SJE RHOMBUS CL40 Single Phase Duplex Pump Control System Instructions

August 9, 2024
SJE RHOMBUS

SJE RHOMBUS CL40 Single Phase Duplex Pump Control System Instructions
SJE RHOMBUS CL40 Single Phase Duplex Pump Control
System

Demand Dose or Timed Dose, Float or C-Level™ Sensor Controlled System for Pump Control, System Monitoring, Event Logging and Reporting.

The IFS In-Site® duplex control panel utilises an innovative circuit board design to control two alternating 120/208/240V single phase pumps in water and sewage applications. IFS panels feature an easy-to-use touch pad on inner door for programming and system monitoring. The alternating action equalises pump wear. In addition, this system provides override control should either pump fail. Quick retrieval of all system events can be done by downloading panel information onto a USB flash drive. The panel configuration can be easily converted in the field to either a timed dose or demand dose. Available with the Connection® float system.

Monitor system events including pump run times, pump cycles, alarm conditions, power outages, service calls and more! Quick, convenient reports make diagnosing system conditions easy! Plug the flash drive into the USB port located on the inner door of the IFS In-Site® panel to download system events which occurred. No computer is needed at the site! Use the flash drive (included with panel) with any computer to download system information and reports. The pre-loaded software on the flash drive formulates system data for you, creating reports quickly in an easy-to-read format so system conditions can be easily identified and corrected. In addition to monitoring system events, the IFS In-Site® panel logs any service calls and changes made to system settings, which helps protect service providers.

The panel can utilise the C-Level™ sensor for continuous level monitoring. It senses the level in the tank and sends a signal to the panel. Pump activation levels can be adjusted by using the panel touch pad. C-Level™ CL40 sensor operating range is 3-39.9 inches (7.6-101.3 cm). C-Level™ CL100 operating range is 3-99.5 inches (7.6-252.7 cm).

  • Five-year limited warranty on panel
  • Two-year limited warranty on C-Level™ Sensor

TOUCH PAD FEATURES

A. Level Status indicators illuminate when floats or set points are activated; alarm will activate if a float operates out of sequence
B. HOA (Hand-Off-Automatic) buttons with indication control pump mode; Hand mode defaults to Automatic when stop level or redundant off level is reached
C. Pump Run indicators will illuminate when pumps are called to run
D. LED display for system information including: level in inches or centimetres (C-Level™ only), mode, pumps elapsed time (hh:mm), events (cycles), alarm counter, float error count, timed dose override counter (timed dose only), pump ON/OFF times (timed dose only), and sequence ON/OFF times (timed dose only)
E. NEXT push button toggles display
F. UP and SET Push Buttons used to set pump ON/OFF times (timed dose only), pump operation (alternate 1-2 and 2-1), date and hour, activation levels (C-Level™ only)

Panel layout may vary with options. Reg. Cdn Pat. & TM Off C-Level™ Sensor US Patent No. 8,336,385; 8,567,242; 8,650,949
Components

COMPONENTS

  1. Enclosure base measures 16 x 14 x 6 inches (40.64 x 35.56 x 15.24 cm); NEMA 4X (ultraviolet stabilised thermoplastic with removable mounting feet for outdoor or indoor use)
  2. Red LED beacon provides 360° visual check of alarm condition
  3. Exterior Alarm Test/Normal/Silence switch allows horn and light to be tested and horn to be silenced in an alarm condition; alarm automatically resets once alarm condition is cleared
  4. Alarm horn provides audio warning of alarm condition (83 to 85 decibel rating)
  5. Circuit breakers (optional) provide pump disconnect and branch circuit protection
  6. Power relays control pump by switching electrical lines; definite purpose contactors used when pump full load amps are above 15
  7. Float connection terminal block
  8. Incoming Control/Alarm Terminal Block
  9. Control Power indicator/fuse indicator light illuminates if control power is present in panel; alarm activates if control fuse is blown
  10. Alarm Power indicator/fuse indicator light illuminates if alarm power is present in panel (Not shown)
  11. Ground lugs
  12. Incoming pump power connections
  13. RF filter
  14. Power supply
  15. Control fuse
  16. Alarm fuse
  17. USB port for flash drive to download time-stamped system events
  18. Manual report switch date and time stamps service calls
    Note: Options, voltage, and amp range selected may change enclosure size and component layout.
    Note: Schematic/Wiring Diagram and Pump Specification Label are located inside the panel.

INSTALLER FRIENDLY SERIES® IN-SITE® SINGLE PHASE DUPLEX – Demand or timed dose float controlled system for pump control, system monitoring, event logging and reporting.

  • CONTROL PANEL
  • MODEL TYPE
  • ALARM PACKAGE
  • ENCLOSURE RATING
  • STARTING DEVICE
  • PUMP FULL LOAD AMPS
  • PUMP DISCONNECTS
  • LEVEL CONTROL APPLICATION
  • OPTIONS (LISTED BELOW)

CONTROL PANEL| ✓| IFI|
---|---|---|---
MODEL TYPE| | 3| Duplex Timed Dose (includes Option 8AC as standard)
| 4| Duplex Demand Dose (includes Option 8AC as standard)
ALARM PACKAGE| ✓| 1| Alarm Package (includes test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING| ✓| W| Weatherproof, NEMA 4X (engineered thermoplastic)
STARTING DEVICE| | 1| 120/208/240V
| 9| 120V only
PUMP FULL LOAD AMPS| | 0| 0 – 7 FLA
| 1| 7 – 15 FLA
| 2| 15 – 20 FLA
PUMP DISCONNECTS| | 0| No Pump Disconnect
| 4| Circuit Breaker(s) 120V (select STARTING DEVICE Option 9 above)
Circuit Breaker(s) 120/208/240V (select STARTING DEVICE Option 1 above)
LEVEL CONTROL APPLICATION| | H| Floats – Pump Down (select Option 17 below)Timed dose = timer enable and alarm / Demand dose = stop, start, and alarm
| E| EZconnex® Float Switch System(select Option 34 or 35 below)| Timed Dose
Demand Dose
| X| No Floats| Timed Dose
Demand Dose
| C| C-Level™ Sensor (select Option 24 or 29)* Select Option 3E and/or 4A & 4D for high water alarm and/or redundant off floats| Timed Dose
Demand Dose

NOTE : Pump down applications only. Industry practices suggest that a secondary device, such as a float switch,
be used for redundant activation of the high level alarm and pump shut off when using the C-Level™ sensor.

PRICING WORKSHEET

IFI Duplex Base Price

  • Alarm Package
  • Enclosure Rating
  • Starting Device
  • Pump Full Load Amps
  • Pump Disconnects
  • Level Control Application
  • Total Options
  • TOTAL LIST PRICE

| OPTIONS| DESCRIPTION
---|---|---
| 1J| Duo Alarm Inputs
| 3A| Alarm Flasher
| 3B| Manual Alarm Reset
| 3E| High Water Alarm Float (must also select Option 17) Only Available with Level Control Application = C
| 4A| Redundant Off(must also select Option 4D if floats are required)| Timed Dose
Demand Dose
| 4D| Redundant Off Float (must also select Option 4A and Option 17)
| 6A| Auxiliary Alarm Contact, Form C
✓| 8AC| Display Board – Includes: ETM Counter, Events (Cycles) Counter, Alarm Counter, Override Counter (Timed Dose Only), and Lead/ Lag Selector (Demand Dose Only) (included as standard)
| 10E| Lockable Latch – NEMA 4X
| 10F| Lightning Arrest or (select pump circuit breakers, control and alarm power combined)
| 10K| Anti-condensation Heater (must select if operating temperature is colder than 0 degrees F or -18 degrees C)
| 11C| Additional NEMA 1 Remote Alarm Panel (must also select Option 6A)
| 11D| Additional NEMA 4X Remote Alarm Panel (must also select Option 6A)
| 15A| Control/Alarm Circuit Breaker
| 16A| 10’ Cord in Lieu of 20’ Cord (per Float)
| 16B| 15’ Cord in Lieu of 20’ Cord (per Float)
| 16C| 30’ Cord in Lieu of 20’ Cord (per Float)
| 16D| 40’ Cord in Lieu of 20’ Cord (per Float)
| 17C| Sensor Float® / Internally Weighted (per Float) – Mercury
---|---|---
| 17D| Sensor Float® / Externally Weighted (per Float) – Mercury
| 17G| SJE Mill Amp Master™ / Pipe Clamp (per Float) – Mechanical
| 17H| SJE Mill Amp Master™ / Externally Weighted (per Float) – Mechanical
| 17J| Sensor Float® / Pipe Clamp (per Float) – Mercury
| 18A| Timer Override Float (Timed Dose Float Panel Only)
| 19F| Fourth Float to Separate Alarm Function from Lag(Demand Dose Float Panel Only)
| 24E| C-Level™ CL40 Sensor with 25′ Vented Cable
| 24F| C-Level™ CL40 Sensor with 50′ Vented Cable
| 24P| C-Level™ CL40 Sensor with 100′ Vented Cable
| 24X| No C-Level™ CL40 Sensor
| 29A| C-Level™ CL100 Sensor with 25′ Vented Cable
| 29B| C-Level™ CL100 Sensor with 50′ Vented Cable
| 29C| C-Level™ CL100 Sensor with 100′ Vented Cable
| 29X| No C-Level™ CL100 Sensor
| 34D ■| EZconnex® 4-Port, 25’, with 10’ Floats (3) / Pipe Clamp, Sealing Plug
| 34E ■| EZconnex® 4-Port, 50’, with 10’ Floats (3) / Pipe Clamp, Sealing Plug
| 34G ■| EZconnex® 4-Port, 25’, with 20’ Floats (3) / Pipe Clamp, Sealing Plug
| 34H ■| EZconnex® 4-Port, 50’, with 20’ Floats (3) / Pipe Clamp, Sealing Plug
| 35D ■| EZconnex® 4-Port, 25’, with 10’ Floats (4) / Pipe Clamp
| 35E ■| EZconnex® 4-Port, 50’, with 10’ Floats (4) / Pipe Clamp
| 35G ■| EZconnex® 4-Port, 25’, with 20’ Floats (4) / Pipe Clamp
| 35H ■| EZconnex® 4-Port, 50’, with 20’ Floats (4) / Pipe Clamp

*C-Level™ Sensor lengths up to 300 ft. available. Call for details.