IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
-
Toreduce the risk of death, personal injury or property damage from fire, electric shock, falling parts, cutslab rasions, and o nd other hazards please read all wamings and instructions included with and on the future box and all fidure labels.
-
Before instaling, servicing, or performing routine maintenance upon this equipment, follow these general precautions
-
Installation and service of luminaires should be performed by a qualified licensed electrician.
-
Maintenance of the luminaires should be performed by person(s) famillar th the luminaires construction and operation and any hazards involved with Regular fixture maintenance programs are recommended.
-
It will occasionally be necessary to clean the outside of the refractorilens
Frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to user. Refractor lens should be washed in a solution of warm water and arry mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractorilens and clean in above manner, replacing damaged gaskets as necessary -
DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been property packed so that no parts should have been damaged during transit Ihapect to confim. Any part damaged or broken during or after assembly should be replaced.
-
Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov.
-
These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc.
WARNING RISK OF ELECTRIC SHOCK
- Disconnect or tum off power before installation or sarvioing.
- Verify that supply voltage is correct by comparing it with the luminaire label Information.
- Make all electrical and grounded connections in accordance with the National Electrical Code (NEC) and any applicable local code requirements.
- All wiring connections should be capped with UL approved recognized wire connectors
CAUTION RISK OF INJURY
- Wear gloves and safety glasses at all smes when removing luminaire from carton, installing, servicing or performing maintenance.
- Avoid direct eye exposure to the light source while it is on.
WARNING RISK OF BURN
- Allowlamp/fixture to cool beforehandling. Donottouchenclosure orlight source.
- Do not exceed maximum wattage marked on luminaire label.
- Follow all manufacturer’s warmings, recommendations and restrictions for driver type, burning position, mountinglocations/methods, replacementandracycling.
CAUTION RISK OF FIRE
- Keep combustible and other materials that can bum, away from lampfens
- Do not operate in close proximity to persons, combustible materials or substances affected by heat or drying.
CAUTION: RISK OF PRODUCT DAMAGE
- Never connect components under load.
- Do not mount or support these fixtures in a manner that can cut the outer jacket or damage wire insuladon.
- Unless individual product specifications deem otherwise: Never connectan LED product to dimmer packs, occupancy sensors, timing devices, or other related control devices. LED fixtures must be po powered directly off a switched circuit.
- Unless individual product specifications deem otherwise: Do not restrict fixture ventiation. Allow for some volume of airspace around fixture. Avoid covering LED faxtures with insulation, foam, or other material that will prevent convection or conduction cooling.
- Unless individual product specifications deem otherwise: Do not exceed fixtures maximum ambient temperature Only use fixture in its intende ple use fixture in its intended location anded location.
- LED products are Polarity Sensitive. Ensure proper Polarity before installation.
- Electrostatic Discharge (ESD) ESD can damage LED fixtures. Personal grounding equipment must be womduring all installation or servicing of the unit.
- Do not touch individual electrical components as this can cause ESD shorten lamp life, or alter performance.
- Some components inside the fixture may not be serviceable. In the unlikely dare may not be event your unit may require ser rvice, stop using g the unit immediately and contact an ABL representative for assistance.
- Always read the fixtures complete installation instructions prior to installation for any additional fixture specific warmings.
- Verify that power distribution system has proper grounding. Lack of proper earth ground can lead to fixture failure and may void warranty
All luminaires that contain electronic devices that generate frequencies above 9kHz from any component within the luminaire comply with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation.
Failure to follow any of of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com. Acuity Brande Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.
ABL LED General Warnings. Form No. 503.203
©2010 Acuity Brands Lighting, Inc. All rights reserved. 12/01/10
BE UNIVERSAL LED EXIT SIGN
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Package Contents
SURFACE MOUNT OPTION
Part| Description| Quantity
1| Housing Assembly| 1
2| Mirrored Exit Sign (Double Face)| 1
3| Mirrored Backplate (For Single Face)| 1
4| Canopy| 1
5| Crossbar| 1
6| Snap Assemblies (5 Male & 5 Female)| 5
7| Canopy Screw (ST3.5 X 16 mm)| 3
8| Canopy Crossbar Screw (M4 X 20 mm)| 3
9| Canopy J-Box Screw (6-32 X’ “)| 3
10| Canopy J-Box Screw (8-32 X’ “)| 3
11| Wall Anchor Screw (ST4 X 20 mm)| 3
12| Wall Anchors| 3
13| Wire Nuts| 2
14| Chevrons| 2
UNIVERSAL MOUNT OPTION
(INCLUDES ALL SURFACE MOUNT PARTS)
15| Recess Bracket| 1
16| Trim Plate| 1
17| Trim Plate Insert with Test Button and Status LED Mounts| 1
18| Trim Plate without Test Button and Status LED Mounts| 1
19| Recess J-Box| 1
20| J-Box Screw (ST3.5 X 5 mm)| 3
21| Trim Plate Screws (M4 X 5 mm)| 3
22| Recess Bracket Screws (ST4 X 12 mm Hex Head)| 5
23| Status LED Bushing| 1
Recommend junction boxes
- 4″ Sq with plaster ring
- 3.5″ Round using crossbar
- Single Gang
Warnings and Cautions
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Review the diagrams thoroughly before beginning.
- All electrical connections must be in accordance with local codes, ordinances, and the National Electric Code. If you are unfamiliar with methods for installing electrical wiring, secure the services from a qualified licensed electrician.
- Before starting the installation, disconnect the power by turning off the circuit breaker.
- Do not use outdoors. Suitable for use in 32°F to 104°F(0°C-40°C) indoor damp locations.
- Do not mount near gas or electric heaters.
- Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or eyes, flush acid with fresh water and contact a physician immediately.
- Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for other than its intended use.
- All service should be performed by qualified personnel only.
- Allow battery to charge for 24 hours before first use.
- After switch position has been selected for the chosen application (AC ONLY or BATT), do not attempt to adjust switch position without knowledge of application and an understanding of the switch behavior in product.
SAVE THESE INSTRUCTIONS
NOTE: First turn off electricity.
Recessed Ceiling Mount Battery Backup
- Position recessed kits and bar hangers between joists. Make sure bar hangers are in the correct position and level with the bottom of the joists. Hammer in temporary “nail in” tabs on hanger to hold in place and then secure permanently with the included Recess Bracket Screws for metal joists or wood (ST4 x 12 mm Hex Head and torque to 5.3 in lbs (0.6 Nm)). Adjust recessed kit vertically to the desired position and then tighten all screws. The recommended opening in the surface is 3.5” x 15” rectangle. Max distance between Ceiling Joist is 18.5”.
- Use screwdriver to gently open the front cover.
- EL models only: Slide the battery switch to “BATT” Position. (Product is shipped in AC ONLY position)
- Remove top hole plug.
- Feed AC supply wires through the center hole.
- Snap the front cover back in place.
- Install recess J-Box that is included with the unit by feeding wires through the J-Box and install with the included J-Box Screws (ST3.5 X 5 mm and torque to 5.3 in lbs (0.6 Nm)) which are shipped inside Universal Mount Accessory Kit located inside the J-Box
- Remove the end cap with the Test Switch and Status LED using a #1 Philips Screwdriver. Be careful as the end cap also holds the Light Bar and Sign Ratchet. Remove the Test Button by unplugging the Test Button Connector, pinching the lever locks on the inside of the End Cap, and pushing the Test Button through the End Cap. Remove the Status LED from the Status LED Mounting Bushing by gently pushing the Status LED back through the End Cap. Route the Status LED through the larger Test Button hole. Reinstall the End Cap with the same screws (ST3.0 X 10 and torque to 5.3 in lbs (0.6 Nm)) making sure the wires from the Test Button and Status LED are pulled through the Test Button hole.
- Make the electrical connections to the unit inside the J-Box (see wiring diagram). With a strain relief provided by the contractor and secure the lid of the J-Box with the J-Box to J-Box Screw (M4 x 5 and torque to 5.3 in lbs (0.6 Nm)).
- In preparation for the next step, route Status LED harness and Test Button harness through Recess Bracket between the Trim Plate Mounting Tab and Spring Clip, which is shown in the picture below.
- Install the light fixture into the Recess Bracket making sure not to pinch any wires. Tip: Keep the body of the light fixture close to the same plane as the ceiling surface for easier installation.
- Install the Trim Plate Insert with Test Button and Status LED Mounts into the Trim Plate. Push the Test Button into the trim plate front side until lock ramps snap in place and reconnect connector. Insert the Status LED Bushing into the front side of trim plate and push Status LED into bushing from backside of trim plate.
- Reconnect test button connector.
- Install Trim Plate with included Trim Plate Screws (M4 X 5 mm and 3.54 in lbs (0.4 Nm)) which are shipped inside Universal Mount Accessory Kit located inside the J-Box.
- If a single sided panel is wanted, remove all 4 snaps (shipped without snaps installed) gently with a tool that will not scratch the sign. Remove clear film off shiny side of back panel and line up back panel with shiny side out. Apply snaps by squeezing them in place in the same orientation. If a double sign is wanted add snaps without back panel.
- Insert panel into main body assembly gently. Make sure the Chevron orientation is correct by peeling unnecessary Chevron(s) off with finger and clean any residue off surface with Pledge Furniture Polish (recommended).
NOTE: First turn off electricity.
Recessed Ceiling Mounting AC Only
- Position recessed kits and bar hangers between joists. Make sure bar hangers are in the correct position and level with the bottom of the joists. Hammer in temporary “nail in” tabs on hanger to hold in place and then secure permanently with the included Recess Bracket screws for metal joists ST4 x 12 mm Hex Head and torque to 5.3 in lbs (0.6 Nm)) which are shipped inside Universal Mount Accessory Kit located inside the J-Box. Adjust recessed kit vertically to the desired position and then tighten all screws. The recommended opening in the surface is 3.5” x 15” rectangle.
- Use a screwdriver to gently open the front cover.
- Verify switch is in the AC Only Position. (Product is shipped in AC ONLY position)
- Remove top hole plug.
- Feed AC supply wires through canopy center.
- Snap the front cover back in place.
- Install Recess J-Box that is included with the unit by feeding wires through the J-Box and install included J-Box Screws (ST3.5 X 5 mm and torque to 5.31 in lbs (0.6 Nm)) which are shipped inside Universal Mount Accessory Kit.
- Make the electrical connections to the unit inside the J-Box (see wiring diagram), with a strain relief provided by the contractor and secure the lid of the J-Box with the J-Box to J-Box Screw (M4 x 5 and torque to 5.3 in lbs (0.6 Nm)).
- Install the light fixture into the Recess Bracket making sure not to pinch any wires. Push the unit evenly into recess bracket by engaging both springs on the recess bracket. Tip: keep the body of the light fixture close to the same plane as the ceiling surface for easier installation.
- Insert the Trim Plate Insert without Test Button and Status LED Mounts into the Trim Plate.
- Install Trim Plate with included Trim Plate Screws (M4 X 5 mm and 3.54 in lbs (0.4 Nm)) which are shipped inside Universal Mount Accessory Kit located inside the J-Box.
- If a single sided panel is wanted, remove all 4 snaps (shipped without snaps installed) gently with a tool that will not scratch the sign. Remove clear film off shiny side of back panel and line up back panel with shiny side out. Apply snaps by squeezing them in place in the same orientation. If a double sign is wanted add snaps without back panel.
- Insert panel into main body assembly gently. Make sure the Chevron orientation is correct by peeling unnecessary Chevron(s) off with finger. Clean any residue off surface with Pledge Furniture Polish (recommended).
Recessed Assembly Drawing
Ceiling & Wall Mounting
-
Use screwdriver and gently open front cover.
-
EL models only: Slide the battery switch to “BATT” Position. If AC Only the Switch should remain in the AC Only Position. (Product is shipped in AC ONLY position.)
-
Remove top hole plug.
-
Feed AC Supply wires through the canopy center hole.
-
Snap the front cover back in place.
-
Install Canopy that is included with the unit by feeding wires through the Canopy and install with included Canopy Screws (ST3.5 X 16 mm and torque to 5.3 in lbs (0.6 Nm)) which are shipped inside Surface Mount Accessory Kit.
-
Install unit per configuration 1 with Crossbar, or configuration 2 without Crossbar. Canopy Crossbar Screws (M4 X 20 mm and torque to 7.0 in lbs (0.8 Nm)), and Canopy J-Box Screws (6-32 X 1/2” and torque to 7.0 in lbs (0.8 Nm)) are included in the Surface Mount Accessory Pack Kit. Remember to tuck wires neatly into J-Box. CONFIGURATION 1:
CEILING MOUNT WITH CROSSBAR
(IF J-BOX HOLES DO NOT LINE UP WITH CANOPY HOLES) CONFIGURATION 2:
CEILING MOUNT WITHOUT CROSSBAR
(IF J-BOX HOLES DO LINE UP WITH CANOPY HOLES) -
If a single sided panel is wanted, remove all 4 snaps (shipped without snaps installed) gently with a tool that will not scratch the sign. Remove clear film off shiny side of back panel and line up back panel with shiny side out. Apply snaps by squeezing them in place in the same orientation. If a double sign is wanted add snaps without back panel.
-
Insert panel into main body assembly gently. Make sure the Chevron orientation is correct by peeling unnecessary Chevron(s) off with finger and clean any residue off surface with Pledge Furniture Polish (recommended).
-
The unit can be installed on any surface, the panel can rotate along the axis of rotation to accommodate different surface angles. WALL SURFACE
(SIGN IS ROTATED PARRALEL TO WALL)
Ceiling and Wall Assembly Drawing
NOTE: First turn off electricity. (J-Box, Plaster Ring and J-Box Mounting screws are not included)
Surface End Mounting
-
Use screwdriver to gently open front cover and pull out the AC supply wires.
-
EL models only: Switch the battery switch to “BATT” Position. If AC Only the Switch should remain in the AC Only Position. (Product is shipped in AC ONLY position).
-
Ensure the top hole is covered with Top Cover Plug.
-
Remove the hole plug from mounting end cap (opposite the endcap containing the Test Switch). Plug may be removed by pressing the cover from the inside with finger or screwdriver into center section of plug.
-
Feed the AC supply wires through the center hole of end cap.
-
Snap front cover back in place.
-
Assemble canopy onto main body assembly with Canopy Screw (ST3.5 X 16 mm and torque to 5.3 in lbs (0.6 Nm)) which are shipped inside Surface Mount Accessory Kit.
-
Install unit per configuration 1 with Crossbar, or configuration 2 without Crossbar. Canopy Crossbar Screws (M4 X 20 mm and torque to 7.0 in lbs (0.8 Nm)), and Canopy J-Box Screws (6-32 X 1/2” and torque to 7.0 in lbs (0.8 Nm)) are included in the Surface Mount Accessory Pack Kit. Remember to tuck wires neatly into J-Box. CONFIGURATION 1:
SIDE MOUNT WITH CROSSBAR
(IF J-BOX HOLES DO NOT LINE UP WITH CANOPY HOLES) CONFIGURATION 2:
SIDE MOUNT WITHOUT CROSSBAR
(IF J-BOX HOLES DO LINE UP WITH CANOPY HOLES) -
If a single sided panel is wanted, remove all 4 snaps (shipped without snaps installed) gently with a tool that will not scratch the sign. Remove clear film off shiny side of back panel and line up back panel with shiny side out. Apply snaps by squeezing them in place in the same orientation. If a double sign is wanted add snaps without back panel.
-
Insert panel into main body assembly gently. Make sure the Chevron orientation is correct by peeling unnecessary Chevron(s) off with finger and clean any residue off surface with Pledge Furniture Polish (recommended).
Surface End Assembly Drawing
Wire Diagram
Testing
National Electric Code (NEC) and NFPA life safety code regulations require
that routine tests need to be performed as listed below:
Once every month, the unit needs tested for duration of 30 seconds.
- Push in and hold the test switch to perform the test.
Once every 12 months, a full 90-minute (per UL requirements) test needs to be performed on the unit.
- Remove Power to the unit and leave in the emergency mode. The lamps should stay ON for at least 90 minutes.
Operation
CAUTION: Battery Backup Orientation – Switch in the “Batt” position: The
battery in this unit may not fully charged. After electricity is connected to
the unit, let battery charge for at least 24 hours, then normal operation of
this unit should take effect.
- Apply AC power to the sign. The LED indicator should turn GREEN.
- After the battery has been left to charge for 2 hours, test the sign by pushing the test button. The LED Status light turns OFF and the sign should remain ON.
- When the switch is released, EXIT section remains ON and the LED indicator turns back to GREEN.
- When battery is disconnected the Status LED turns RED.
Chevron(s)
If a Chevron(s) needs to be reapplied peel the back of Chevron tab(s) and
place Chevron tab(s) on panel using dimensions shown with main part of the tab
aligned to the edge of the sign. Carefully peel off the tab around the
chevron. If Mirrored Back Plate needs to be removed refer to step 9. Remove
any bubbles that may present themselves on the Chevron(s)
Panel Removal
If the panel should need to be removed turn off electricity. If the unit is
recessed mounted remove trim plate first and pull unit from recess bracket.
Loosen the End Cap Screws with a No 1 Phillips Screwdriver on the side with
the Test text to remove the End Cap from the main body. Be careful as the End
Cap also holds the Sign Ratchet, the Led Board Holders, and the LED Board in
place. Reinstall the end cap with the same screws (ST3.0 X 10 and torque to
5.3 in lbs (0.6 Nm)). When reassembling insert the Exit Sign in last.
Ceiling Mounting Dimensions
End Mounting Dimensions
Recess Mounting Dimensions
LIFE SAFETY SOLUTIONS
TEL: 800-705-SERV (7378)
techsupport-emergency@acuitybrands.com
www.lithonia.com
Part # 912-00477-001
Rev A, 1/2024
© Acuity Brands Lighting, Inc. 2018
All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>