LUTRON HJS-0-FM VIVE Networking Wireless HUB User Guide

June 3, 2024
Lutron

LUTRON HJS-0-FM VIVE Networking Wireless HUB

TYPICAL HUB – AS REQUIRED FLUSH MOUNT AND SURFACE MOUNT OPTIONS AVAILABLE BACNET INTEGRATION AVAILABLE ON CERTAIN MODELS MINIMUM OF 10′ BETWEEN HUBS ON THE SAME FLOOR


HJS-0-FM
VIVE HUB
W/ CLEAR CONNECT & TIMECLOCK 24V POWER SUPPLY & ADAPTER INCLUDED SEE SPEC SHEET FOR MOUNTING REQUIREMENTS COMMUNICATES W/ CLEAR CONNECT DEVICES WITHIN 71′[22m] RADIUS


TYPICAL SENSORS & REMOTE CONTROLS CAN BE A MAX OF 30′ TO LOAD DEVICES – MAX OF 71′ FROM VIVE HUB AND LOCATED ON THE SAME FLOOR

TYPICAL LOAD DEVICES CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR
TYPICAL WALLBOX LOAD CONTROLS CAN BE A MAX OF 71′ FROM VIVE HUB AND LOCATED ON SAME FLOOR

FRONT OF HOUSE RETAIL AREA

AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL

RMJS-8TN-DV-B
POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD


AS REQUIRED FOR ELV ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING

MRF2S-6ELV120-GR
MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE DIGITAL FADE DIMMER 120V, 600W ELECTRONIC LOW-VOLTAGE PLENUM RATED (MOUNTS TO 2 GANG JBOX BY OTHERS)
LOCATION TBD


AS REQUIRED FOR LED/INC ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING

MRF2S-6CL-GR
MAESTRO WIRELESS
MULTI-LOCATION/SINGLE-POLE
CL DIMMER, 120V~ 150 W DIMMABLE CFL/LED/ 600W INCANDESCENT/HALOGEN PLENUM RATED (MOUNTS TO 2 GANG JBOX BY OTHERS)
LOCATION TBD


AS REQUIRED FOR TRIAC/MLV ZONE CONTROL DEVICE TO BE MOUNTED IN CEILING

MRF2S-6ND-120-GR
MAESTRO WIRELESS MULTI-LOCATION/SINGLE-POLE SPEC GRADE DIMMER 120V, 600W/VA INCANDESCENT/HALOGEN *NEUTRAL WIRE REQUIRED PLENUM RATED (MOUNTS TO 2 GANG JBOX BY OTHERS)
LOCATION TBD


AS REQUIRED FOR DIMMING SCENE CONTROL UP TO 10 PER MODULE

PJ2-4B-GWH-XXX
434 MHZ PICO WIRELESS 4 BUTTON CONTROL SHOWN WITH CW-1-WH CLARO WALLPLATE *SEE SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD


AS REQUIRED FOR SECOND FLOOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE

LRF2-DCRB-WH
434MHZ WIRELESS DAYLIGHT SENSOR 1.6″[40,6mm] (DIA) X 0.7″[17,8mm] (D) *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD


BREAK ROOM

AS REQUIRED FOR VACANCY SENSING UP TO 10 PER MODULE

LRF2-VCR2B-P-WH
434MHZ WIRELESS VACANCY SENSOR 3.57″[90,7mm] (DIA) X 1.13″[28,7mm] (D) MAX 10 PER QSM *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH RECESS MOUNT KIT FOR NON-METALLIC CEILINGS)


FOR USE WHEN DAYLIGHT SENSING IS REQUIRED

AS REQUIRED FOR DIMMING ZONE CONTROL TYPICAL OF 1 PER DIMMING ZONE

PJ2-3BRL-GWH-XXX
434 MHZ PICO WIRELESS, LIGHT 3 BUTTON CONTROL WITH RAISE/LOWER SHOWN WITH CW-1-WH CLARO WALLPLATE *SEE SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD


AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL

RMJS-8TN-DV-B
POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD


AS REQUIRED FOR DAYLIGHT SENSING WHERE APPLICABLE MAX OF 1 PER MODULE

LRF2-DCRB-WH
434MHZ WIRELESS DAYLIGHT SENSOR 1.6″[40,6mm] (DIA) X 0.7″[17,8mm] (D) *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD


OR

AS REQUIRED FOR NON-DIM ZONE CONTROL TYPICAL OF 1 PER NON-DIM ZONE

PJ2-2B-GWH-XXX
434 MHZ PICO WIRELESS 2 BUTTON CONTROL SHOWN WITH CW-1-WH CLARO WALLPLATE *SEE SPECIFICATION SHEET FOR DIMENSIONS, ENGRAVING OPTIONS, & MOUNTING INSTRUCTIONS
LOCATION TBD


FOR USE WHEN DAYLIGHT SENSING IS NOT REQUIRED

RMJS-16R-DV-B
POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
LOCATION TBD


STORAGE ROOMS

AS REQUIRED FOR NON-DIMMING ZONE CONTROL

MRF2S-8SSV-WH
120/277V~, 50/60 Hz MAESTRO SENSOR SWITCH VACANCY SENSOR SINGLE POLE/MULTI- LOCATION *NEUTRAL WIRE REQUIRED MANUAL ON/AUTO OFF (1 GANG US BACKBOX BY OTHERS)
LOCATION TBD


AS REQUIRED FOR 0-10V DIMMING ZONE CONTROL

MRF2S-8SDV010-WH
120/277V~, 50/60 Hz MAESTRO SENSOR 0-10V DIMMER VACANCY SENSOR SINGLE POLE /MULTI-LOCATION *NEUTRAL WIRE REQUIRED MANUAL ON/AUTO OFF (1 GANG US BACKBOX BY OTHERS)
LOCATION TBD


AS REQUIRED FOR ADDITIONAL VACANCY SENSING COVERAGE

LRF2-VCR2B-P-WH
434MHZ WIRELESS VACANCY SENSOR 3.57″[90,7mm] (DIA) X 1.13″[28,7mm] (D) MAX 10 PER QSM *DEVICE IS SURFACE-MOUNTED AND BATTERY POWERED, DOES NOT REQUIRE POWER FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH RECESS MOUNT KIT FOR NON-METALLIC CEILINGS)


TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH GENERATOR SYSTEMS

AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY 0-10V LOADS

RMJS-8T-DV-B-EM
NORMAL/EMERGENCY POWPAK DIMMING MODULE 120/277V~, 50/60 Hz W/ 0-10 V CONTROL DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D)
(87mm X 72mm X 32mm)
LOCATION TBD


AS REQUIRED PER ZONE FOR CONTROL OF EMERGENCY NON-DIM LOADS

RMJS-16R-DV-B-EM
NORMAL/EMERGENCY POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (87mm X 72mm X 32mm)
D RMJS-16R-DV-B-EM NORMAL/EMERGENCY POWPAK RELAY MODULE 120/277V~, 50/60 Hz W/ (1) 16A SOFTSWITCH RELAY DIMENSIONS: 3.42″(H) X 2.82″(W) X 1.25″(D) (


TYPICAL EMERGENCY LIGHTING INTERFACES FOR USE WITH EITHER GENERATOR OR INVERTER SYSTEMS PROVIDED BY LVS CONTROLS – CONTACT YOUR LUTRON REPRESENTATIVE FOR MORE INFORMATION

AS REQUIRED FOR UL 924 COMPLIANCE

LUT-SHUNT-D
LVS CONTROLS SHUNT RELAY FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS


AS REQUIRED FOR UL 924 COMPLIANCE

LUT-SHUNT
LVS CONTROLS SHUNT RELAY FOR USE WITH LINE VOLTAGE SWITCHING AND DIMMING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS

AS REQUIRED FOR UL 924 COMPLIANCE

LUT-ALCR-D
LVS CONTROLS ALCR DEVICE FOR USE WITH 0-10V & ECOSYSTEM LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS


AS REQUIRED FOR UL 924 COMPLIANCE

LUT-ALCR
LVS CONTROLS SHUNT RELAY FOR USE WITH SWITCHING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS


AS REQUIRED FOR UL 1008 COMPLIANCE

LUT-ATS-D
LVS CONTROLS TRANSFER SWITCH FOR USE WITH LINE VOLTAGE DIMMING LOADS REFER TO APPLICATION NOTE #628 FOR DETAILED WIRING DIAGRAMS


WIRING LEGEND:

| INPUT POWER (NORMAL-EMERGENCY)
---|---
| INPUT POWER (NORMAL)
| 2 #12AWG (4 mm2)
| 0-10V SIGNAL: 2 #18AWG (1.0 mm2)
| 1-WAY RF COMMUNICATION
| 2-WAY RF COMMUNICATION
CONCEPT DRAWING NOTES:
CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT INTENDED FOR CONSTRUCTION. EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL SCHEDULES, CONTROL INTENT AND SPECIFICATIONS. SHADE EQUIPMENT SHOULD BE VERIFIED IN ACCORDANCE WITH ARCHITECTURAL PLANS, SPECIFICATIONS AND WINDOW SCHEDULES/DETAILS.

LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND CONTROL. LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS COMBINATION

TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON’S PRODUCT COMPATIBILITY MATRIX ON-LINE AT WWW.LUTRON.COM/LED.

TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT LEDS@LUTRON.COM.

LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME LED DRIVERS USED WITH APPROPRIATE LUTRON CONTROLS. PLEASE REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION.

IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. PRODUCTS FOLLOWING THE IEC STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION.

IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE AND COMPATIBILITY CANNOT BE GUARANTEED BY LUTRON. ELV PRODUCTS PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS OR LUTRON HI-LUME 1% 2-WIRE DRIVERS ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER’S DISCRETION.


LUTRON NOTES:

ALL DIMMING BALLASTS TO BE LUTRON ECOSYSTEM, ECOSYSTEM H-SERIES, OR HI-LUME 3D TYPE UNLESS OTHERWISE NOTED.
ALL DIMMING DRIVERS TO BE LUTRON ECOSYSTEM DRIVERS: HI-LUME 1%; HI-LUME 1% WITH SOFT-ON, FADE-TO-BLACK; 5-SERIES; OR HI-LUME PREMIER 0.1% UNLESS OTHERWISE NOTED.

E.E. TO CONFIRM ALL CIRCUITING REQUIREMENTS.

ARCHITECT TO VERIFY QUANTITY, LOCATION & FINISH OF ALL CONTROLS.
LUTRON FIELD SERVICE COMMISSIONING INCLUDED IN ALL SYSTEMS INITIATES AN 2 YEAR LIMITED WARRANTY. THE ELECTRICAL CONTRACTOR MUST CONTACT LUTRON (1-844-588-7661) TO SET UP VISIT WITH 10 DAYS NOTICE.

LUTRON SERVICES

| O N SITE PROGRAMM I NG4 HO U R BLOCK ( L SC -O S-PROG4 SP )| ONSITE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING DELIVERED BY A LUTRON SERVICES REPRESENTATIVE . THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOURVISITS PURCHASED.
---|---|---
| REMOTE PROGRAMM I NG4 HOUR BLOCK (L SC RMT-PROG4-SP )| REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED FACTORY CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR WITH THE ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR SESSIONS PURCHASED.
| ONSI T E SCENE & LEVE L T UNING (L S C- AF V I SIT )| AN ONSITE VISIT WITH THE SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS.
| ONS I TE PERFORMANCE VERIFI C ATION WALKTHROUGH (LSC WA L K )| ONSITE WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE FOLLOWING ONSITE ACTIVITIES  –  CONSULTATION TRAINING DEMOS, FUNCTIONAL TESTING ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT.
POST-STARTUP SERVICES
| CUSTO M ER SITE SOLUTION TRAINING ( L SC -TRAIN I NG- S P )| A VISIT TO TEACH SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM.
| SY STEM OPT I M I ZAT I ON ( L SC-S Y SOP T -SP )| ONSITE CONSULTATIVE VISIT TO IDENTIFY & IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY & CREATE A MORE PRODUCTIVE WORK ENVIRONMENT.
MAINTENANCE & **SUPPORT SERVICES
|
ONS I TE PROGRAMMING4 HO U R BL O CK ( L S C- O S -PROG4 SP )| ONSITE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUS HOURS OF SYSTEM PROGRAMMING DEUVERED BY A LUTRON SERVICES REPRESENTATIVE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR VISITS PURCHASED.
|
REMOTE P ROGRAMM I NG4 HO U R BLOCK (L SC RMT-PROG4-S P )| REMOTE SYSTEM PROGRAMMING VISIT – UP TO 4 CONTIGUOUSHOURS OF SYSTEM PROGRAMMING DELIVERED BY A DEDICATED FACTORY CERTIFIED REMOTE TECHNICIAN EITHER VIA A REMOTE NETWORK CONNECTION OR WITH THE ASSISTANCE OF AN ELECTRICAL CONTRACTOR OVER THE PHONE. THE SYSTEM WILL BE PROGRAMMED PER AN APPROVED SEQUENCE OF OPERATION. QUANTITY DICTATES THE NUMBER OF 4-HOUR SESSIONS PURCHASED.
|
ONSI T E  S C ENE & LEVEL TUNING ( LSC A F- V I SIT )| AN ONSITE VISIT WITH THE SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW DESIGN INTENT, FINE-TUNE SCENE LEVEL PROGRAMMING, AND TIMECLOCK ADJUSTMENTS.
|
ON S I TE PERFORMANCE VERIFI C ATION WALKTHROUGH ( LSC WA L K )| ONSITE WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE  FOLLOWING  ONSITE  ACTIVITIES-  CONSULTATION fTRAINING DEMOS, FUNCTIONAL TESTING ASSISTANCE, & INVENTORY OF LUTRON EQUIPMENT.
POST-STARTUP SERVICES
|
C USTOMER SI T E SOLUTION TRAINING ( LS C -TRAIN I NG- S P )| A VISIT TO TEACH SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM.
|
S Y STEM OPTIM I ZAT I ON ( L SC- SYSOP T -SP )| ONSITE CONSULTATIVE VISIT TO IDENTIFY & IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY & CREATE A MORE PRODUCTIVE WORK ENVIRONMENT.
MAINTENANCE & **SUPPORT SERVICES
| ENHAN C ED S I LVER (LSC E S S )| YEARS 1 & 2: 100% REPLACEMENT PARTS & 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A FIRST-AVAILABLE RESPONSE TIME (SILVER PLAN); YEARS 3-5: 50% PARTS ONLY COVERAGE; YEARS 6-8: 25% PARTS ONLY COVERAGE.
|

ENHANCED GOLD ( LSC-ESG )

| YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A 72-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERAGE; YEARS 6-8: 25% PARTS ONLY COVERAGE.
|

ENHANCED PLAT I NUM (LSC ESP)

| YEARS 1-2: 100% REPLACEMENT PARTS & 100% LUTRON LABOR COVERAGE WITH A 24-HOUR RESPONSE TIME AND AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT (GOLD PLAN); YEARS 3-5: 50% PARTS ONLY COVERA E; YEARS 6-8: 25% PARTS ONLY COVERAGE.
| SILVER TECHNOLOGY SUPPORT PLAN ( LSC-SILV- I W )| AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A FIRST-AVAILABLE ONSITE OR REMOTE RESPONSE TIME.
| GOLD TECHNOLOG Y SUPPORT PLAN (LSC-GO L D I W )| AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON LABOR WITH A 72-HOUR ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT EACH YEAR.
| PLAT I NUM TECHNOLOG Y SUPPOR T PLAN ( LSC PLAT I W)| AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A 24-HOUR ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTATIVE MAINTENANCE VISIT EACH YEAR.
| PREVENT I VE MAINTENANCE VIS I T ( S )

(LSC SCH A I NT)

| YEARLY SCHEDULED MAINTENANCE VISIT TO PERFORM PREVENTIVE MAINTENANCE, MINOR PROGRAMMING, AND CONDUCT SYSTEM TRAININGS. QUANTITY IS IN ADDITION TO ANY YEARLY VISITS SPECIFIED WITH AN ENHANCED WARRANTY OR TECHNOLOGY SUPPORT PLAN.
| ON SI T E BATTERY REP LACEMEN T SE RV I CE ( LSC BATT-RPL SP )| SCHEDULED MAINTENANCE FOR BATTERY OPERATED SENSORS & KEYPADS DURING WHICH ALL BATTERIES ARE REMOVED, RECYCLED & REPLACED. THIS IS A SINGLE USE SERVICE OCCURRING 7-8 YEARS AFTER SYSTEM STARTUP IS COMPLETE TO COINCIDE WITH APPROX. 20% -30% OF BATTERY LIFE REMAINING (ASSUMING AVERAGE USE). THIS SERVICE DOES NOT COVER INTERMITTENT BATTERY FAILURE PRIOR TO THE SCHEDULED REPLACEMENT. THIS SERVICE APPLIES TO ALL BATTERY-OPERATED SENSORS & KEYPADS PURCHASED IN THE SAME BILL OF MATERIAL AS THE SERVICE.
PLEASE GO TO WWW.LUTRON . COM/SERVICESFOR FURTHER INFORMATION.

TYPICAL RETAIL
NYCECC 2020
IECC 2018 PATH
NEW YORK, NY


CONCEPT DRAWING
NOT FOR CONSTRUCTION

Project Number:| TBD
Drawn By:| ER/TMS/CR
Drawing Revision:| 2
Drawing Date:| 05.11.2022
Sheet:| 1 OF 1

Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036 | USA
610-282-3800 | fax: 610-282-1146

LUTRON Logo