BANNER DXM700-B1R1 Wireless Controller User Guide
- June 4, 2024
- BANNER
Table of Contents
DXM700-B1R1 Wireless Controller
User Guide
Vibration Monitoring and Predictive Maintenance
Solutions Kit Quick Start Guide
Overview
The Solutions Kit provides visual status of up to 40 Banner 1-wire serial or
All-in-One Vibration Sensor Nodes (assets) that are bound to the included DXM
Wireless Controller.
The Condition Monitoring VT/CT Node (CM1L) can also take advantage of current
measurements in combination with the vibration and temperature measurements.
The Solutions Kit uses the Error 404–Not Found
(bannerengineering.com)
software to program the DXM Wireless Controller.
The Sensor Nodes take a data sample every 5 minutes and the software uses the
raw data to detect whether an asset is running, and creates a baseline of the
four vibration characteristics (RMS Velocity (10-1000 Hz) and RMS High-
Frequency Acceleration (1000-4000 Hz) on Z and X axis) and generates warning
and alarm thresholds for those characteristics. Only data from an operational
asset is used to create the baselines or thresholds and only that data is used
to trigger warnings or alarms. Data from assets that are not operational
appear on the graphs but are not used in the analysis.
RMS Velocity identifies problems such as imbalance, misalignment, looseness,
and other low-frequency machine issues. RMS high-frequency acceleration is
used to indicate early bearing wear issues.
Hardware
The items included with the Vibration Monitoring and Predictive Maintenance
Solutions Kit are:
- 10″ Banner Touch Screen HMI with Ethernet connection
- 404 | Leader in Process & Industrial Automation Solutions (bannerengineering.com)
- 5-port Ethernet switch
- M12 power input connector
- 404 | Leader in Process & Industrial Automation Solutions (bannerengineering.com), DIN rails, and terminal blocks
This kit also requires a 24 V DC Class 2 (UL) or a Limited Power Source (LPS) (CE) power supply that is sold separately. Banner recommends model PSW-24-1 (FCC/CE) or model PSD-24-4 (FCC/CE) if you are powering additional indicator lights.
HMI Home Screen
Status icons represent groups of 10 assets. Each icon is a color-coded
indication of the status of vibration warnings or alarms, temperature warnings
or alarms, or wireless Node connection status within that group.
The icon acts as a touch button that brings up the 10 individual icons that
represent that assets’ status and acts as a touch button to view that assets’
screen where detailed data viewing options are available (see Vibration Node
Group Screens on page 2).
Press X (in the upper right-hand corner of each icon) to hide that group of
assets and prevent Node status alerts for any Nodes within that group. Press
the icon that appears after pressing X to unhide that group for future
expansion.
Press Settings to open access to Node binding, Node site survey, asset
baselining, log file downloads, and other settings (see Settings Screen on
page 3).
Touch each asset group label to re-label the icon.
Vibration Node Group Screens
Each asset group on the main page has a screen of icons, one for each
sensor/radio pair. These icons represent the status of the motor with colored
icons.
Touch any icon to bring up the individual sensor’s screen that includes
graphs, raw data, and alert descriptions (see Individual Radio (Asset) Status
Screen on page 2).
Touch X (upper right-hand corner of each icon) to hide that asset and prevent
connection status alerts from that sensor/radio from appearing on the main HMI
screen. Use the button that appears after pressing X to unhide that group for
future expansion. For example, asset #8 is hidden in the sample screen.
Touch each asset label to re-label the icon. That label remains in non-
volatile memory and appears on the Node’s status screen, binding screen, site
survey screen, and baselining screens.
A small green lamp in the bottom right corner of a Node’s icon indicates when
that Node is baselining. Only temperature warnings and alarms appear during
the baselining phase. After baselining is complete, the threshold levels are
established and vibration alerts may begin to appear.
If a sensor appears out of sync (orange), that means the radio it is attached
to is no longer in sync with the main controller. This may indicate you need
to replace the battery in the radio or interference is preventing the radio
from remaining in sync. After replacing the battery or improving the radio’s
site survey results, use the network reformation button (see ).
Individual Radio (Asset) Status Screen
Select a sensor/radio icon to open that sensor/radio’s status screen. Use the
Back button to return to the previous screen.
Select Vibration Characteristic (1)
Use Select Vibration Characteristic to graph raw data.
Options include Z-Axis Velocity, Z-Axis High-Frequency Acceleration, X-Axis
Velocity, and X-Axis High-Frequency Acceleration. The bottom left of the
screen shows a real-time readout of the selected characteristic. Velocity is
displayed in in/s (mm/s for Vibemetric versions) and acceleration is displayed
in g. Note: Velocity values of 6.5535 and/or acceleration values of 5.355
indicate a sensor error. The system ignores these data points to avoid
affecting the saved baseline or trended data. The system will not baseline
when the raw data values appear as those values. Contact Banner support for
troubleshooting.
Time Scale (2)
Select the Time Scale of the graph from 1 to 168 total hours.
Use the arrow keys to scroll right or left to see different periods of the
collected data. The maximum viewable data on the HMI is 168 hours or 7 days.
The graphing data loggers have a fixed number of data points. If you are using
the DEMO MODE button on the Settings page, the increased sample rate reduces
the number of data points available for viewing until those data points have
rolled off the end of the timeline.
Scale Maximum (3)
Select the data Scale Maximum. For acceleration, the range is 0.25 g to 5 g
(g-force). For velocity, the range is 0.5 in/s to 5 in/s (10 mm/s to 60 mm/s
for metric versions).
Current Alerts (4)
The Current Alerts section shows any warnings or alarms based on the Axis,
Vibration Characteristic, and type (Chronic or Acute) that the system is
detecting.
Acute alerts are those crossing the threshold for five samples in a row (or
the user setting on the Settings screen) and Chronic alerts are when a
100-point moving average crosses the thresholds. Only data from an operational
asset is used to calculate averages and alerts.
Select Temperature (5)
Use Select Temperature to view the temperature graph over the selected time
period.
Directly above the button is the current temperature in degrees Fahrenheit of
the selected Node. The readout color is white if it’s nominal, yellow if it’s
in a warning state, and red if it’s in an alarm state. The warning and alarm
temperature settings are 158 °F and 176 °F respectively. A raw temperature
value of 327.67 indicates a sensor error. Contact Banner’s technical support
for troubleshooting.
Select Current (6)
Use Select Current to view the current graph over the selected time period.
Directly to the right of the button is the raw current reading in Amps of the
selected Node. The readout color is white if it’s normal, yellow if it’s in a
warning state, and red if it’s in an alarm state. Requires the use of the
Banner CM1L Condition Monitoring VT/CT node. This option only appears if
Enable Current Measurements is turned on within the Settings screen. Warning
and alarm settings are set on the Current Alarm Settings screen within the
Settings page.
In the upper right corner of the screen is the Sensor’s Modbus ID and the
radio ID to which the sensor is attached. This can be useful in finding which
radio a sensor is connected to if the orange Out of Sync status icon appears.
The signal quality or battery replacement may be necessary for a radio that
loses connection status.
Settings Screen
Acute Alarm Samples
The default number of samples above the warning or alarm threshold before an
alert is triggered is five consecutive samples. Use the numeric entry box to
adjust the default value up or down.
Asset Baselining
Nodes bound into the system automatically begin baselining. This button opens
a screen to enable the creation of new baselines and thresholds of each sensor
Node individually, displays the remaining samples in the current baseline, and
allows manual threshold limits to be set for both vibration and temperature on
each sensor Node (see Baseline a Sensor/Radio (Asset) on page 6).
Baseline Samples
The Solutions Kit takes a baseline of the first 300 running samples of an
asset. This can be adjusted up or down by clicking on this numeric entry box
to any desired sample. Samples are taken at a fixed 5-minute interval.
Binding
Opens a screen to allow the binding of each sensor Node to the Solutions Kit
(see Bind the Nodes (Assets) on page 5).
DEMO MODE
Use only for demonstration purposes when fast sampling is required. Demo mode
enables the Teach mode on all the bound sensor Nodes, putting them into a
2-second sample rate and changing the HMI graphs to log at a 2-second sample
rate for 15 minutes (status indicated by the green light within the button).
We also recommend you reduce the Baseline Samples to less than 30 for
demonstration purposes. Using Demo Mode drains the battery faster and creates
a larger log file that fills up memory quicker, so only use this mode when
demonstrating the kit, not during standard operation.
Enable Cloud Pushing
Turn ON/OFF the switch to enable the DXM to begin pushing data to a cloud
webserver at 5-minute intervals. This requires additional setup and
modification of the XML file in the DXM to point to the correct web server
with the correct site ID. Cloud pushing also requires connecting the DXM to a
local network via Ethernet or a separately sold cellular modem.
Enable Current Measurements
Turn ON this rocker switch when using the Banner VT/CT CM1L Condition
Monitoring Node to enable current measurements and graphs on individual asset
screens. This setting also enables the Current Alarm Settings button below the
rocker switch to set the scale, warning, and alarm settings for the current
measurements on each Node.
Enable Password for Settings (Lvl 8)
Turn ON/OFF the switch to enable/disable a password to access the settings
menu. The default password for User Level 8 is “88888888”. This can be
modified by clicking the Password Table button above and changing the password
for level 8 to any number password up to 9 numbers long.
HMI Options
Provides the ability to copy/manage HMI log files, HMI configuration for
advanced options, functional HMI options, and an Icon Legend as well as a
Graph Legend.
Site Survey
Opens a screen to perform a site survey on any sensor Node bound to the
Solutions Kit network (see Perform a Site Survey on page 5).
Time until next sample (s)
Displays the time (in seconds) until the Solutions Kit samples data from all
bound sensor Nodes and updates graphs and other visual indicators.
Vibration Node Binding Screen
Bind the Nodes (Assets)
Bind the Banner Wireless Q45 or P6(L) Nodes combined with Banner’s QM42VT
Vibration and Temperature Sensors or the Q45VA All-in-One Vibration Sensor
Node to the DXM Wireless Controller to begin communicating.
Follow these instructions to assign the Q45/P6 Nodes a Node address and begin
communicating with the DXM Controller. Nodes and sensors are purchased
separately and after they are combined, must be bound individually. A new
Q45/P6 Node and sensor can be added to the network at any time by using the
binding procedure.
-
On the HMI screen, touch the ON/OFF rocker switch for the desired Node to turn on binding.
-
On the Node, enter binding mode.
• For Q45 models, triple-click the binding button under the lid.
• For P6 or P6L Node Models, triple-click button 2. For the P6, follow the Node’s datasheet to set the rotary dials before entering binding mode.
After the Node is bound, the LEDs stay solid momentarily, then flash four times. The Node automatically exits the binding mode. -
On the HMI screen, touch the same ON/OFF rocker switch to turn the switch off to take the DXM out of binding mode.
After the DXM is out of binding mode, the indicator LED on the Node flickers green when the Node is in sync with the DXM. -
Repeat steps 1 through 3 for as many Nodes as are needed for the network. Use the Nodes #1-20 and Nodes #21-40 tabs to access binding switches for up to 40 sensor Nodes.
Entering binding mode causes all Nodes to go out of sync until the DXM exits the binding mode. The Nodes will resume communicating with the DXM within a few seconds.
Vibration Node Site Survey Screen
Perform a Site Survey
Perform a site survey on each Node after they are installed to analyze the
wireless communication between the Nodes and DXM.
-
On the HMI, touch the ON/OFF rocker switch for the desired Node to turn on Site Survey mode for that Node.
If the Node is communicating with the DXM, the results display at the bottom of the HMI screen. The results add up to a total of 100. It takes several seconds for the first 100 packets to display complete results. -
Follow the interpreting section of the Conducting a Site Survey and Interpreting the Results (bannerengineering.com) technical note on www.bannerengineering.com.
-
After the site survey is complete, touch the ON/OFF rocker switch to turn Site Survey mode off.
-
Repeat for each additional Node.
Use the tabs Nodes #1-20 and Nodes #21-40 to access site survey switches for up to 40 sensor Nodes. Note that entering site survey mode causes all the Nodes to go out of sync with the DXM until the DXM exits Site Survey mode. The Nodes will resume communicating with the DXM within a few seconds.
Baseline a Sensor/Radio (Asset)
After the sensor/radio is installed and the system is powered on, the software
automatically begins collecting data and determines if the asset is running.
The software generates a baseline and thresholds based on the first 300 data
samples or about 24 hours of asset running time (unless modified on the
Settings page).
When an asset is replaced, repaired, or has heavy maintenance done, create a
new baseline. If the sensor is moved after the initial baseline is calculated,
generate a new baseline.
-
Turn on baselining for the appropriate Nodes if a new baseline needs to be generated.
The initial baseline is generated any time a new sensor is connected to the system (or bound to the controller radio) and begins sending data without the need to trigger these switches. The number of baseline samples remaining displays next to the ON/OFF switch. The baseline switch remains on during baselining and resets to off after the baseline is complete. -
Use the tabs Assets #1-10, Assets #11-20, Assets #21-30, and Assets #31-40 to access the baseline switches for the sensors/radios.
-
Use the corresponding Manual Warning & Alarm Adjustments button for each sensor/radio to open an individual windowed screen where current baseline threshold settings are visible.
-
Touch the numeric entry box in any of the New Settings rows to manually enter a new value for any or all the warning or alarm thresholds, including temperature.
-
Set vibration settings back to zero to use the original baseline setting.
-
Manually set the temperature back to the baseline set by entering 158 °F (70 °C) for warning or 176 °F (80 °C) for alarm.
Temperature is not a baseline value. Although it displays a baseline value, the value is for reference if the new setting is changed.
Current Alarm Settings Screen
After enabling the Current measurements rocker switch, users are able to
adjust the CT scale, current warning, and alarm measurements. The CT scale
from the DIP switch settings of the Condition Monitoring VT/CT Node is read
and populated into the scale field.
CT Scale
The default setting will be based on the DIP switch setting of the Condition
Monitoring Node. If the user replaces the 20A or 150A CT provided with the
Condition Monitoring Node, adjust the scale manually.
Current Warning
Set the warning level for the current data to trigger yellow motor icons when
in a warning state.
Current Alarm
Set the alarm level for the current data to trigger red motor icons when in an
alarm state.
Use the Nodes #1-10, Nodes #11-20, Nodes #21-30, and Nodes #31-40 tabs to
access the scale, warning, and alarm settings for up to 40 Sensor Nodes.
HMI Options Menu Screen
The HMI Options screen provides some added HMI functionality along with icons
and graph legends.
The HMI also provides data logging of all the raw data, baselines, and
thresholds. This data is saved to a file every 10 minutes and a new file is
generated every day and stored in monthly folders. The HMI has storage for
about 75 days of log files.
Auto Delete Files Older than ‘X’ Days
The HMI auto deletes files older than the selected number of days.
Default is 30 days with a maximum of 45 days for MulitHop radio kits and 60
days for Performance radio kits.
Copy Log Files to USB Drive
Plug a USB drive into the back of the HMI and click here to select the log
files or folders to copy.
HMI System Setup
Enters HMI Panel Setup.
Use for setting Time, Date, and Advanced Options. Entering this screen will
clear any logged data from the graphs but will not clear any data saved to
files.
Manually Delete Files Older than ‘X’ Days
Deletes files older than a specified number of days immediately.
Use this option if the HMI is warning about an inability to save data or a
lack of storage space. Shortening the auto delete days parameter may be
necessary.
Re-Initialize HMI Non-Volatile on Restart
Flip the switch to ON before restarting the HMI to reinitialize default
settings and labels.
Restart HMI Application
Restarts the HMI application, which clears all graphed data but retains the
saved logs.
Stop Operation Safely
Stops HMI operation safely without data corruption before you power off the
HMI.
Always use this button before powering down to avoid data file corruption. If
a Failed to write logged data to file or Failed to save message appears, this
is because of a power loss during the saving process. You must delete this
file (from the day of the power loss) by using the HMI System Setup menu.
Install a Warning or Alarm Light
Add a tower light or indicator light (such as a K70, TL50, TL70, etc.) to the
solution box for added local indications of all clear, warnings, or alarms.
The DXM Controller uses PNP outputs with a maximum of 100 mA per output. An
interposing relay may need to be added to accommodate higher amperage lights.
- Cut a hole in the box and mount the light accordingly.
- Wire the DC ground to the light or an interposing relay from the bottom row of the gray two-row terminal blocks inside the Solutions Kit on the DIN rail adjacent to the DXM Controller.
- Wire the input of the light or interposing relay to the DXM.
a) O1 – Pin 5 – indicates a radio/asset in an Alarm condition
b) O2 – Pin 6 – indicates a radio/asset in a Warning condition
c) O3 – Pin 7 – indicates a radio/asset in either a Warning or an Alarm condition
d) O4 – Pin 8 – indicates no Warning or Alarm conditions exist
Connect the DXM and HMI to a Wide Area Network (WAN)
By default, the HMI and DXM Controller is configured to communicate using
static IP addresses. To connect to a WAN, configure the two devices to have a
new static IP address on the new network or to acquire their own IP address
via DHCP.
Connecting to a WAN allows the devices to be configured by any computer on the
network and allows the DXM to be configured to push data to a cloud web server
for remote monitoring.
Figure 1. Panel setup HMI screen![BANNER DXM700-B1R1 Wireless Controller
-
Panel setup](https://manuals.plus/wp-content/uploads/2022/08/BANNER- DXM700-B1R1-Wireless-Controller-Panel-setup.png)
-
Open the Solution Kit’s enclosure and connect an ethernet cable from the WAN to the ethernet switch inside the enclosure.
-
On the DXM: With power applied to the DXM, use the arrow keys to select System Config. Press Enter.
-
Use the arrow keys to select Ethernet.
-
Set the IP address.
• If you are using a static IP address, select the IP address shown and press Enter. Then use the arrow and Enter keys to set the new static IP address.
• If you are using DHCP, press Enter on DHCP. Use the arrow keys to select DHCP ON and press Enter.
A device reboot is requested if any changes are made to these settings. -
If you are using DHCP, navigate to the System Info > Ethernet and write down the IP address to enter into the HMI. The subnet mask can be adjusted here as well if needed.
-
On the HMI: From the main screen, go to the HMI Options screen and choose HMI System Setup.
-
In the Panel Setup screen, select General.
-
On the pop-up screen that appears, set up DHCP in one of two ways:
• Type in the IP address and network information for a static IP address by selecting the appropriate fields.
• Toggle from false to true in the field next to Get an IP address automatically, then press OK. -
Press Link 1 and select the IP address field.
-
Enter in the IP address of the DXM from earlier and press OK.
-
Press Run.
-
Push Information to BannerCDS
The DXM Wireless Controller can connect to the Web via Ethernet or an internal
cell module. The controller pushes data from the DXM to be stored and
displayed on a website.
The Banner platform for storing and monitoring the system’s data is
https://bannercds.com. The Banner Cloud Data
Services website automatically generates dashboard icons and graphs for the
application that is populated onto the Dashboard. Email alerts can be
configured using the Alarms screen.
For more information on creating accounts on and using the Banner Cloud Data
Services (CDS) system, please refer to the Banner CDS Quick Start Guide (p/n
404 Not Found
(bannerengineering.com))
or the Instruction Manual (p/n 404 Not Found
(bannerengineering.com)).
Logging into the Web Service
The web server captures data from the DXM Controller using either a cellular
connection or an Ethernet connection. Users collect and view the data or
update and manage the DXM Controller using a web browser.
Within a few minutes of your purchase, you will receive an email with your
authorization code and details regarding the data subscription service. If the
authorization code is not received within 10 minutes, please check your spam
folder or contact Banner Engineering at
1-888-373-6767 to obtain the code.
Use both the website and the DXM Configuration Software to set up and
configure your data collection. Use the latest version of your browser (Google
Chrome is recommended) and enter the URL: h
ttps://bannercds.com. The login page appears.
Create a New Gateway
After you log into the Banner Cloud Data Services website, the Gateway screen
displays. Follow these steps to create a new monitoring site.
-
Click on +New Gateway.
Create a new Gateway/site for each device that will be sending data to the web server.
A Create New Gateway prompt appears. -
Verify Traditionally is selected for the Configuration.
-
Enter a site name.
-
Click Create.
The Gateway/Site appears in the listing of devices on the Gateways screen. -
Click Edit Gateway (pencil icon) next to your Gateway/Site name.
The Gateway detail window appears. -
Copy the Site ID number located at the top of this window.
The Site ID number created by the web server is a required parameter in the configuration of the DXM. The Site ID is the
address the webserver uses to store the data pushed from the DXM. -
Click Save.
Connect to the Software and Download the Existing Configuration
Follow these steps to connect your DXM to the configuration software and
download the existing configuration file from your DXM to your hard drive.
-
On the computer, download the 404 Not Found (bannerengineering.com) from the Banner Engineering website and install it.
-
On the DXM: Apply power to the DXM.
-
Connect the DXM Controller to the computer with a USB cable or skip if the DXM is connected to the same network as the computer.
-
On the computer: Launch the DXM Configuration Software.
-
From the DXM Model drop-down list, select DXM700.
-
On the menu bar, go to Device > Connection Settings.
• If you are using the USB cable, select Serial, then select the COM port that the USB cable is plugged into. Click Connect. If you are unsure which COM port and multiple appear, attempt to connect to each one of them until successful.
• If you are connected to the same network as the DXM, select TCP/IP and enter the DXM IP address. Click Connect. -
After the DXM is connected to the software, click Device > Get XML configuration from DXM to download the current XML file.
-
Name and save the file to the computer.
Configure the DXM to Push Information to the Cloud
-
Within the DXM Configuration Software, go to the Settings > Cloud Services screen.
-
Set the Server name/IP to push.bannercds.net.
-
Select the appropriate Push interface to either Cellular or Ethernet.
• To set up Ethernet, use the Settings > Network screen.
• To set up cellular, refer to the Install and Activate a Cellular Modem (bannerengineering.com) (p/n 205026) technical note. -
Leave the Cloud push interval and Sample count unchanged. The DXM script controls this to push every 5 minutes.
-
Modify the Cloud Permissions for the registers.
Registers are preselected to push to the cloud. Some registers can be removed if you are not using all 40 Nodes. Additional registers can be added by going to the Local Registers tab on the left. The preselected READ registers are 1-200 for the raw Node data, 201-240 for vibration failure mask info, 281-320 for Node connection status, and 5181-5660 for baseline/threshold data. The preselected READ/WRITE registers are 321-360, which are the re-baselining registers. READ/WRITE is used so the Baseline registers can be updated from the website from 0 to 1 to trigger a new baseline remotely.
• Click on each register and edit the Cloud Permissions at the bottom of the screen; or
• Choose the Modify Multiple Registers tab at the bottom of the Local Register screen to edit the Cloud Permissions for a block of registers -
In the Web Server section, keep the Site ID in drop-down selection as GUID and paste the copied ID from the webpage into the Site ID field.
Save and Upload the Configuration File
After making any changes to the configuration, you must save the configuration
files to your computer, then upload it to the device.
Changes to the XML file are not automatically saved. Save your configuration
file before exiting the tool and before sending the XML file to the device to
avoid losing data. If you select DXM > Send XML Configuration to DXM before
saving the configuration file, the software will prompt you to choose between
saving the file or continuing without saving the file.
- Save the XML configuration file to your hard drive by going to the File > Save As menu.
- Go to the DXM > Send XML Configuration to DXM menu.
- If the Application Status indicator is red, close and restart the DXM Configuration Tool, unplug and re-plug in the cable and reconnect the DXM to the software.
- If the Application Status indicator is green, the file upload is complete.
- If the Application Status indicator is gray and the green status bar is in motion, the file transfer is in progress.
After the file transfer is complete, the device reboots and begins running the new configuration.
Upload the XML Configuration File to the Website
To upload an XML configuration file to the website, follow these instructions.
-
At the web server, select the Home screen.
-
On the row displaying your new site, click the Edit Gateway (pencil) icon.
-
Select Update XML.
-
Click Choose File and select the file that was just updated to the DXM and click Save.
After the XML file is loaded into the webserver, the webserver uses the register names and configurations defined in the configuration file. -
Click on the Site Name link to go to the configured registers to see the values uploaded by the DXM.
The same XML configuration files are now loaded on both the DXM and the Website. After some time, the data should be seen on the website.
Completing these steps creates continuity between the site created on the
website with the DXM used in the field. The DXM pushes data to the website,
which can be viewed at any time.
Refer to the Banner Cloud Data Services
(bannerengineering.com)
(p/n 178337) to review all the features available for monitoring, comparing
data, and establishing warnings/alarms on the website.
VNC Viewing on Laptop and Mobile Devices
The Solutions Kit HMI can be viewed and controlled through a VNC application
on either a mobile phone, tablet, or laptop connected to the same network as
the Solutions Kit. Follow the steps in the Tech Note to set up VNC remote
viewing and control: b_4492805.pdf
(bannerengineering.com)
This creates continuity between the site created on the website with the DXM.
If the DXM has a network connection, it will upload data on its next cloud
push interval. Refer to the Banner Cloud Data Services
(bannerengineering.com)l
to review all the features available for monitoring, comparing data, and
establishing warnings/alarms on the website.
To access a Demo version of the website, contact your local Banner distributor
and follow the instructions in the technical note b_4476257.pdf
(bannerengineering.com)
for modified instructions on how to send data to the Demo site.
For additional advanced options using the DXM, such as sending an email or
SMS/text alerts, refer to the Error 404–Not Found
(bannerengineering.com)
on the Banner Engineering website. NOTE: The files used in the Solutions Kit
are slightly different than those used with the Solutions Guide and should NOT
be installed on the DXM being used with the HMI. Use the DXM Configuration
Software and perform a Device > Get XML configuration from DXM to make
modifications to the file pre-loaded to the DXM in the Solutions Kit.
For additional information on any products, visit
www.bannerengineering.com.
Specifications
Radio Range¹
900 MHz, 1 Watt: Up to 9.6 km (6 miles)
2.4 GHz, 65 mW: Up to 3.2 km (2 miles)
Antenna Minimum Separation Distance
900 MHz, 150 mW, and 250 mW: 2 m (6 ft)
900 MHz, 1 Watt: 4.57 m (15 ft)
2.4 GHz, 65 mW: 0.3 m (1 ft)
Radio Transmit Power
900 MHz, 1 Watt: 30 dBm (1 W) conducted (up to 36 dBm EIRP)
2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or equal to 20 dBm (100
mW) EIRP
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
900 MHz Compliance (1 Watt)
Contains FCC ID: UE3RM1809: FCC Part 15, Subpart C, 15.247
Contains IC: 7044A-RM1809
IFT: RCPBARM13-2283
(NOM approval only applies to 900 MHz models)
Supply Voltage
24 V DC (±10%) (use only with a Class 2 (UL) power supply or a Limited Power
Source (LPS) (CE) power supply)
Power Consumption
9 W average; 30 W maximum
Mounting
A mounting system that provides for various mounting options has been provided
with this enclosure.
To connect the mounting brackets, turn the enclosure such that the backside is
visible. Place the mounting brackets over the octagon bosses either
horizontally, diagonally, or vertically, and fasten them with the ¼”-20 x
0.25” SS, countersunk Philips drive screws provided (torque limit = 30 in.
lbs.). The enclosure can be mounted vertically (on a wall) or horizontally
(tabletop)
Certification
| Banner Engineering Europe Park Lane,
Culliganlaan 2F bus 3, 1831 Diegem,
BELGIUM| (CE/UKCA approval only applies to 2.4 GHz models)
---|---|---
| Turck Banner LTD Blenheim House,
Blenheim Court, Wickford, Essex SS11
8YT, Great Britain
2.4 GHz Compliance (DX80-2400 Radio Module)
Radio module is indicated by the product label marking Contains FCC ID:
UE300DX80-2400: FCC Part 15, Subpart C, 15.247
Radio Equipment Directive (RED) 2014/53/EU
Contains IC: 7044A-DX8024
ANATEL www.gov.br/anatel/pt-br/
2.4 GHz Compliance (SX243 Radio Module)
The radio module is indicated by the product label marking Contains FCC ID:
UE3SX243: FCC Part 15, Subpart C, 15.247
Radio Equipment Directive (RED) 2014/53/EU
Contains IC: 7044A-SX243
ANATEL www.gov.br/anatel/pt-br/
Operating Conditions
HMI: 0 °C to +50 °C (+32 °F to +122 °F)
DXM: –40 °C to +85 °C (–40 °F to +185 °F)
DXM LCD: –20 °C to +80 °C (–4 °F to +176 °F)
Micro SD Card (if applicable): –25 °C to +85 °C (–13 °F to +185 °F)
90% maximum relative humidity (non-condensing)
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in
material and workmanship for one year following the date of shipment. Banner
Engineering Corp. will repair or replace, free of charge, any product of its
manufacture that, at the time it is returned to the factory, is found to have
been defective during the warranty period. This warranty does not cover damage
or liability for the misuse, abuse, or improper application or installation of
the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER
EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING
UNDER COURSE OF PERFORMANCE, COURSE OF DEALING, OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of
Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING
CORP. BE LIABLE TO THE BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA
COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL, OR
SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY
TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT,
STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the
design of the product without assuming any obligations or liabilities relating
to any product previously manufactured by Banner Engineering Corp. Any misuse,
abuse, or improper application or installation of this product or use of the
product for personal protection applications when the product is identified as
not intended for such purposes will void the product warranty. Any
modifications to this product without prior express approval by Banner
Engineering Corp will void the product warranties. All specifications
published in this document are subject to change; Banner reserves the right to
modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is
provided in any other language. For the most recent version of any
documentation, refer to:
www.bannerengineering.com.
For patent information, see
www.bannerengineering.com/patents.
¹The radio range is with the 2 dB antenna that ships with the product. High-
gain antennas are available, but the range depends on the environment and line
of sight. Always verify your wireless network’s range by performing a Site
Survey.
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a Class
A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
Industry Canada
This device contains license-exempt transmitters(s)/receiver(s) that comply
with Innovation, Science, and Economic Development Canada’s license-exempt
RSS(s). Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
Mexican Importer
Banner Engineering de Mèxico, S. de R.L. de C.V.
David Alfaro Siqueiros 103 Piso 2 Valle oriente
San Pedro Garza Garcia Nuevo Leòn, C. P. 66269
81 8363.2714
©Banner Engineering Corp. All rights reserved
www.bannerengineering.com
– Tel: + 1 888 373 6767
P/N 215579 Rev. C