|
2| Drain Pan Alarm| 13| Space Static Pressure Sensor Alarm| 24|
3| Filter Alarm| 14| Space High Static Alarm| 25|
4| GreenTrol OAD AFMS Alarm| 15| Return CO2 Sensor Alarm| 26|
5| Outside Air Temp Sensor Alarm| 16| | 27|
6| Space CO2 Sensor Alarm| 17| Shutdown Input Alarm| 28|
7| Supply Air Temp Sensor Alarm| 18| | 29|
8| Space Temperature Sensor Alarm| 19| | 30|
9| Supply Temp Low Limit Alarm| 20| | 31|
10| Supply Temp High Limit Alarm| 21| | |
Heating Alarm Table (IV-14)
Bit| Heating_Alarm_Word| Bit| Heating_Alarm_Word|
Bit| Heating_Alarm_Word
0| DG Flame Safeguard General Reference| 11| IG Furnace 1 Pressure Switch
Fault Alarm| 22| IG Furnace 3 Ignition Controller Alarm
1| DG Flame Safeguard Manual Reset at FSG| 12| IG Furnace 1 Combust Fan
Proving Alarm| 23|
2| DG Pilot Flame Alarm Did Not Prove| 13| IG Furnace 1 Max Retries| 24|
3| DG Heating Safety Check Circuit| 14| IG Furnace 1 High Limit Trip| 25|
4| DG Flame Safeguard Check Functionality| 15| IG Furnace 1 IC fault Check
Furnace Wiring| 26|
5| DG Burner Differential Check Pressure| 16| IG Furnace 1 Combustion Fan
Alarm| 27|
6| General IG Furnace Alarm| 17| IG Furnace 2-No Flame Alarm After 3 Tries|
28|
7| IG Furnace 1 No flame Alarm After 3 Tries| 18| IG Furnace 2 Max Retries|
29|
8| IG Furnace 1 Large No Flame After 3 Tries| 19| IG Furnace 2 Ignition
Controller Alarm| 30|
9| IG Furnace 1 Combust Fan High PressureSwitch| 20| IG Furnace 3-No Flame
Alarm After 3 Tries| 31|
10| IG Furnace 1 Ignition Controller Alarm| 21| IG Furnace 3 Max Retries| |
Unit Status Word Table (IV-11)
Bit| Unit_Status_Word| Bit| Unit_Status_Word| Bit|
Unit_Status_Word
0| Off/Standby| 11| Remote Off| 22| Dehumidifying
1| Unoccupied Start| 12| System Shutdown Alarm| 23| Hot Gas Reheat Active
2| Occupied Start| 13| Supply Fan Only| 24| HGRH Purging
3| Opening Dampers| 14| Exhaust Fan Only| 25| Dehum w/Heat
4| Dampers Open| 15| Purge Mode (Supply and Exhaust Only)| 26| Energy Recovery
Defrost Active
5| Fan Start Delay| 16| Case Heat Active| 27| Heat Pump Defrost Active
6| Exhaust Fan On| 17| Fans Only| 28| Morning Warm Up/Cool Down Active
7| Supply Fan On| 18| Economizing| 29| Winter Ramp Active
8| System On| 19| Energy Recovery Active| 30|
9| Soft Shutdown| 20| Cooling| 31| Overrides Active
10| System Disabled| 21| Heating| |