LUTRON HJS-0-FM VIVE Networking Wireless HUB User Guide
- June 3, 2024
- Lutron
Table of Contents
LUTRON HJS-0-FM VIVE Networking Wireless HUB
TYPICAL HUB – AS REQUIRED FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLE BACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOOR
HJS-0-FM
VIVE HUB
W/ CLEAR CONNECT & TIMECLOCK 24V POWER SUPPLY & ADAPTER INCLUDED SEE SPEC
SHEET FOR MOUNTING REQUIREMENTS COMMUNICATES W/ CLEAR CONNECT DEVICES WITHIN
71′[22m] RADIUS
TYPICAL SENSORS & REMOTE CONTROLS CAN BE A MAX OF 30′ TO LOAD DEVICES – MAX OF 71′ FROM VIVE HUB AND LOCATED ON THE SAME FLOOR
TYPICAL LOAD DEVICES CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME
FLOOR
TYPICAL WALLBOX LOAD CONTROLS CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON
SAME FLOOR
FRONT OF HOUSE RETAIL AREA
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
RMJS-8TN-DV-B
POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS:
3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD
AS REQUIRED FOR ELV ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING
MRF2S-6ELV120-GR
MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE DIGITAL FADE DIMMER 120V, 600W
ELECTRONIC LOW-VOLTAGE PLENUM RATED (MOUNTS TO 2 GANG JBOX BY OTHERS)
LOCATION TBD
AS REQUIRED FOR LED/INC ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING
MRF2S-6CL-GR
MAESTRO WIRELESS
MULTI-LOCATION/SINGLE-POLE
CL DIMMER, 120V~ 150 W DIMMABLE CFL/LED/ 600W INCANDESCENT/HALOGEN PLENUM
RATED (MOUNTS TO 2 GANG JBOX BY OTHERS)
LOCATION TBD
AS REQUIRED FOR TRIAC/MLV ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING
MRF2S-6ND-120-GR
MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE SPEC GRADE DIMMER 120V, 600W/VA
INCANDESCENT/HALOGEN *NEUTRAL WIRE REQUIRED PLENUM RATED (MOUNTS TO 2 GANG
JBOX BY OTHERS)
LOCATION TBD
AS REQUIRED FOR DIMMING SCENE CONTROL UP TO 10 PER MODULE
PJ2-4B-GWH-XXX
434 MHZ PICO WIRELESS 4 BUTTON CONTROL SHOWN WITH CW-1-WH CLARO WALLPLATE *SEE
SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD
AS REQUIRED FOR SECOND FLOOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE
LRF2-DCRB-WH
434MHZ WIRELESS DAYLIGHT SENSOR 1.6″[40,6mm] (DIA) X 0.7″[17,8mm] (D) *DEVICE
IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD
BREAK ROOM
AS REQUIRED FOR VACANCY SENSING UP TO 10 PER MODULE
LRF2-VCR2B-P-WH
434MHZ WIRELESS VACANCY SENSOR 3.57″[90,7mm] (DIA) X 1.13″[28,7mm] (D) MAX 10
PER QSM *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER
FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH RECESS MOUNT KIT FOR NON-METALLIC CEILINGS)
FOR USE WHEN DAYLIGHT SENSING IS REQUIRED
AS REQUIRED FOR DIMMING ZONE CONTROL TYPICAL OF 1 PER DIMMING ZONE
PJ2-3BRL-GWH-XXX
434 MHZ PICO WIRELESS, LIGHT 3 BUTTON CONTROL WITH RAISE/LOWER SHOWN WITH
CW-1-WH CLARO WALLPLATE *SEE SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING
OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
RMJS-8TN-DV-B
POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS:
3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD
AS REQUIRED FOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE
LRF2-DCRB-WH
434MHZ WIRELESS DAYLIGHT SENSOR 1.6″[40,6mm] (DIA) X 0.7″[17,8mm] (D) *DEVICE
IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD
OR
AS REQUIRED FOR NON-DIM ZONE CONTROL TYPICAL OF 1 PER NON-DIM ZONE
PJ2-2B-GWH-XXX
434 MHZ PICO WIRELESS 2 BUTTON CONTROL SHOWN WITH CW-1-WH CLARO WALLPLATE *SEE
SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD
FOR USE WHEN DAYLIGHT SENSING IS NOT REQUIRED
RMJS-16R-DV-B
POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH RELAY
DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD
STORAGE ROOMS
AS REQUIRED FOR NON-DIMMING ZONE CONTROL
MRF2S-8SSV-WH
120/277V~, 50/60 Hz MAESTRO SENSOR SWITCH VACANCY SENSOR SINGLE POLE/MULTI-
LOCATION *NEUTRAL WIRE REQUIRED MANUAL ON/AUTO OFF (1 GANG US BACKBOX BY
OTHERS)
LOCATION TBD
AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL
MRF2S-8SDV010-WH
120/277V~, 50/60 Hz MAESTRO SENSOR 0-10V DIMMER VACANCY SENSOR SINGLE POLE
/MULTI-LOCATION *NEUTRAL WIRE REQUIRED MANUAL ON/AUTO OFF (1 GANG US BACKBOX
BY OTHERS)
LOCATION TBD
AS REQUIRED FOR ADDITIONAL VACANCY SENSING COVERAGE
LRF2-VCR2B-P-WH
434MHZ WIRELESS VACANCY SENSOR 3.57″[90,7mm] (DIA) X 1.13″[28,7mm] (D) MAX 10
PER QSM *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER
FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH RECESS MOUNT KIT FOR NON-METALLIC CEILINGS)
TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH GENERATOR SYSTEMS
AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY 0-10V LOADS
RMJS-8T-DV-B-EM
NORMAL/EMERGENCY POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL
DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D)
(87mm X 72mm X 32mm)
LOCATION TBD
AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY NON-DIM LOADS
RMJS-16R-DV-B-EM
NORMAL/EMERGENCY POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH
RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
D RMJS-16R-DV-B-EM NORMAL/EMERGENCY POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/
(1) 16A SOFTSWITCH RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (
TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH EITHER GENERATOR OR INVERTER SYSTEMS PROVIDED BY LVS CONTROLS – CONTACT YOUR LUTRON REPRESENTATIVE FOR MORE INFORMATION
AS REQUIRED FOR UL 924 COMPLIANCE
LUT-SHUNT-D
LVS CONTROLS SHUNT RELAY FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO
APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
AS REQUIRED FOR UL 924 COMPLIANCE
LUT-SHUNT
LVS CONTROLS SHUNT RELAY FOR USE WITH LINE VOLTAGE SWITCHING AND DIMMING LOADS
REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
AS REQUIRED FOR UL 924 COMPLIANCE
LUT-ALCR-D
LVS CONTROLS ALCR DEVICE FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO
APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
AS REQUIRED FOR UL 924 COMPLIANCE
LUT-ALCR
LVS CONTROLS SHUNT RELAY FOR USE WITH SWITCHING LOADS REFER TO APPLICATION
NOTE #628 FOR DETAILED WIRING DIAGRAMS
AS REQUIRED FOR UL 1008 COMPLIANCE
LUT-ATS-D
LVS CONTROLS TRANSFER SWITCH FOR USE WITH LINE VOLTAGE DIMMING LOADS REFER TO
APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS
WIRING LEGEND:
| INPUT POWER (NORMAL-EMERGENCY)
---|---
| INPUT POWER (NORMAL)
| 2 #12AWG (4 mm2)
| 0-10V SIGNAL: 2 #18AWG (1.0 mm2)
| 1-WAY RF COMMUNICATION
| 2-WAY RF COMMUNICATION
CONCEPT DRAWING NOTES:
CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT
INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS
AND QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE
LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL
SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE
VERIFIED IN ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW
SCHEDULES/DETAILS.
LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL. LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS COMBINATION
TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON’S PRODUCT COMPATIBILITY MATRIX ON-LINE AT WWW.LUTRON.COM/LED.
TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT LEDS@LUTRON.COM.
LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME LED DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. PLEASE REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. ELV PRODUCTS PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS OR LUTRON HI-LUME 1% 2-WIRE DRIVERS ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION.
LUTRON NOTES:
ALL DIMMING BALLASTS TO BE LUTRON ECOSYSTEM, ECOSYSTEM H-SERIES, OR HI-LUME 3D
TYPE UNLESS OTHERWISE NOTED.
ALL DIMMING DRIVERS TO BE LUTRON ECOSYSTEM DRIVERS: HI-LUME 1%; HI-LUME 1%
WITH SOFT-ON, FADE-TO-BLACK; 5-SERIES; OR HI-LUME PREMIER 0.1% UNLESS
OTHERWISE NOTED.
E.E. TO CONFIRM ALL CIRCUITING REQUIREMENTS.
ARCHITECT TO VERIFY QUANTITY, LOCATION & FINISH OF ALL CONTROLS.
LUTRON FIELD SERVICE COMMISSIONING INCLUDED IN ALL SYSTEMS INITIATES AN 2 YEAR
LIMITED WARRANTY. THE ELECTRICAL CONTRACTOR MUST CONTACT LUTRON
(1-844-588-7661) TO SET UP VISIT WITH
10 DAYS NOTICE.
LUTRON SERVICES
| O N SITE PROGRAMM I NG – 4 HO U R BLOCK
( L SC -O S-PROG4 – SP )| ONSITE SYSTEM
PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING DELIVERED
BY A LUTRON SERVICES REPRESENTATIVE . THE SYSTEM WILL BE PROGRAMMED PER AN
APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOURVISITS
PURCHASED.
---|---|---
| REMOTE PROGRAMM I NG – 4 HOUR BLOCK (L SC –
RMT-PROG4-SP )| REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4
CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED FACTORY
CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR WITH THE
ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE
PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER
OF 4-HOUR SESSIONS PURCHASED.
| ONSI T E SCENE & LEVE L T UNING (L
S C- AF – V I SIT )| AN ONSITE VISIT WITH THE
SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE
LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS.
| ONS I TE PERFORMANCE VERIFI C ATION WALKTHROUGH
(LSC – WA L K )| ONSITE WALKTHROUGH WITH FACILITY
REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE SYSTEM
FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE FOLLOWING
ONSITE ACTIVITIES – CONSULTATION TRAINING DEMOS, FUNCTIONAL TESTING
ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT.
POST-STARTUP SERVICES
| CUSTO M ER – SITE SOLUTION TRAINING ( L
SC -TRAIN I NG- S P )| A VISIT TO TEACH SYSTEM
USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM.
| SY STEM OPT I M I ZAT I ON ( L
SC-S Y SOP T -SP )| ONSITE CONSULTATIVE VISIT TO
IDENTIFY & IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY &
CREATE A MORE PRODUCTIVE WORK ENVIRONMENT.
MAINTENANCE & **SUPPORT SERVICES
| ONS I TE PROGRAMMING – 4 HO U R BL O CK
( L S C- O S -PROG4 – SP )| ONSITE
SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING
DEUVERED BY A LUTRON SERVICES REPRESENTATIVE. THE SYSTEM WILL BE PROGRAMMED
PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR
VISITS PURCHASED.
| REMOTE P ROGRAMM I NG – 4 HO U R BLOCK
(L SC – RMT-PROG4-S P )| REMOTE SYSTEM PROGRAMMING
VISIT – UP TO 4 CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED
FACTORY CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR
WITH THE ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM
WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES
THE NUMBER OF 4-HOUR SESSIONS PURCHASED.
| ONSI T E S C ENE & LEVEL TUNING ( LSC
– A F- V I SIT )| AN ONSITE VISIT WITH THE
SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE
LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS.
| ON S I TE PERFORMANCE VERIFI C ATION
WALKTHROUGH ( LSC – WA L K )| ONSITE
WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO
DEMONSTRATE THAT THE SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY
INCLUDE ANY OF THE FOLLOWING ONSITE ACTIVITIES- CONSULTATION fTRAINING
DEMOS, FUNCTIONAL TESTING ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT.
POST-STARTUP SERVICES
| C USTOMER – SI T E SOLUTION TRAINING (
LS C -TRAIN I NG- S P )| A VISIT TO TEACH
SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM.
| S Y STEM OPTIM I ZAT I ON ( L SC-
SYSOP T -SP )| ONSITE CONSULTATIVE VISIT TO IDENTIFY &
IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY & CREATE A
MORE PRODUCTIVE WORK ENVIRONMENT.
MAINTENANCE & **SUPPORT SERVICES
| ENHAN C ED S I LVER (LSC – E S S )|
YEARS 1 & 2: 100% REPLACEMENT PARTS & 100% LUTRON DIAGNOSTIC LABOR COVERAGE
WITH A FIRST-AVAILABLE RESPONSE TIME (SILVER PLAN); YEARS 3-5: 50% PARTS ONLY
COVERAGE; YEARS 6-8: 25% PARTS ONLY COVERAGE.
|
ENHANCED GOLD ( LSC-ESG )
| YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A
72-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE
VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERAGE; YEARS 6-8: 25% PARTS
ONLY COVERAGE.
|
ENHANCED PLAT I NUM (LSC – ESP)
| YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A
24-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE
VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERA E; YEARS 6-8: 25% PARTS
ONLY COVERAGE.
| SILVER TECHNOLOGY SUPPORT PLAN ( LSC-SILV- I W )|
AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON
DIAGNOSTIC LABOR WITH A FIRST-AVAILABLE ONSITE OR REMOTE RESPONSE TIME.
| GOLD TECHNOLOG Y SUPPORT PLAN (LSC-GO L D – I
W )| AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND
100% LUTRON LABOR WITH A 72-HOUR ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES
AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT EACH YEAR.
| PLAT I NUM TECHNOLOG Y SUPPOR T PLAN (
LSC – PLAT – I W)| AN ANNUAL SERVICE PLAN THAT COVERS
100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A 24-HOUR ONSITE
OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED
PREVENTATIVE MAINTENANCE VISIT EACH YEAR.
| PREVENT I VE MAINTENANCE VIS I T ( S )
(LSC – SCH – A I NT)
| YEARLY SCHEDULED MAINTENANCE VISIT TO PERFORM PREVENTIVE MAINTENANCE, MINOR
PROGRAMMING, AND CONDUCT SYSTEM TRAININGS. QUANTITY IS IN ADDITION TO ANY
YEARLY VISITS SPECIFIED WITH AN ENHANCED WARRANTY OR TECHNOLOGY SUPPORT PLAN.
| ON – SI T E BATTERY REP LACEMEN T SE RV
I CE ( LSC – BATT-RPL – SP )| SCHEDULED
MAINTENANCE FOR BATTERY OPERATED SENSORS & KEYPADS DURING WHICH ALL BATTERIES
ARE REMOVED, RECYCLED & REPLACED. THIS IS A SINGLE USE SERVICE OCCURRING 7-8
YEARS AFTER SYSTEM STARTUP IS COMPLETE TO COINCIDE WITH APPROX. 20% -30% OF
BATTERY LIFE REMAINING (ASSUMING AVERAGE USE). THIS SERVICE DOES NOT COVER
INTERMITTENT BATTERY FAILURE PRIOR TO THE SCHEDULED REPLACEMENT. THIS SERVICE
APPLIES TO ALL BATTERY-OPERATED SENSORS & KEYPADS PURCHASED IN THE SAME BILL
OF MATERIAL AS THE SERVICE.
PLEASE GO TO WWW.LUTRON .
COM/SERVICESFOR FURTHER
INFORMATION.
TYPICAL RETAIL
NYCECC 2020
IECC 2018 PATH
NEW YORK, NY
CONCEPT DRAWING
NOT FOR CONSTRUCTION
Project Number:| TBD
Drawn By:| ER/TMS/CR
Drawing Revision:| 2
Drawing Date:| 05.11.2022
Sheet:| 1 OF 1
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036 | USA
610-282-3800 | fax:
610-282-1146