SPACE-RAY SUH-S Gas Fired Warm Air Heater Installation Guide
- August 2, 2024
- SPACE-RAY
Table of Contents
- SUH-S Gas Fired Warm Air Heater
- Gas Fired Warm Air Heater – Model SUH-S+
- Specifications
- Product Usage Instructions
- Installation
- Flue Systems
- Operating the Air Heater
- Commissioning
- Combustion Settings
- Maintenance
- Q: What should I do if I encounter explosive ignition or
- Q: How often should I perform basic maintenance on the air
SUH-S Gas Fired Warm Air Heater
Gas Fired Warm Air Heater – Model SUH-S+
Specifications
- Performance: Efficient heating
- Gas types: Natural gas, Propane (G31)
- Dimensions: Compact design
Product Usage Instructions
Installation
Before installation, ensure to follow safety instructions for
protection against dust, temperature, corrosive vapors, and water.
Proper positioning, gas type and connection, electrical connection,
and room thermostat installation are essential.
Flue Systems
Proper installation of flue terminals, consideration of flue
length, and prevention of condensation are crucial for the
efficient operation of the air heater.
Operating the Air Heater
Understand the burner cycle, minimum firing time, Delta-T
regulation, summer ventilation, overheat protection, and regular
checks on the flue passage for safe and effective operation.
Commissioning
Adjust settings and commission the air heater properly before
use. Follow guidelines for first-time use with the thermostat.
Combustion Settings
Learn how to adjust burner settings and convert to another gas
type if necessary.
Maintenance
Regular maintenance is essential for optimal performance. Follow
instructions for basic maintenance, burner unit maintenance, and
maintenance in dusty environments.
FAQ
Q: What should I do if I encounter explosive ignition or
frequent flame failures?
A: Check for proper gas supply and follow troubleshooting steps
for explosive ignition or flame failures mentioned in the
manual.
Q: How often should I perform basic maintenance on the air
heater?
A: Basic maintenance should be performed regularly as per the
maintenance schedule provided in the manual, typically every few
months depending on usage.
®
INSTALLATION MANUAL
Gas Fired Warm Air Heater
Model SUH-S+
Content
1. Introduction
3
1.1 Symbols used in this manual
3
1.2 Warranty
3
2. Safety Instructions
3
2.1 Installation
3
2.1.1 Protection against dust
3
2.1.2 Temperature
3
2.1.3 Corrosive vapours
3
2.1.4 Protection against water
3
2.2 Use
3
2.3 Maintenance and cleaning
3
2.3.1 Protection from water (IP class)
3
2.4 Children and vulnerable users
3
3. Technical Specifications
4
3.1 Performance
4
3.2 Gas types
4
3.2.1 Natural gas
4
3.2.2 Propane (G31)
5
3.3 Dimensions
5
4. Installation
6
4.1 Preparation
6
4.1.1 Standards
6
4.2 Positioning the air heater
6
4.2.1 Orientation
6
4.2.2 Suspension
6
4.3 Gas type and connection
8
4.4 Electrical connection
8
4.4.1 Power supply
8
4.4.2 Fuse
8
4.5 Roon thermostat
8
4.5.1 Installation requirements
8
4.5.2 Modulating room thermostat
9
installation
4.5.3 Installation of multiple heaters on
9
one control unit
5. Flue systems
10
5.1 Flue terminals
10
5.1.1 Flue material
10
5.2 Flue length (max)
11
5.3 Condensation in the flue system
11
5.3.1 Air heater type
11
5.3.2 Air heater location
11
5.3.3 Flue pipe length
11
5.4 Installation of the flue terminal
12
5.4.1 Installation – roof terminal
12
5.4.1.1 Preparation
12
2
5.4.1.2 Installation
12
5.4.2 Installation – wall terminal
13
5.4.2.1 Preparation
13
5.4.2.2 Installation
13
5.4.3 Installation of the flue system parts 13
5.4.3.1 Requirements
13
5.4.3.2 Elements system ALU FIX thick wall 13
5.4.3.3 Seals
13
5.4.3.4 Installation
14
6. Operating the air heater
14
6.1 Burner cycle
14
6.2 Minimum firing time
14
6.3 Delta-T regulation
15
6.3.1 Switch off Delta-T
15
6.4 Summer ventilation
15
6.5 Overheat protection
15
6.5.1 Heat exchanger
15
6.5.2 Flue system
15
6.6 Flue passage check
15
7. Commissioning the air heater
16
7.1 Adjusting the settings
16
7.2 Commissioning the air heater
16
7.2.1 First use – Thermostat
16
8. Combustion settings
17
8.1 Adjusting the burner settings
17
8.2 Converting to another gas
17
9. Troubleshooting
17
9.1 Volatile lock outs
18
9.2 Temporary errors
18
9.3 Warnings
18
9.4 Instructions
19
9.5 Further troubleshooting
20
9.5.1 Explosive ignition and/or frequent 20 flame failures
9.5.2 Insufficient output
20
9.5.3 Non modulating system fan
20
10. Maintenance
20
10.1 Preparation
20
10.2 Basic maintenance
20
10.3 Maintenance of the burner unit
21
10.4 Maintenance in dusty environments 21
11. Electrical wiring diagrams
22
12 Exploded view and spare parts
26
13 Declaration of conformity
27
14 Disposal and recycling
27
1. Introduction
This manual is intended for the gas, electrical and mechanical installer.
This document gives instructions on how to use and maintain the air heater. It
is most important to follow the instructions in this document for safe
operation of this air heater.
It is important to read this document before starting the installation
process. Store this document close to the air heater for quick reference.
1.1. Symbols used in this manual DDAANNGGEERR!! Indicates a dangerous
situation that would lead to death or severe injury.
WARNING! Indicates a potentially dangerous situation that could lead to death,
severe injury or serious product damage.
CAUTION! Indicates a potentially dangerous situation that could lead to injury
or product damage.
NOTICE Indicates important information that is not directly related to safety.
1.2. Warranty NOTICE Using, installing or maintaining this air heater in any
other way than described in this manual may cause damage that voids the
warranty.
NOTICE Failing to follow the safety instructions in this manual can lead to
damage to the air heater or the installation and void the warranty
cause the internal components to degrade much faster.
NOTICE Air heaters installed in very cold environments may form condensate in
the flue system. Make sure a condensate discharge is installed.
2.1.3. Corrosive vapours WARNING! Do not install the air heater in areas that
contain any corrosive or explosive vapours. Corrosive vapours (e.g. containing
Chlorine) that are sucked into the air intake will cause corrosion of the heat
exchanger and a leakage of condensate and flue gas. This is also the case for
the room thermostat.
2.1.4. Protection against water WARNING! Never use water when cleaning
electrical parts. This air heater is not waterproof and has an IP00B
classification.
WARNING! Do not expose the air heater to rain, spray or dripping water.
2.2. Use CAUTION! Make sure the area around the air heater is dry when
performing maintenance on the air heater.
CCAAUUTTIIOONN!! Always close the doors and inspection hatches of the air
heater, except when adjusting and checking the appliance.
2.3. Maintenance & Cleaning Frequent maintenance and cleaning of the air
heater is necessary to ensure safe and proper operation. Failure to do so
could lead to damage to the heater or its surroundings and void the warranty.
2. Safety instructions
Always follow the safety instructions in this chapter
when installing, using or performing maintenance on this
air heater:
2.3.1. Protection from water (IP class) WARNING! Never use water when cleaning electrical parts. This air heater is not waterproof and has an IP20B classification.
2.1. Installation CAUTION! This air heater must be installed and maintained by
an authorized, qualified and competent installer, using calibrated equipment.
NOTICE This air heater must be installed and maintained in accordance with
this manual, national and local building regulations and local health and
safety regulations.
2.1.1. Protection against dust CAUTION! Do not use the air heater in a very
dusty environment. Dust may accumulate and cause a defect of the heater. This
is also the case for the room thermostat.
2.1.2. Temperature CAUTION! Do not install the heater in places where the
temperature can rise above 35°C. Higher temperatures
WARNING! Do not expose the air heater to rain, spray or dripping water.
2.4. Children and vulnerable users WARNING! This air heater can be used by
children aged 8 years and above and by persons with reduced physical, sensory
or mental capabilities or lack of experience and knowledge, if they are
supervised or instructed concerning use of the appliance in a safe way and
understand the hazards involved.
WARNING! Children shall not play with the air heater.
WARNING! Children shall not clean and maintain this air heater without
supervision.
3
3. Technical Specifications
3.1 Performance
Model
Technical Specification – SUH-S+ Series
Unit
SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S 10+ 20+ 30+ 40+ 50+ 60+ 80+ 100+ 120+
Net Heat Input
Max kW Min kW
Heat Output
Max kW Min kW
Efficiency (net)
Max output % Min output %
Air volume (maximum)
m3/h
Throw (maximum)
Horizontal m Vertical m
Gas consumption maximum
Nat gas (G20) LPG (G31)
m3/h kg/h
Gas connection size
BSP
Electrical supply
V
NOx Emission (GCV)
mg/kWh
NOx Class
–
Flue connection size Ø
mm
Horizontal unit m Maximum straight flue run
Vertical unit m
Flue gas volume (maximum)
kg/h
Flue system pressure (maximum)
pa
Power consumption (maximum)
W
Power consumption (maximum) EC version
W
Electrical current (maximum)
A
Electrical current (maximum) EC Version
A
Protection class
Noise level (5m from front)
High dB(A) Low dB(A)
Mounting height (minimum)
Horizontal m Vertical m
Weight
kg
3.2 Gas types 3.2.1 Natural gas
14.0 8.5 12.5 8.0 90.4 93.8 2,750 22 5 1.5 1.1 ½”
48 5 80
21.7 90 200 160 0.9 1.3
56.5 54.0 2.7 4.0 46
22.8 13.5 20.7 12.8 90.6 94.6 4,000 30
7 2.4 1.8 ½”
4.8 5 80 6.0 2.0 35.5 90 300 175 1.4 1.6
58.0 56.5 2.7 4.0 50
32.0 18.0 28.9 17.0 90.4 94.6 4,200 31
7 3.4 2.5 ½”
45 5 80
51.3 90 300 175 1.4 1.6
59.0 56.0 2.7 4.0 53
44.0 55.0 66.0
26.4 33.0 39.6
41.1 50.7 61.2
25.3 31.5 37.9
93.5 92.2 92.7
95.8 95.6 95.6
5,400 8,000 8,000
32
46
30
8
11
8
4.7 5.8 7.0
3.5 4.4 5.3
¾”
¾”
¾”
230V N & E 50Hz
39
49
45
5
5
5
80
80
80
8.0
2.0
70.6 88.2 105.8
120 120 120
325 750 750
260 475 475
1.5 3.5 3.5
1.2 2.3 2.3
IP20B
59.0 64.0 64.0
54.5 58.0 58.0
2.7 2.7 2.7
5.0 6.0 6.0
78
86
82
72.0 91.0 111.0
48.0 60.0 72.0
68.6 86.9 105.6
46.0 57.6 69.4
95.3 95.5 95.1
95.9 96.0 96.4
10,200 10,700 13,000
38
40
43
–
–
–
7.6 9.6 11.7
5.8 7.3 8.9
1″
1″
1″
51 5 100
115.4 150 730 770 3.3 3.5
43 5 100 9.0 145.9 150 760 630 3.5 4.8
60 5 130
177.9 150 1,210 1,080 5.5 4.9
62.0 62.0 62.0
58.0 58.0 58.0
2.7 2.7 2.7
–
–
–
185 195 215
Specification
Nominal supply pressure Supply pressure (min – max) Gas category Class
Unit
mbar mbar
–
Natural Gas G20
20 17-25 12H B23, C13, C33
Specification
CO 2
High
CO 2
Low
CO 2
Low
service
mode
O 2
High
O 2
Low
O 2
Low
service
mode
4
Unit
SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S 10+ 20+ 30+ 40+ 50+ 60+ 80+ 100+ 120+
%
9.1 9.0 9.0 9.0 9.0 9.0 9.1 9.1 9.1
%
8.5 8.5 8.5 8.5 8.6 8.6 9.0 8.9 9.1
%
8.5 8.5 8.5 8.5 8.6 8.6 8.5 8.5 8.5
%
4.7 4.8 4.8 4.8 4.8 4.8 4.7 4.7 4.7
%
5.8 5.8 5.8 5.8 5.6 5.6 4.9 5.0 4.7
%
5.8 5.8 5.8 5.8 5.6 5.6 5.8 5.8 5.8
3.2.2 Propane G31
Specification
Nominal supply pressure Supply pressure (min – max) Gas category Class
Specification
CO 2
High
CO 2
Low
CO 2
Low
service
mode
O 2
High
O 2
Low
O 2
Low
service
mode
3.3 Dimensions
Unit
mbar mbar
–
Unit
% % % % % %
Propane G31
30-50 25-50 13P B23, C13, C33 SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S SUH-S
SUH-S
10+ 20+ 30+ 40+ 50+ 60+ 80+ 100+ 120+ 11.0 10.8 10.8 10.8 10.8 10.6 11.0 11.0
11.1 10.5 10.5 10.5 10.5 10.3 10.3 10.8 10.7 11.0 10.5 10.5 10.5 10.5 10.3
10.3 10.5 10.5 10.5 4.2 4.5 4.5 4.5 4.5 5.0 4.2 4.2 4.1 4.9 4.9 4.9 4.9 5.2
5.2 4.5 4.7 4.2 4.9 4.9 4.9 4.9 5.2 5.2 4.9 4.9 4.9
Fig 1. SUH-S+10 to 30
Fig 2. SUH-S+40 to 60
Fig 3. SUH-S+80 to 100 5
Fig 4. SUH-S120+
4. Installation
4.1 Preparation Before installation, please use the data badge to check:
· if the heater is in accordance with the order · if the heater is suitable
for the local present
provisions (gas type, gas pressure, electrical supply etc.)
Before leaving the factory, the air heater has been tested for safety and has
been set to the operating settings. It has been configured for the type of gas
that is stated on the data badge. Should there be any doubt about the settings
that apply to your situation, please contact your supplier.
· Make sure the air flow to and from the heater is free from obstacles at
least 5 metres in front of the
heater. Also make sure the air intake is free from
obstacles.
· Make sure enough space remains to open the door of the air heater.
· Make sure the wall can support the air heater. · Ensure sufficient clearance
distance for the flue
system.
4.1.1. Standards
NOTICE The installation must comply with all applicable local and national
standards.
NOTICE The air heater must be installed in accordance
with the relevant requirements of the Gas Safety regulations, Electrical
installation regulations and or other local regulations that may apply.
For United Kingdom only: NOTICE The air heater must be installed in accordance
with the relevant requirements of the Gas Safety regulations, Electrical
installation regulations and or other local regulations that may apply (e.g.
The Institute of Gas Engineers IGE UP-1 and 2, BS6230, BS5440 building
regulations and the IIE regulations that incorporate the gas safety
regulations).
4.2. Positioning the air heater Keep the following requirements in mind when
choosing a location to install your air heater:
WARNING! Never install an air heater close to flammable materials.
· Keep sufficient distance between the heater and any obstructions. This is
both for safety reasons and to allow access for service and maintenance (Fig
5.).
6
Fig 5. Minimum clearances around the air heater
4.2.1. Orientation · When the heater is not installed horizontally, readjust
the CO2 setting from the gas valve. · If the air heater is installed with the
air stream vertically downwards, maintain a maximum suspension height of 8m to
ensure that warm air will reach the floor.
4.2.2. Suspension Depending on the model of heater, four types of wall support
can be used:
Model SUH-S10+ to 30+ SUH-S40+ to 60+ SUH-S80+ to 120+ SUH-S10+ to 30+
Wall Bracket Standard Standard Standard Pivoting
Part Number GA8610 GA8620 GA8622 GA8630
Fig 6. Standard wall mounting bracket
Dimension A (mm) B (mm) C (mm) D (mm)
SUH-S10+ to 30+ 550 640 830 540
SUH-S40+ to 60+ 665 815 990 720
Fig 8. Vertical suspension kit
Model
Decription
SUH-S10+ to 60+ Vertical suspension kit
Part Number GA8645
Dimension A (mm)
SUH-S10+ to 30+ 540
SUH-S40+ to 60+ 720
Fig 7. Pivoting wall mounting bracket
Fig 9. Large wall mounting bracket (GA8622) 7
4.3. Gas type & connection The unit is suited for the use of natural gas or
propane gas.
The specific gas type that a heater is set up for can be found on the
packaging labels and on the heater badge. The heater can be converted to
another gas type. Contact your supplier for more information.
WWAARRNNIINNGG!! Never use a room thermostat to interrupt the electric power
supply to the heater.
4.4.2. Fuse One fuse is present on the air heater’s control board (see the
electrical wiring diagram in sect11.).
· When replacing this fuse, always use one of the same type (5AT).
The working and standing supply pressure must be a minimum of 17 mbar, and a
maximum of 50 mbar, measured at the inlet pressure nipple of the gas control
in the heater.
NOTICE The supply line’s manual isolation valve must be placed within reach of
the heater.
NOTICE All gas supply lines must be mounted without any mechanical tension.
NOTICE Always clean the inside of a gas supply line before connecting it to
the air heater. Place a gas filter in the supply line when needed.
CAUTION! When using pressures above 60 mbar to test the supply lines, always
close the manual isolation valve of the air heater.
For United Kingdom only: The supply line for gas must comply with the Gas
Engineers publications UP-1 and UP-2, as well as with BS6891.
4.4. Electrical connection The electrical installation must comply with local
and national requirements as well as IEE regulations.
4.4.1. Power supply The air heater requires an earthed power supply of
230V/AC. The control circuit is a two wire low voltage bus communication.
4.5. Room thermostat The heater can only be controlled with one of the
following modulating room thermostats:
· The MTS: a modulating digital thermostat. · The MTC: a modulating digital
clock thermostat
with optimiser. · Interface module; a specially designed interface
module for BMS systems. Contact your supplier for more information.
WARNING! Never use a room thermostat to interrupt the electric power supply to
the heater.
NOTICE This air heater must not be controlled with a simple ON/OFF thermostat
due to ERP requirements.
4.5.1. Installation requirements Following these requirements when placing the
thermostat to ensure the heater functions correctly:
· Make sure that air can circulate around the thermostat.
· Make sure the sun does not shine directly upon the thermostat.
· Do not place the thermostat on a cold wall. · Place the thermostat on an
inner wall free from
draught. · Never place the thermostat within the throw of
the heater. · Never mount the thermostat near the aerials of
internal communication networks. These emit radiation that can disturb the
thermostat. Keep several meters distance.
230V 1Phase 50Hz
L
N
In all cases, the communication between the heater and the thermostat is based on a two wire, low-voltage connection. (see the electrical wiring diagram in sect11.). Follow these instructions to prevent malfunction of the installation and damage to the thermostat or air heater:
L PE N
Fig 10. Heater power connections
· Connect the wires of the mains cable to the clamps in the connection box
(Fig. 10).
· The heater must be electrically isolated during servicing. Use an isolation
switch (min. 3mm contact opening gap), a power plug or a nonswitched fuse
spur. See the electrical wiring diagram in sect 11.
Use a cable with the following specifications: Signal cable. Shielded and
twisted. Minimum dimensions: 1 x 2 x Ø0,8 mm2. Maximum length: 200 m.
CAUTION! Keep the thermostat cable separated from the mains cables.
CAUTION! Connect the cable’s earth shield only to the
8
earth terminal inside the air heater. Do not connect the other end of the cable’s earth shield.
can control up to 8 air heaters. To connect the air heaters, do the following (Fig. 14):
NOTICE A cable with a thickness of less than 0.8 mm will result in a poor
signal.
NOTICE A cable that is not shielded and twisted may result in a disturbed
communication in an EMC-unfriendly environment.
4.5.2. Modulating room thermostat installation To connect the air heater to an
MTS or MTC thermostat, do the following:
1. Connect the two wires of the thermostat to terminals 4 and 5 of the first
air heater.
2. Connect the first air heater to the second air heater.
3. Repeat for each subsequent air heater.
1
NL PE N L
1
45 NL
2
NL PE N L
2
45 NL
3
NL PE N L
3
45 NL
…8
NL
…8
PE N L
45 NL
1. 1. Connect the two control wires to terminals 4 and 5 (see figure 11 or
the electrical wiring diagram in sect11.).
2. Set the S1 and J14 switches on the control unit as follows (figure 12 /
13): a. Set S1 to 1. b. Set J14 to 1.
NOTICE The air heater must be switched off when setting the switches.
Otherwise the settings will have no effect.
PE N L 4 5
PE N L 4 5
PE N L 4 5
PE N L 4 5
22°C 22°C
45
45
45
S1
J14
10
ON
1S21 3 4 5 6 7 8J14
1
10
ON
2 1ON 0 12345678 12345678
1
45
22°C
45
45
10
ON
3 1ON 0 12345678 12345678
2
ON
22°C
10
12345678
3
Fig 14. Connection of multiple air heaters to a
modulating room thermostat
Fig 11. Modulating thermostat connection
SS11
11 00
JJ1144
OONN
11 22 33 4455 66 77 88
Fig 12. Position of S1 & J14 switches
Each air heater needs an unique number to be recognised by the room
thermostat. This number can be set
with the J14 switch on the control unit of each air heater:
1. Set the S1 and J14 switches on the control unit as follows (figure 15): a. Set the S1 switch of the first air heater to 1. b. Set the S1 switch of the other air heaters to 0. c. Set the J14 switch of the first air heater to 1. d. Set the J14 switch of the second air heater to 2, etc.
S1
10
J14
ON
12345678
10
ON
12345678
Fig 13. Location of S1 & J14 switches
4.5.3 Installation of multiple heaters on one control unit An MTC or MTS room
thermostat, or interface module
ON
10
12345678
Fig 15. Position of S1 and J14 switches for the first three air heaters in a
system
9
NOTICE If the J14 switch of more than one air heater is set to the same number, the system will not work.
NOTICE The air heater must be switched off when setting
the switches. Otherwise the settings will have no effect.
S1
J14
5. Flue systems ON
To ensure1safe0and proper use, this air heater must be connected to a flue
s1ys2te3m4. T5hi6s f7lu8e system must be
installed according to this manual as well as national and local regulations.
A flOuNe system consists of a flue terminal, piping1and0an optional condensate
discharge system.
12345678
CAUTION! Do not use flue terminals for condensing
appliances on non-coOnNdensing heaters. This can lead to water insid1e th0e
flue system.
12345678
NOTICE Only use the prescribed flue material for the roof terminal, wall terminal and for the piping between the heater and the terminal. This is the only way the installation will be approved.
Dimension
A (mm) B (mm) d (Ømm) D (Ømm) HOH (mm)
SUH-S10+ to 30+ 1200 400 80 125 110
SUH-S40+ to 60+ 1200 400 80 125 110
SUH-S90+ to 100+
1200 500 100 150 140
SUH-S 120+ 1850 955 130 200 225
Model
SUH-S1+ to 60+ SUH-S80+ to 100+ SUH-S120+ SUH-S10+ to 30+
Horizontal Discharge
Flue Terminal
Part Number
Concentric 80/125
IA8113
Concentric 100/150
IA8112
Concentric 130/200
IA8312
2 Pipe Terminal
GA8201
NOTICE Local regulations can require the flue terminal to be placed at least 0.6 m above roof level.
NOTICE Local regulations can require a minimum distance between the flue terminal and air ventilation openings on the building.
5.1. Flue terminals
The following flue terminals are compatible with this air heater
Model
Vertical Discharge
Flue Terminal
Part Number
SUH-S10+ to 60+ SUH-S80+ to 100+ SUH-S120+
Concentric 80/125 Concentric 100/150 Concentric 130/200
IA8202* IA8101 IA8305
- For h > 0.5m above the roof, use part number. IA8218
Fig 17. Horizontal concentric flue terminal
Fig 16. Vertical concentric flue terminal 10
5.1.1. Flue material Only use CE marked flue material from the manufacturers
Muelink & Grol (M&G) and Burgerhout.
Use type Alu-fix with a minimum temperature class of T250 P1.
Use flue pipes with the same diameter as the flue spigots on the heater.
Contact your supplier to purchase these flue materials.
NOTICE Different manufacturers use different connections systems for flue
pipes. Do not combine
systems from different manufacturers.
5.2. Flue length (max.) The maximum straight length L (m) between the air heater and its flue terminal for both orientations is:
Heater Orientation Flue Outlet Figure
SUH-S10+ to 30+ SUH-S40+ to 60+ SUH-S80+ to 120+
Horizontal Wall Fig 18. 6 8 9
Horizontal Roof Fig 19. 6 8 9
Vertical Roof Fig 20. 2 2 –
Bends that are used in the connection between an air heater and the flue terminal cause a decrease in pressure:
· Using a 90° bend decreases the maximum length of the connection by 2 meters.
· Using a 45° bend decreases the maximum length of the connection by 1 meter.
For further information regarding the flue system, please contact your
supplier.
L
Fig 20. Flue length: vertical heater orientation, vertical flue
5.3. Condensate in the flue system Condensate can form in the flue system when
the air heater is heating up. This condensate will evaporate if the heater is
operating for a longer period of time. The forming of condensate depends on
the following factors:
Fig 18. Flue length: Horizontal heater orientation, horizontal flue
5.3.1. Air heater type Condensate is especially likely to form in the smaller
heaters (< 25 kW).
Condensate will most likely not form in the larger heaters (> 25 kW).
5.3.2. Air heater location When an air heater burns frequently and is placed
in
a normally heated room (temperature above 15 °C), condensate is unlikely to
form.
Air heaters placed in a room that needs to be just above
5OC will only burn for short periods at the time. Formed condensate will not
evaporate in these short burning periods. The condensate will accumulate and
eventually result in pressure switch errors. To prevent this:
· Add a T-piece (Fig 21.) or
· Add a condensate drain (Fig 22.)
Fig19. Flue length: horizontal heater orientation, vertical flue
5.3.3. Flue pipe length When the flue pipe is long and runs through a cold
space, condensate can form. If the straight length of the flue pipe is longer
than 4 meters, the condensate will not evaporate and accumulate in the heater.
11
In this case. To prevent this: · Insulate the flue pipes. or · Place a
condensate trap (Fig. 21)
Fig 21. Tee piece (6) and condensate trap (7)
5.4. Installation of the flue terminal There are flue terminals available for installation through a roof or through a wall.
NOTICE The flue terminal must be installed according to local and national regulations.
NOTICE Do not combine components or materials from different manufacturers.
5.4.1. Installation – Roof terminal To install the flue terminal in the roof, do the following:
5.4.1.1. Preparation 1. Check all components for possible damage. 2. Determine the roofing type:
Flat Roof Flashing
Synthetic Tile
Universal Pitched Roof flashinG
Ø80 to 130mm
Ø130 to 210mm
–
IA8121
GA8334
–
3. Determine where the flue terminal will be positioned.
5.4.1.2. Installation 1. Create a hole from the outside of the roof.
CAUTION! Make sure no debris or dust gets into the air heater.
2. Install the weather collar. 3. Carefully insert the flue terminal from the outside.
Ø32
Fig 22. Condensate drain 12
CAUTION! Do not rotate the cap.
4. Put the flue terminal into a vertical position. Use a level.
5. OPTIONAL – If desired, fit cover plates. These are supplied separately.
6. Place the supplied wall clamp around the flue terminal and fit it to the
roof construction. Do not tighten the clamp yet.
7. Connect the gasket and the twin-tube connection. Make sure that the gasket
is not damaged.
9. Connect the gasket and the twin-tube connection.
NNOOTTIICCEE Make sure the flue tube and the air inlet tube are not mixed up.
The flue tube should be in the centre of the flue terminal.
10. Check if all steps have been carried out correctly.
5.4.3. Installation of the flue system parts This chapter gives the
instructions for installing an ALU FIX flue system.
5.4.3.1. Requirements The installation must follow these requirements:
· Minimum distance between the flue system and combustible materials of 40 mm.
· Minimum depth of female sockets of 40 mm.
· Minimum slope of horizontal piping of 50 mm/m (3°). This allows condensate
to flow to the heater.
NOTICE Make sure the flue tube and the air inlet tube are not mixed up. The
flue tube should be in the centre of the flue terminal.
8. Tighten the roof wall clamp. 9. Check if all steps have been carried out
correctly.
NOTICE Use brackets that match the flue system. Different manufacturers use
different connection systems for flue pipes. It is not allowed to combine
systems from different manufacturers.
5.4.3.2. Elements system ALU FIX thick wall An ALU FIX flue system is created
with four elements (figure 23).
5.4.2. Installation – Wall terminal To install the flue terminal in a wall, do the following:
5.4.2.1. Preparation 1. Check all components for possible damage. 2. Determine where the flue terminal will be positioned.
5.4.2.2. Installation 1. Create a hole through the wall.
CAUTION! Make sure no debris or dust gets into the air heater.
2. Carefully insert the flue terminal from the outside.
CAUTION! Do not rotate the cap.
3. Put the flue terminal in a horizontal position. Use a level.
4. Mark the holes on the wall. 5. Drill the holes. 6. Insert screws to fix
the terminal in place. 7. Seal the edges of the flue terminal with kit. 8. Fix
the shield on the inside of the wall.
CAUTION! Make sure that the gasket is not damaged.
Fig 23. Components of a flue system
5.4.3.3. Seals The connection between the different flue elements must be made
airtight and waterproof with silicon seals.
CAUTION! If the flue elements have been cut, make sure to clean and chamfer
the edges. Sharp edges will damage the seals.
CAUTION! Do not drill or screw in the flue elements.
CAUTION! Do not try to seal the connections with kit, foam or tape.
CCAAUUTTIIOONN!! Do not use grease, vaseline or oil to lubricate the
installation.
CAUTION! Only use the lubricant allowed by the
13
manufacturer to lubricate the connections. A maximum soap concentration of 1%
is allowed.
NOTICE Follow the instructions from the manufacturer if the connections need
to be fixed.
6. Operating the air heater
6.1. Burner cycle
The air heater’s display shows the current status of the burner cycle (Fig
24.)
5.4.3.4. Installation Take note of the following rules and requirements when installing a flue system:
CAUTION! Do not apply mechanical force on the parts during installation.
Requirements for horizontal and non-vertical piping: · Maximum distance between brackets of 1 m. · On tensile joints; maximum distance between brackets of 2 m.
Fig 24. Air heater display
Follow the manufacturer’s instructions. · Spread the brackets evenly along the piping.
Requirements for vertical piping: · Maximum distance between brackets of 2 m. · Spread the brackets evenly along the piping.
Always place a bracket on or near a bend or elbow piece, except if the flue pipes before and after the elbow piece are shorter than 0.25 m. In this case, fix the second element after the elbow with a bracket.
Every flue discharge system needs to be secured with at least one bracket. The first bracket needs to be within the first 0.5 m of the air heater.
When installing a flue system inside a shaft, do the following:
1. Check the components for possible damage or blockage.
2. Check that the pipe is at the right slope (see Requirements).
3. Mark the flue pipes and fresh air pipes to avoid mixing them up.
4. Make sure that the pipes extend for at least 50mm
when passing through a wall or other obstacle. 5. Fix the last element before
entering the shaft in
place. If the last element is an elbow piece, the next element must also be
fixed in place. 6. Check if ventilation openings and inspection hatches comply
with national and local regulations.
6.2. Minimum firing time The heater will always fire for a minimum of 4
minutes, even if the heat demand stops. This is to avoid a large amount of
start and stops and to prevent condensate
from accumulating in the flue system.
NOTICE The heater will try to ignite 2 times before it stops and gives an error.
14
6.3. Delta-T-regulation The air heater can function as a de-stratification
fan. This is called delta-T regulation and it is done via the room thermostat,
with a temperate measurement sensor that is located on the air heater.
The system fan is activated when the temperature difference between the sensor
on the heater (the delta-T NTC sensor) and the sensor in the thermostat is
greater than 12OC (standard factory setting). This procedure ensures an even
distribution of temperature throughout the building, thus acting as a fully
automatic destratification fan.
6.3.1. Switch off delta-T-regulation Delta-T regulation can be switched off
when it is not desired (e.g. when it causes discomfort). This can be done in
the Settings menu on the room thermostat. See the user manual of the special
Room thermostat for more information.
If the flue system becomes too hot, this sensor will cause the heating process
to stop. Depending on the temperature, the heater performs the following
actions:
· Step 1: Power reduction (when possible). · Step 2: Burner stop, followed by
an automatic
restart when cooled down. · Step 3: Burner stop, followed by a Lock Out. A
manual reset is required. (display L16).
6.6. Flue passage check The air heater is equipped with a pressure switch that
checks the passage of combustion air through the heat exchanger. The pressure
switch checks if there is sufficient movement of combustion air through the
heat exchanger (only during the pre-purge phase). If the pressure difference
is too low, the air heater will not start. Error L-14 will be shown on the
display.
NOTICE Delta-T regulation is automatically switched off when the delta-T sensor (sensor terminal J6) is disconnected.
6.4. Summer ventilation The fan can be set to run in the summer. Follow the instructions in the user manual of the special Room thermostat.
6.5. Overheating protection The air heater’s heat exchanger and flue system are both protected from excessive temperatures.
6.5.1. Heat exchanger An NTC sensor is located near (or on) the heat exchanger. This sensor monitors the heat exchanger temperature.
If the heat exchanger becomes too hot, this sensor will cause the heating process to stop. Depending on the temperature, the air heater performs the following actions:
· Step 1: Power reduction (when possible). · Step 2: Burner stop, followed by
an automatic
restart when cooled down (display: E05 / E36). · Step 3: Burner stop, followed
by a Lock Out. A
manual reset is required. (display L15).
NOTICE A manual reset can be done on the electronic
circuit board or remotely with the special room thermostat.
6.5.2. Flue system
The flue sensor (NTC) is an optional component that is located in the flue
system of the air heater. This sensor monitors the flue temperature.
15
7. Commissioning the air heater
7.1. Adjusting the settings Prior to packaging, the safety and functioning of
each
air heater is checked in detail. It is also set to the right
combustion efficiency.
In general, the heater does not need to be adjusted after installation. It is only necessary to perform a functional check and to obtain a flue gas analysis and record it for later reference.
CAUTION! Always adjust the burner settings of the heater using the manual test mode (see sect7.2.2.). Do not use the thermostat to adjust the burner settings.
CAUTION! Use only calibrated instruments to adjust the air heater.
CAUTION! Never carelessly turn the adjuster screws.
NOTICE Adjusting the control without a supporting flue gas analysis voids the warranty.
Only
adjust
the
CO 2
value
if
the
CO 2
reading
differs
more
than 0.2% from its setting. O2 value ± 0.3%.
7.2. Commissioning the air heater Once the unit is installed according to this manual, the unit can be commissioned. To do so, follow these instructions:
7.2.1. First use thermostat To commission the air heater via the room
thermostat, do the following:
· Put the thermostat in the highest position. The start sequence is always the
same.
The air heater will burn for the minimal firing time (see sect6.2. for more
information).
N7.O2T.2IC. E First use – display To commission the air heater via the
display’s manual test mode, do the following:
NOTICE The display’s manual test mode will only work for maximum 10 minutes.
1. Press and hold the Return and () button for a few seconds (Fig 25). The
display will alternate between Lo and St. This means the heater will start up
in Low fire.
2. Press the (+) and () buttons to toggle between Low and High fire (Fig
25).
3. Press the () button until 0 is displayed to exit the service. The air
heater will always cool down the heat exchanger for several minutes.
The test mode will automatically end after 10 minutes
1. Make sure the gas supply pipe is clean, gas tight and free from air.
2. Switch on the electric supply with the maintenance switch.
You are now able to observe the first start-up and become familiar with the functioning of the heater.
NOTICE If the gas line is not purged correctly, the heater will attempt to start twice before going into a lock-out condition. In this case, manual reset is necessary.
1. Instruct the end user of the about a safe use of the
air heater: The presence of gas The location of the manual gas valve
2. Instruct the end user abou the operation of the heater: Lock-out
indication Reset
3. Instruct end user about the necessary
maintenance. 4. Leave this manual with the end user.
Fig 25. Using the heater display 16
8. Combustion settings
In principle, it is not necessary to adjust the gas valve shortly after
commissioning the air heater. When the control does have to be adjusted after
a period of use or after installing a new heater, this must be done by a
qualified person using calibrated equipment.
DANGER! A poor adjustment can lead to overheating of the air heater and/or
production of toxic carbon monoxide.
CAUTION! Always adjust the burner settings of the heater using the manual test
mode (see sect7.2.2.). Do not use the thermostat to adjust the burner
settings.
8.1. Adjusting the burner settings The flow of gas to the burner is controlled
with a gas valve. This valve must be set to the high and a low power settings
of the heater. When adjusting, the CO2 or O2 in flue gas has to be monitored
with a calibrated analyser.
The gas valve is adjusted with two screws (Fig 27):
The Offset adjuster screw for Low fire. The Gas/air adjuster screw for
High fire.
NOTICE If the air heater does not ignite while sparking, close the air- openings of the gas-air mixer during ignition. Use your forefinger. The gas mixture will become richer and will ignite more easily.
Look for the correct CO value for the air heater in 2
sect3.2. Adjust the CO2 value if the difference is more then 0.2%. O2 value ±
0.3%.
Check
the
CO 2
value
in
High
fire
(Hi).
2. Turn the Ratio adjuster screw to the right to
decrease the CO value. 2
3. 3. Turn the Ratio adjuster screw to the left to
increase the CO2 value. 4. Check the CO2 value in Low fire (Lo). The CO2 value
in Low fire should be lower than in High fire.
5. Turn the Offset adjuster screw to the left to
decrease the CO value. 2
6. Turn the Offset adjust screw to the right to
increase the CO2 value. 7. Return to High fire (Hi) and readjust the CO2 value
with the Ratio adjust screw.
8. Return to Low fire (Lo) and readjust the CO2 value with the Offset adjuster screw.
9. Repeat the steps above until both CO2 values are ok.
P_in
P_Offset
Offset adjustment P_out
DANGER! Always measure the air heater’s CO production. Too much CO usually means the gas mixture is too rich. Adjust this if necessary with the two adjusters (fig 27). The concentration of CO should always be below 100 ppm.
Ratio adjustment
8.2. Converting to another gas type CAUTION! The air heater’s gas type may only be converted by the manufacturer or its representative. Contact your supplier for more information.
Fig 26. Main gas valve parts models SUH-S10+ to 60+
9. Troubleshooting
If the air heater malfunctions, first check if the problem is caused by
external circumstances (e.g. no supply power). If the problem is not caused by
external circumstances, use the tables and instructions in this chapter to fix
the air heater.
1. Shut-off solenoid valve (EV1) 2. Offset adjuster screw 3. Pilot gas flow
restrictor 4. Gas/air adjuster screw 5. Inlet pressure test point
6. Outlet pressure test point*
7. Shut-off solenoid valve (EV2)
8. Pilot outlet
9. Main gas outlet 10. Holes for fixing flanges (M5) 11. Supplementary valve
body
fixing points 12. Air in signal
Fig 27. Main gas valve parts models SUH-S80+ to 120+
The air heater MUST first be commissioned at High fire.
NOTICE Please remember the built in waiting times of the air heater; the signals of the LED’s and the code on the display. Do not react too soon.
17
9.1. Volatile lock outs The table below describes the volatile lock outs that can occur. These can only be reset by hand.
Display
Error Type
L-0 Internal error
L-1 Ignition error
L-2 & 3 Internal error L-4 E-error L-5 Burner fan error
L-6 & 7 Burner fan error
L-8 to 12 L-13
L-14
Internal error
Pressure switch error Pressure switch error
L-15 Overheating
L-16
L17 to 19
Flue temperature error
Internal error
L-20 Flame error
L-21 Flame error
L-22 Flame error
L-25 Sensor error
L-26 Sensor error
L-27 to 31
Internal error
L-32 Sensor error
L33 to 38
L-42
Internal error
Flue temperature error
L-43 Overheating
Description Internal error Flame lasts only 5 seconds after ignition No flame
after ignition Internal error E-error for more than 24 hrs Burner fan does not
work Burner fan rotates at the wrong speed
Internal error
Pressure switch is closed in stand-by mode Pressure switch does not close
during pre-purge Heat exchange sensor is overheated
Flue sensor is overheated
Internal error
Flame detected after closing the gas valve Flame detected before opening the
gas valve. Flame failure during burning Heat exchange sensor failure Flue
sensor failure
Internal error
Heat exchange sensor failure
Internal error
Too many flue temperature errors Heat exchange sensor is overheated too often
Case # 13 1
2 13 12 6 7
13
14
11
3
3
13
15
16 5 4 4 13
4
13
3
3
9.2. Temporary errors
The table below describes the temporary errors that can occur. These will
disappear automatically after the cause has been resolved.
Display Error Type
E-00 to 04
Internal error
E-05 Overheating
E-06 to Internal error 13
E-14 Flame error
E15 to 19 & Internal error 22
E-20 & Heat exchanger 21 sensor error
E-23 & 24
Flue sensor error
E-27 & Heat exchanger 28 sensor error
E30 & 31
Flue sensor error
E-34
Reset button error
E-36 Overheating
E-38 & Heat exchanger 39 sensor error
E-47 & Heat exchanger 48 sensor error
E-49 to 64
Internal error
E-65 Voltage too low
E-66 Voltage too high
E-67
Pressure switch error
E-68
Flue temperature error
E-69
Configuration error
Description
Internal error
Heat exchange sensor is overheated Internal error
Flame detected when there shouldn’t be one
Internal error
Heat exchanger sensor not detected
Flue sensor not detected
Heat exchanger sensor short-circuit
Flue sensor short-circuit
Too many reset actions in a short timespan Heat exchanger sensor is overheated
Heat exchanger sensor not detected Heat exchange sensor short-circuit
Internal error
Supply voltage is too low for over 1 minute Supply voltage is too high for
over 1 minute Too many pressure switch errors
Flue sensor is overheated
Heater configuration error
Case # 13 3 13 16 13 4 4 4 4 9 3 4 4 13
11 3 19
9.3. Warnings The table below describes the temporary warnings that can occur.
The heater may still be working, or stops until
the cause has been resolved.
Display
Error Type
A-02
Configuration error
A-07 Overheating
A-08 Overheating
Description Heater configuration error
Case # 19
Heat exchange sensor is
3
almost overheated
Flue sensor is almost
13
overheated
18
9.4. Instructions After identifying the problem, use the Case number to find
the possible cause in this paragraph.
Case 1: Flame lasts only 5 seconds after ignition.
· The flame is not detected: Check the ignition/ionisation cable and the
electrode. The cable should have a resistance of 1 k.
· The air heater is not earthed properly. · The circuit board is defective.
Case 2: No flame after ignition.
· There is not enough gas pressure. · The gas mixture is too poor:
Adjust the gas valve (see sect8.1.). · The gas valve does not open:
During ignition, check for a 230 V voltage on the valve.
· Check if the ignition electrode sparks. If not: Check the cable and
electrode and replace them when damaged. Check the burner control unit and
replace it when it does not give a spark output.
Check the gas supply pressure while the heater is burning.
· The burner pressure for Low fire is too low. This causes the flame to
extinguish because it is too small to be detected. Check the burner pressure
at Low fire and adjust if necessary (see sect8.1).
· Recirculation of flue gas. Due to a problem with the flue terminal the flue
gas is sucked back into the air inlet. This results into a lack of oxygen and
causes the flame to stop. Check the flue system and fresh air supply. Only
certified, original parts should be used.
Case 6: Burner fan does not work.
· Check if the burner fan is blocked. · Check if the wiring is damaged. · The
burner fan is defective.
Case 7: Burner fan rotates at the wrong speed.
· Check if the burner fan runs smoothly. · Check if the wiring is damaged.
Case 9: Too many reset actions in a short timespan.
Case 3: Heat exchanger sensor or flue sensor is overheated.
· This error will disappear after some time or if the main power is disconnected for a while.
· Check if the connectors J12 and J6 are plugged in correctly and if the
connection J12[1-4] (optional overheating protection) is closed.
· Check if the system fan supplies enough air. · Check the settings of the gas
valve. The heater
may be overfired. If so: Adjust the burner pressure.
Case 11: Insufficient air passage through the heat exchanger. Pressure switch
does not close.
· Check if the combustion fan is running. · Check if the flue system is
blocked or restricted. · Check the pressure switch and the connections. ·
Check the heat exchanger for flue leakage.
Case 4: Heat exchange sensor or flue sensor not detected, or short circuit.
NOTICE L-25 refers to the heat exchange sensor. L-26 refers to the flue
sensor, if applicable.
· The heat exchange sensor consists of two internal sensors. The readings of
these sensors may differ too much: Measure the resistance of each sensor.
The resistance should be 20 K at 25 °C and 25 K at 20 °C. If the measured
values differ too much, replace the sensor.
Case 5: Too many flame failures while burning.
· The gas supply is not constant. This results in a drop in gas supply
pressure while burning and causes the flame to extinguish.
Case 12: E-error for more than 24 hours.
· Switch the air heater off and on and check the error code.
Case 13: Internal error.
· Isolate the electrical supply and reenergise. If this does not help:
Replace the burner control unit.
Case 14: Pressure switch is closed in stand-by mode.
· Check if the contact is stuck. If so: Replace the pressure switch.
· Check if there is water in the hose. If so: Dry the hose.
19
Case 15: Flame detected after closing the gas valve.
· Check if the gas valve closes too slow. If so: Replace the gas valve.
· Check if the ionisation electrode is wet. If so: Dry, clean or replace the
electrode.
Case 16: Flame detected before opening the gas valve.
10. Maintenance
CAUTION! The air heater must be inspected and cleaned once a year by a
qualified installer with sufficient knowledge about the device.
CAUTION! Sufficient maintenance is critical in circumstances such as high
humidity, dust, high switching on/off frequency, etc.
· Check if there really is a flame before ignition. If so: Replace the gas
valve.
· Check if the ionisation electrode is wet. If so: Dry, clean or replace the
electrode.
Case 19: Heater configuration error
· The heater does not know which program to run, due to a mismatch between the
burner control unit and the display. If so: Contact your supplier.
9.5. Further troubleshooting When the air heater does start but shows a
different problem than described above, check if the following problems apply.
10.1. Preparation Before performing maintenance on an air heater that is
already installed, do the following:
1. Set the thermostat to the lowest setting. 2. Close the manual gas valve.
3. Turn off the power supply to the air heater using
the maintenance switch.
CAUTION! Always check for gas leaks after working on the air heater.
CCAAUUTTIIOONN!! Do not use water when cleaning the air heater.
CAUTION! The heater must be electrically isolated during servicing.
9.5.1. Explosive ignition and/or frequent flame failures
· Check if the gas control settings are correct (see sect8.1). A correct CO2
value is important for a proper ignition.
· Check the ignition cable. It should have a resistance of 1 k.
· Check the position of the ignition electrode. The spark has to be formed
between the two electrodes, not between the electrode and the burner.
9.5.2. Insufficient output The heat output of the air heater is insufficient
if there is too much resistance in the inlet or outlet flue system. The burner
fan still rotates at full speed, but the resistance prevents enough gas
mixture from entering the burner.
· Check the flue system for blockage. · Check the burner for dust or other
pollution.
9.5.3. Non modulating system fan System fan (M1) sometimes does not start or
does not vary in speed.
· Check the functioning of this fan by connecting it to a supply of 230 V.
· Check if the fan is energised. Use a multi-meter. If so, the cause of the
problem lies in the burner control unit.
20
10.2. Basic maintenance To perform basic maintenance on the air heater, do the
following:
CAUTION! When cleaning parts of the air heater, use a dry cloth, brush,
compressed air or a vacuum cleaner. Never use a steel brush.
1. Inspect the outside of the heat exchanger. 2. Clean the fan guard on the
outside of the heater.
Clean the fan blades if required. 3. Open the access panel. 4. Clean the
inside of the air heater. Focus on the
following parts: Body Fan blades and motor Heat exchanger Temperature
sensor Vane switch (if present)
5. Check if the wiring, nuts and bolts are properly secured and tightened.
6. Grease any parts and bolts that are regularly loosened for maintenance.
7. Open the manual gas valve in the supply line and check if the supply lines
are air tight, do not leak and do not contain air.
Some checks can only be performed when the heater is running. Do the
following:
1. Reconnect the air heater to the power supply.
2. Switch on the air heater. 3. Check if the heater operates without
problems.
See sect9. if any errors occur. 4. Check the air heater’s combustion
efficiency. If
necessary: Adjust the burner settings (see §8.1.).
10.3. Maintenance of the burner unit The burner unit is an important part of
the air heater and requires special maintenance.
10.4. Maintenance in dusty environments The grid in front of the burner may
become clogged in dusty environments.
1. Remove the burner fan. 2. Clean the grid with a brush and a vacuum
cleaner. 3. Place the burner fan back.
To perform maintenance on the burner unit, do the following:
1. Remove the gas pipe between the gas valve and the combustion fan.
2. Remove the ignition and fan wires. 3. Unscrew the socket screws (M6). 4.
Remove the burner unit from the air heater,
complete with flange and pre-mix fan. 5. Disassemble the burner unit.
6. Adjust the ignition electrode: a. The distance between the electrode and
the burner should be 5.0 (±0.5) mm (figure 28). b. The distance between the
two electrodes should be 3.6 (±0.4) mm (figure 29). c. Check the setting of
the ignition electrode. The spark should be formed between the two electrodes,
not between the electrode and the burner.
Fig 29. The grid in front of the burner
Fig 28. Distance between the electrode and burner
Fig 29. Distance between the two electrodes 7. Reassemble the burner unit and
install it back in the
air heater. Use new gaskets. 21
11. Electrical wiring diagram
A complete electrical wiring diagram is shown in Fig 31, 33, 35 & 37. The
connections that are most important to the
installation process are shown in figure .
C3 C6
21 (0-10V)
20 (GND)
RT
K6
T4 T2 R1
K6
11 13
20K@25°C
100K@25°C 1K
dP S2
T1
20K@25°C 20K@25°C
C2
4
22°C
C4
5
J9- 1 J9- 3 J9- 2 J9- 4
J6- 1 J6- 8 J6- 2 J6- 9 J6- 3 J6- 10 J6- 4 J6- 11 J6- 5 J6- 12 J6- 6 J6- 13
J6- 7 J6- 14
T1
J17 J2-1..6
J1- 1 J1- 5 J1- 2 J1- 6 J1- 3 J1- 7
F1: 5AT J1- 4
J1- 8
J3- 2 J3- 6 J3- 1 J3- 7 J3- 3
J7- 1 J7- 2 J7- 3 J7- 4 J7- 5 J7- 6
J3- 8 J3- 4 J3- 9 J3- 5 J3- 10
J7- 7 J7- 8 J7- 9 J7- 10 J12- 1 J12- 4 J12- 2
J4- 2 J4- 3 J4- 5 J4- 4 J4- 1 J4- 6
J12- 5
J12- 3
J5- 1
J12- 6
Modbus
1 A/+
31 J16
2 B/-
42
3 24V
4 GND
J8- 1
J8- 2
J25 4 3 21
J5- 2 J5- 4 J5- 3 LED RESET
I1
PE
N
E1 P1
L
PE
L triac
12
11
K6 A2
A1
M2
9 (L)
A1 10 (A1)
8 (N)
1 2 3 4 5
L N
M3 V1
43 21
43 21
D2 D1
Fig 31. Electrical wiring diagram SUH-S10+ to 60+ (AC fan models)
Fig 32. Main installer connections SUH-S10+ to 60+ (AC fan models) 22
C3 C6
21 (0-10V)
20 (GND)
RT
K6
T4 T2 R1
K6
11 13
20K@25°C
100K@25°C 1K
M10 EC
J15-2 0-10V J15-3 GND
dP
S2
T1
20K@25°C 20K@25°C
C2
4
22°C
C4
5
J9- 1 J9- 3 J9- 2 J9- 4
T1 J17 J2-1..6
J6- 1
J6- 8 J6- 2 J6- 9 J6- 3 J6- 10 J6- 4 J6- 11 J6- 5 J6- 12 J6- 6
J1- 1 J1- 5 J1- 2 J1- 6 J1- 3 J1- 7
F1: 5AT J1- 4
J1- 8
J3- 2
J6- 13
J3- 6
J6- 7 J6- 14 123 4 5 6 J15 J7- 1 J7- 2 J7- 3 J7- 4 J7- 5 J7- 6 J7- 7 J7- 8 J7- 9 J7- 10 J12- 1 J12- 4 J12- 2
J3- 1 J3- 7 J3- 3
J3- 8 J3- 4 J3- 9 J3- 5 J3- 10
J4- 2 J4- 3 J4- 5 J4- 4 J4- 1 J4- 6
J12- 5
J12- 3
J5- 1
J12- 6
Modbus
1 A/+
31 J16
2 B/-
42
3 24V
4 GND
J8- 1
J8- 2
J25 4 3 21
J5- 2 J5- 4 J5- 3 LED RESET
EC
K6 A2
A1
1 2 3 4 5
L N
I1 PE N P1 L
M10 PE
9 (L)
A1 10 (A1)
8 (N)
M3
V1
43 21
43 21
D2 D1
Fig 33. Electrical wiring diagram SUH-S10+ to 60+ (EC fan models)
Fig 34. Main installer connections SUH-S10+ to 60+ (EC fan models)
23
C3 C6
21 (0-10V)
20 (GND)
RT
K6
T4 T2 R1
K6
11 13
20K@25°C
100K@25°C
3,9K
dP S2
T1
20K@25°C 20K@25°C
C2
4
22°C
C4
5
J9- 1 J9- 3 J9- 2 J9- 4
J6- 1 J6- 8 J6- 2 J6- 9 J6- 3 J6- 10 J6- 4 J6- 11 J6- 5 J6- 12 J6- 6 J6- 13
J6- 7 J6- 14
T1
J17 J2-1..6
J1- 1 J1- 5 J1- 2 J1- 6 J1- 3 J1- 7
F1: 5AT J1- 4
J1- 8
J3- 2 J3- 6 J3- 1 J3- 7 J3- 3
J7- 1 J7- 2 J7- 3 J7- 4 J7- 5 J7- 6
J3- 8 J3- 4 J3- 9 J3- 5 J3- 10
J7- 7 J7- 8 J7- 9 J7- 10 J12- 1 J12- 4 J12- 2
J4- 2 J4- 3 J4- 5 J4- 4 J4- 1 J4- 6
J12- 5
J12- 3
J5- 1
J12- 6
Modbus
1 A/+
3 1 J16 2 B/-
42
3 24V
4 GND
J8- 1
J8- 2
J25 4 3 21
J5- 2 J5- 4 J5- 3 LED RESET
I1
PE
N
E1 P1
L
21
11
K9
14
22
M12
PE
L triac 12
N
11
K6 A2
A1
M11
9 (L)
A1 10 (A1)
8 (N)
1 2 3 4 5
L N
M3 V1
43 21
43 21
D2 D1
Fig 35. Electrical wiring diagram SUH-S80+ to 120+ (AC fan models)
Fig 36. Main installer connections SUH-S80+ to 120+ (AC fan models)
24
C3 C6
21 (0-10V)
20 (GND)
RT
K6
T4 T2 R1
K6
11 13
20K@25°C
100K@25°C
3,9K
M10 EC
J15-2 0-10V J15-3 GND
dP
S2
T1
20K@25°C 20K@25°C
C2
4
22°C
C4
5
J9- 1 J9- 3 J9- 2 J9- 4
T1 J17 J2-1..6
J6- 1
J6- 8 J6- 2 J6- 9 J6- 3 J6- 10 J6- 4 J6- 11 J6- 5 J6- 12 J6- 6
J1- 1 J1- 5 J1- 2 J1- 6 J1- 3 J1- 7
F1: 5AT J1- 4
J1- 8
J3- 2
J6- 13
J3- 6
J6- 7
J3- 1
J6- 14 1 23 4 5 6 J15
J7- 1 J7- 2 J7- 3 J7- 4 J7- 5 J7- 6
J3- 7 J3- 3
J3- 8 J3- 4 J3- 9 J3- 5 J3- 10
J7- 7 J7- 8 J7- 9 J7- 10 J12- 1 J12- 4 J12- 2
J4- 2 J4- 3 J4- 5 J4- 4 J4- 1 J4- 6
J12- 5
J12- 3
J5- 1
J12- 6
Modbus
1 A/+
31 4 2 J16
2 B/3 24V
4 GND
J8- 1
J8- 2
J25 4 3 21
J5- 2 J5- 4 J5- 3 LED RESET
L on/off
I1
PE
N
P1
L
M10 M10
M12 M12
PE
K6 A2
A1
9 (L)
A1 10 (A1)
8 (N)
M12 10v out M12 0-10v in
11
K9
13
K9
1 2 3 4 5
L N
M3 V1
43 21
43 21
D2 D1
Fig 37. Electrical wiring diagram SUH-S80+ to 120+ (EC fan models)
Fig 38. Main installer connections SUH-S80+ to 120+ (EC fan models)
25
12. Exploded view and spare parts
The parts of the air heater are shown in an exploded view (Figs 39 & 40). The
table below describes each part and
shows the correct article number for a replacement part.
Fig 39. Exploded view of models SUH-S10+ to 60+
Fig 34. Exploded view of models SUH-S80+ to 120+
No
Description
1 Burner set (nat gas)
1 Burner set (propane)
2 Ignition/ionisation set
5 Burner fan
6 Gas valve
7 System fan
8
Burner control unit (EBM966)
9 Pressure switch
10 Heat exchanger sensor
11 Gasket set
12 Burner ionisation
13 Delta-T sensor
14 Display PCB
15 Flue sensor
SUH-S 10+ GA3260 GA3224-2 GA3460 GY4523 GA3000 GX4201
SUH-S 20+ GA3262 GA3226-2 GA3460 GY4523 GA3000 GX4204
SUH-S 30+ GA3264 GA3228-2 GA3460 GY4523 GA3000 GX4204
SUH-S 40+ GA3266 GA3234-2 GA3460 GY4523 GA3000 GX4206
SUH-S 50+ GA3266 GA3230-2 GA3460 GY4523 GA3000 GX4217
SUH-S 60+ GA3268 GA3232-2 GA3460 GY4523 GA3000 GX4217
SUH-S 80+ –
GA3236-2 GA3460 GY4502 GY3002 GX4212 x 4
SUH-S 100+ SUH-S 120+
–
–
GA3236-2 GA3236-2
GA3460
GA3460
GY4502
GY4502
GY3002
GY3002
GX4212 x 4 GX4214 x 4
GY5901
GY5901
GY5901
GY5901
GY5901
GY5901
GY5901
GY5901
GY5901
GX3932 GY3932 GA6702 GA6700 GY3931 GY5902 GX3931
GX3932 GY3932 GA6702 GA6700 GY3931 GY5902 GX3931
GX3932 GY3932 GA6702 GA6700 GY3931 GY5902 GX3931
GX3932 GY3932 GA6706 GA6704 GY3931 GY5902 GX3931
GX3932 GY3932 GA6706 GA6704 GY3931 GY5902 GX3931
GX3932 GY3932 GA6706 GA6704 GY3931 GY5902 GX3931
GX3932 GY3933 GA6707 GX6730 GY3931 GY5902 GX3931
GX3932 GY3933 GA6707 GX6730 GY3931 GY5902 GX3931
GX3932 GY3933 GA6707 GX6730 GY3931 GY5902 GX3931
26
13. Declaration of conformity
Gas Fired Products (UK) Ltd. Chapel Lane Claydon Ipswich Suffolk, IP6 0JL
United Kingdom
Declares that air heater types: SUH-S10+, SUH-S20+, SUH-S30+, SUH-S40+,
SUH-S50+, SUH-S60+, SUH-S80+, SUH-S100+ & SUH-S120+
CE PIN: 0063BO3156
Are in accordance with the essential requirements of the relevant EU
directives, being: 2016/426/EU (GAR) relating to appliances burning gaseous
fuels 2014/35/EU (LVD) relating to the electric safety of appliances
2014/30/EU (EMC) relating to electromagnetic compatibility of appliances
2006/42/EG (MD) relating to the safety of machinery
Goods should be installed and used in accordance with our instructions and
with the applicable local and international rules. Installation should be done
by an authorized, qualified and competent installer. Ipswich, December 23rd
2021
S. Richter
14. Disposal and recycling
The meaning of the symbol on the material, its accessory or packaging
indicates that this product shall not be treated as household waste. Please,
dispose of this equipment at your applicable collection point for the
recycling of electrical and electronic equipments waste. In the European Union
and Other European countries where there are separate collection systems for
used electrical and electronic product. By ensuring the correct disposal of
this product, you will help prevent potential hazards to the environment and
to human health, which could otherwise be caused by unsuitable waste handling
of this product. The recycling of materials will help conserve natural
resources. Please do not therefore dispose of your old electrical and
electronic equipment with your household waste.
27
®
Tel: +44(0)1473 830 551 Fax: +44(0)1473 832055
www.spaceray.co.uk info@spaceray.co.uk
Gas Fired Products (UK) Ltd Chapel Lane Claydon Ipswich
Suffolk, IP6 0JL
FACTORIES: IPSWICH, ENGLAND – CHARLOTTE, N.C, U.S.A
SUH-S+ Manual Feb 2024
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>