TROLEX TX5952 Sentro Vortex Wireless User Manual

June 16, 2024
Trolex

TX5952 Sentro Vortex Wireless

Product Information

Specifications

  • Product Name: TX5952 Sentro Vortex Wireless Air Flow
    Sensor

  • Operating Features: Fixed point wireless air flow velocity
    measurement in pipes, ducts, and open roadways

  • Application: Ventilation, cooling systems, and process
    condition monitoring in heavy-duty industrial applications and
    hazardous areas

  • Product Options:

    • Side Projecting Sensor

    • Order Reference:

      • Mining Ex ia
      • General Purpose
    • Please specify the probe length when ordering, probes available
      from 160 mm to 2000 mm insertion length, in 100 mm increments.

    • Remote Mounted Sensor

    • Order Reference:

      • Mining Ex ia
      • General Purpose
    • Please specify cable length and non-standard process fittings
      when ordering. Please specify the probe length when ordering,
      probes available from 160 mm to 2000 mm insertion length, in 100 mm
      increments.

    • Remote Mounted Sensor With 11/2 BSP Mounting Bush

    • Order Reference:

      • Mining Ex ia
      • General Purpose
    • Please specify cable length and non-standard process fittings
      when ordering. Please specify the probe length when ordering,
      probes available from 160 mm to 2000 mm insertion length, in 100 mm
      increments.

Installation

Tools and Test Equipment Required

Before starting the installation process, make sure you have the
following tools and test equipment:

  • Tool 1
  • Tool 2
  • Test equipment 1
  • Test equipment 2

Siting Recommendations

Fitting in Pipes and Ducts

When fitting the sensor in pipes and ducts, follow these
recommendations:

  • Recommendation 1
  • Recommendation 2

Fitting in Roadways and Tunnels

When fitting the sensor in roadways and tunnels, follow these
recommendations:

  • Recommendation 1
  • Recommendation 2

Connections

To make the necessary connections, follow these steps:

  1. Step 1
  2. Step 2

Setup and Calibration

Controls and Indicators

The product is equipped with the following controls and
indicators:

  • Control 1
  • Control 2
  • Indicator 1
  • Indicator 2

Software Menus

The product’s software menus include:

  • Menu 1
  • Menu 2

To navigate through the product’s menus, follow these steps:

  1. Step 1
  2. Step 2

Power-up

To power up the product, follow these steps:

  1. Step 1
  2. Step 2

Main Menu

The main menu of the product includes the following options:

  • Sentro Setup
  • Output Setup
  • Module Setup
  • CommTrac
  • Exit

Support

If you need any support regarding the product, please contact
our customer support team at the provided contact details.

Operation

To operate the product, follow these steps:

  1. Step 1
  2. Step 2

Diagnostics and Maintenance

Diagnostic Messages

The product may display diagnostic messages. Refer to the user
manual for a list of diagnostic messages and their meanings.

Maintenance

Introduction

Regular maintenance is required to ensure optimal performance of
the product. Follow these maintenance procedures:

  • Maintenance Procedure 1
  • Maintenance Procedure 2

Sentro Vortex Wireless – Check

To check the Sentro Vortex Wireless, follow these steps:

  1. Step 1
  2. Step 2

Sentro Vortex Wireless Batteries – Replace

To replace the batteries of the Sentro Vortex Wireless, follow
these steps:

  1. Step 1
  2. Step 2

Sentro Vortex Wireless Sensing Probe – Clean

To clean the Sentro Vortex Wireless sensing probe, follow these
steps:

  1. Step 1
  2. Step 2

Sentro Vortex Wireless Sensing Probe – Calibrate

To calibrate the Sentro Vortex Wireless sensing probe, follow
these steps:

  1. Step 1
  2. Step 2

Disposal

When disposing of the product, follow the proper disposal
procedures to ensure environmental safety.

Maintenance Records

Maintain records of all maintenance activities performed on the
product. Use the provided maintenance record template for easy
documentation.

Maintenance and Calibration Log

Keep a maintenance and calibration log to track all maintenance
and calibration activities performed on the product. Use the
provided log template for accurate record-keeping.

FAQ (Frequently Asked Questions)

Q: What is the purpose of the Sentro Vortex Wireless air flow

sensor?

A: The Sentro Vortex Wireless air flow sensor is used for fixed
point wireless air flow velocity measurement in pipes, ducts, and
open roadways.

Q: What applications is the Sentro Vortex Wireless air flow

sensor suitable for?

A: The Sentro Vortex Wireless air flow sensor is suitable for
ventilation, cooling systems, and process condition monitoring in
heavy-duty industrial applications and hazardous areas.

Q: What are the different product options available?

A: The product options include side projecting sensor and remote
mounted sensor.

Q: How do I fit the sensor in pipes and ducts?

A: Follow the recommended fitting guidelines provided in the
user manual for fitting the sensor in pipes and ducts.

Q: How do I make the necessary connections?

A: Follow the connection steps outlined in the user manual to
make the necessary connections.

Q: How do I calibrate the Sentro Vortex Wireless sensing

probe?

A: Refer to the calibration section in the user manual for
detailed instructions on calibrating the Sentro Vortex Wireless
sensing probe.

Q: What should I do if I encounter any issues with the

product?

A: If you encounter any issues with the product, please contact
our customer support team at the provided contact details for
assistance.

TX5952 User Manual

TX5952 Sentro Vortex Wireless Air Flow Sensor Contents

1. Product Overview

4

1.1 Operating Features

5

1.2 Application

5

1.3 Product Options

6

1.3.1 Side Projecting Sensor

6

1.3.2 Remote Mounted Sensor 6

1.4 Dimensions

7

1.4.1 Side Projecting Sensor

7

1.4.2 Remote Mounted Sensor 8

1.5 Technical Information

9

1.6 Electrical Details

10

1.7 Sentro Module

11

2. Certification

12

3. Installation

13

3.1 Tools and Test

Equipment Required

13

3.2 Siting Recommendations 14

3.2.1 Fitting in Pipes and Ducts 14

3.2.2 Fitting in Roadways and

Tunnels

16

3.3 Connections

17

4. Setup and Calibration

18

4.1 Controls and Indicators

18

4.2 Software Menus

20

4.3 Navigation

21

4.4 Power-up

22

4.5 Main Menu

23

4.5.1 Sentro Setup

24

4.5.2 Output Setup

29

4.5.3 Module Setup

31

4.5.4 CommTrac

41

4.5.4 Exit

46

4.6 Support

46

5. Operation

47

6. Diagnostics and

Maintenance

48

6.1 Diagnostic Messages

48

6.2 Maintenance

49

6.2.1 Introduction

49

6.2.2 Sentro Vortex Wireless

– Check

50

6.2.3 Sentro Vortex Wireless

Batteries – Replace

50

6.2.4 Sentro Vortex Wireless

Sensing Probe – Clean

51

6.2.5 Sentro Vortex Wireless

Sensing Probe – Calibrate 52

6.3 Disposal

53

6.4 Maintenance Records

53

6.5 Maintenance and

Calibration Log

54

Disclaimers

55

Trademarks

55

Contact Details

55

Document History

55

www.trolex.com

TX5952-UM-EN-01a 3

1. Product Overview

TX5952 . . . XX TX5952 . . . XX

Sentro Vortex Wireless air flow sensor with side projecting sensing probe for open flow monitoring in tunnels, roadways and process systems.
Sentro Vortex Wireless air flow sensor with remote mounted sensor. For use where fitting space is limited or is difficult to access.

4

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
1.1 Operating Features
· Fully wireless operation · Powered by commercially available batteries giving up to 200 hours of operation · Powered by the Strata CommTrac wireless network · High stability air flow monitoring · Vortex monitoring principle with no moving components · Output signal linearly proportional to flow velocity · Integral LCD screen with large easy to read characters and back light
illumination · Easily programmable function and display configuration · Rangeable flow velocity from 0.5 m/sec to 30 m/sec · Integral LED indicators for General and High alarms · Auxiliary analogue output signal to drive a local audio visual alarm unit, if
required
1.2 Application
Fixed point wireless air flow velocity measurement in pipes, ducts and open roadways. Ventilation, cooling systems and process condition monitoring in heavy duty industrial applications and hazardous areas. Output data linearly proportional to air flow velocity.

www.trolex.com

TX5952-UM-EN-01a 5

1.3 Product Options

1.3.1 Side Projecting Sensor

Side Projecting Sensor

Order Reference

Mining Ex ia

General Purpose

TX5952.XX.XX.XX.XX

TX5952.XX.XX.XX

Please specify the probe length when ordering, probes available from 160 mm to

2000 mm insertion length, in 100 mm increments.

1.3.2 Remote Mounted Sensor

Remote Mounted Sensor With 50 mm ANSI Mounting Flange

Order Reference

Mining Ex ia

General Purpose

TX5952.XX.XX.XX.XX

TX5952.XX.XX.XX.XX

Please specify cable length and non-standard process fittings when ordering.

Please specify the probe length when ordering, probes available from 160 mm to

2000 mm insertion length, in 100 mm increments.

Remote Mounted Sensor With 11/2″ BSP Mounting Bush Order Reference

Mining Ex ia

General Purpose

TX5951.XX.XX.XX.XX

TX5952.XX.XX.XX.XX

Please specify cable length and non-standard process fittings when ordering. Please specify the probe length when ordering, probes available from 160 mm to 2000 mm insertion length, in 100 mm increments.

6

TX5952-UM-EN-01a

www.trolex.com

1.4 Dimensions 1.4.1 Side Projecting Sensor

TX5952 User Manual

www.trolex.com

TX5952-UM-EN-01a 7

1.4.2 Remote Mounted Sensor

8

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual

1.5 Technical Information

Flow measuring range Accuracy Linearity Ambient temperature limits Sensor temperature limit Humidity Protection classification Process media Housing material Sensor material Flexible cable (remote sensor) Maximum static pressure Process fittings
Cable entry
Nett weight
Information display Vibration limits
Impact limits Output Signals
Alarms

Rangeable from 0.5 to 5 m/s up to 0.5 to 30 m/s +/- 2% within 12.5° rotation of flow axis +/- 1% -20 to +40°C -20 to +150°C 0 to 95% non-condensing Dust and waterproof to IP65 Air, steam or saturated vapour Reinforced polymer Stainless steel – grade 316 PVC coated armoured flexible conduit
20 bar · 11/2″ BSP mounting bush · 50 mm ANSI mounting flange · Side projecting sensing probe – 1 x M20 · Remote mounted sensing probe – 1 x 2M20 · Side projecting sensing probe – 1.5 kg · Remote mounted sensing probe – 2.5 kg 128 x 64 dot graphic backlit LCD screen Vibration limits (EN 60079-29-1): · 10 to 30 Hz – 1.00 mm total excursion · 31 to 150 Hz – 19.6 m/s2 acceleration peak 20 joules (housing) · CommTrac wireless proprietary signal · Auxiliary analogue output signal (4 to 20 mA)
to drive a local audio visual alarm Programmable General and High alarm levels with built-in LED indicators

www.trolex.com

TX5952-UM-EN-01a 9

Menu configuration
Fault indication
1.6 Electrical Details

· Security code protection · Scale factor selection (linear/volume/time) · Setpoint level and mode adjustment · Data output protocol configuration · Flow units selection · Duty display text entry · Wireless network configuration and
information
· Loss of communications · Sensing module absent · Sensor over-range

Description Supply voltage
Supply current
Output relays

Mining Ex
6 V dc (+/- 5%) 10 mA – no backlight 30 mA – with backlight 50 mA with 2 alarm signals and backlight None

General Purpose
6 V dc (+/- 5%) 10 mA – no backlight 30 mA – with backlight 50 mA with 2 alarm signals and backlight None

10

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
1.7 Sentro Module
Plug-in pre-calibrated sensing module with standardised output data. · The sensing module stores all the necessary data about its type identification,
sensing range and specific calibration. This data is automatically recognised by Sentro Vortex Wireless when the sensing module is loaded into the module bay · The sensing modules are pre-calibrated so they can be replaced at any time by a replacement sensing module · The sensing module will identify itself when plugged into the sensor housing and auto configuration will take place · All Sentro sensing modules have two output alarm signals for General alarm and High alarm. Default values are entered during manufacture and these can be changed to preferred values · The two alarm signals can be set to illuminate built-in flashing LED indicators · Two auxiliary analogue output signals (4 to 20 mA) to drive a local audio visual alarm unit, if required

www.trolex.com

TX5952-UM-EN-01a 11

2. Certification
Pending

12

TX5952-UM-EN-01a

www.trolex.com

Certification – continued
Pending

TX5952 User Manual

www.trolex.com

TX5952-UM-EN-01a 13

3. Installation
3.1 Tools and Test Equipment Required
No special tools are required: · Metric spanner set · Metric hexagon key set · Standard electrical test meter
Trolex recommends that the Sentro Wireless Gas Detector is positioned a minimum of 6 m (20 ft) and no more than 245 m (800 ft) from a Strata CommTrac C node for the Sentro Wireless Gas Detector to work effectively.

Checkpoint Where the process cannot be interrupted to remove the Sentro Vortex Wireless from a pipeline, an isolating ball valve may be fitted to the process connection at the installation. This is also useful in installations that have a high level of contamination or moisture in the air stream. Build up of debris or water vapour will cause deterioration of the output signal.
3.2 Siting Recommendations
3.2.1 Fitting in Pipes and Ducts
To attain the best accuracy of response, select a position that is at least twenty pipe diameters down-stream from bends or obstructions, and approximately five pipe diameters from down-stream intrusions.
Similarly, the sensor should be mounted

14

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
at least fifteen pipe diameters from a pipe reducer and fifty pipe diameters from valves.
If this is not possible then the installation of a standard flow straightener will improve performance.
Fit a corresponding threaded boss or flange at the monitoring point and install the sensor, ensuring a air tight seal.
Checkpoint High pressure versions, above 2 bar, will be supplied with a welded bush or flange and will require dedicated process fittings.
Release the clamping ring on the mounting bush or flange.
The centre of the flow path of the sensing head should be positioned as shown.
Checkpoint Ensure that pressurised systems have been completely vented before installation or removal of the sensor.
Position the sensing head with the smaller opening facing the flow, within a rotational deviation of no more than 12.5° from the axis of flow. Tighten the clamping ring with moderate force.
Avoid fitting the sensor at low points in pipework structures to prevent the sensing head from being affected by large accumulations of moisture.
TX5952-UM-EN-01a 15

3.2.2 Fitting in Roadways and Tunnels
To attain the best accuracy of response, select a position away from adjacent structures with a clearance of at least 200 mm.
The version with a side projecting sensor can be mounted on to a suitable support using the mounting holes.
Alternatively use a standard mounting bush or flange for fitting to a suitable bracket.

16

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
3.3 Connections
The Sentro Vortex Wireless is battery powered and has wireless communications, therefore no wiring is required to install it. However, there are two analogue output signals. These can be used to connect to local audio visual alarms, if required.
If you decide to use local audio visual alarms you will need to wire them to the Sentro Vortex Wireless. Connections are as follows:
1. Alarm output 1 2. 0 V 3. Alarm output 2 4. Battery + V (no user connection) 5. 0 V Battery – V (no user connection) 6. Reserved for future use (no user
connection)
The terminals are located behind the front cover. Use a cross head screwdriver to remove the four screws securing the front cover and move it out of the way.

www.trolex.com

TX5952-UM-EN-01a 17

4. Setup and Calibration
4.1 Controls and Indicators

18

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual

www.trolex.com

TX5952-UM-EN-01a 19

4.2 Software Menus

20

TX5952-UM-EN-01a

www.trolex.com

4.3 Navigation

TX5952 User Manual

NEXT

SELECT/CHANGE

Checkpoint To use the Sentro Vortex Wireless software and navigate between menus you must press the Setup Buttons: Next is the Left button – L Select/Change is the Right button – R. The use of these buttons is abbreviated to L and R throughout this User Manual.
To access the L (Next) and R (Select/Change) buttons you need to remove the front cover. Use a cross head screwdriver to remove the four screws securing the front cover and move it out of the way.

Checkpoint
The Sentro Vortex Wireless is factory configured with the Security Code unset. If a Security Code has been subsequently set it will need to be successfully entered before the menus can be accessed, see Section 4.5.1.4 for details.

www.trolex.com

TX5952-UM-EN-01a 21

4.4 Power-up
When the Sentro Vortex Wireless is powered-up the Start-up Screen will appear. The Start-up Screen displays basic information about the system including the software version, driver version and output type.
Power On

After five seconds the Main Display will appear. The Main Display displays the current airflow.

22

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
4.5 Main Menu
From the Main Display press and hold L, this will bring up the Main Menu.
From the Main Menu the operating parameters of the Sentro Vortex Wireless may be set up according to preference. The available menus are as follows:
· Sentro Setup · Output Setup · Module Setup · CommTrac · Exit
Checkpoint You can safely remove the front cover of the Sentro Vortex Wireless for setup in a hazardous area, even with the power applied.
Checkpoint The Sentro Vortex Wireless will automatically return to the Main Display if no keys are pressed within 30 seconds.

www.trolex.com

TX5952-UM-EN-01a 23

4.5.1 Sentro Setup
This enables you to view and carry-out setup of the Sentro Vortex Wireless characteristics.
From the Main Menu press L, navigate to Sentro Setup and press R to enter the Sentro Setup Menu.
The available menus are as follows:
· System Information · Display Setup · Alert Setup · Set Security Code · Exit
4.5.1.1 System Information This displays basic information about the system including the main software version, system date, system time, driver versions and output formats.
From the Sentro Setup Menu press L, navigate to the System Information and press R to display the System Information.

24

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
4.5.1.2 Display Setup Menu This enables you to carry-out the setup of the Display.
From the Sentro Setup Menu press L, navigate to the Display Setup and press R to enter the Display Setup Menu.
The available menus are as follows:
· Set Backlight · Adjust Contrast · Exit
Set Backlight The screen backlight illumination may be set to On or Off, to reduce power consumption.
From the Display Setup Menu press L, navigate to Set Backlight and press R to enter the Set Backlight Menu.
From the Set Backlight Menu press R to set the Backlight Illumination to On or Off as required.
Press L to move to Save or Cancel as required. Press R to confirm the selection and return to the Display Setup Menu.

www.trolex.com

Adjust Contrast TX5952-UM-EN-01a 25

The contrast of the screen may be set for best visual appearance.
From the Display Setup Menu press L, navigate to Adjust Contrast and press R to enter the Adjust Contrast Menu.
Press L to navigate to Increase or Decrease as required. Press R to Increase or Decrease the contrast as required.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Display Setup Menu.
Exit From the Display Setup Menu press L, navigate to Exit, press R to confirm the selection and return to the Sentro Setup Menu.
4.5.1.3 Alert Setup Menu This enables you to carry-out the setup of the Alerts.
From the Sentro Setup Menu press L, navigate to Alert Setup and press R to enter the Alert Setup Menu.
The available menus are as follows:
· Visual Alert · Confidence Alarm · Exit

26

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
Visual Alert The integral General and High visual alarms can be set to On or Off.
From the Alert Setup Menu press L, navigate to Visual Alert and press R to enter the Visual Alert Menu.
From the Visual Alert Menu press R to set the Visual Alert to On or Off as required.
Press L and navigate to Save or Cancel as required. Press R to confirm the selection and return to the Alert Setup Menu.
Confidence Alarm The Confidence Alarm flash can be set to On or Off. For details of the Confidence Alert refer to Section 5.
From the Alert Setup Menu press L, navigate to Confidence Alarm and press R to enter the Confidence Alarm Menu.
From the Confidence Alarm Menu press R to set the Confidence Alert to On or Off as required.
Press L to move to Save or Cancel as required.
Press R to confirm the selection and return to the Alert Setup Menu.

www.trolex.com

TX5952-UM-EN-01a 27

Exit From the Alert Setup Menu press L, navigate to Exit and press R to confirm the selection and return to the Sentro Setup Menu.
4.5.1.4 Set Security Code This enables you to enter a Security Code and prevent unauthorised access to the Main Menu.
From the Sentro Setup Menu press L, navigate to Set Security Code and press R to enter the Set Security Code menu.
From Set Security Code press R to increment the first digit. Press L to confirm the selection and move to the next digit.
Repeat for all four digits. Press L and navigate to Save or Cancel as required and Press R to confirm the selection.
4.5.1.5 Exit From the Sentro Setup Menu press L, navigate to Exit, press R to confirm the selection and return to the Main Menu.

28

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
4.5.2 Output Setup
This enables you to view information on and setup characteristics of the Sentro Vortex Wireless output signal. From the Main Menu press L, navigate to Output Setup and press R to enter the Output Setup Menu. The available menus are as follows: · Modbus Address · Baud Rate · TxOn Delay · TxOff Delay · Exit Modbus Address The Modbus Address can be set between 1 and 255 as required.
From the Output Setup Menu press L, navigate to Modbus Address and press R to enter the Modbus Address Menu.
Press L to navigate to Increase or Decrease as required. Press R to Increase or Decrease the Modbus Address as required.
TX5952-UM-EN-01a 29

Press L and navigate to select Save or Cancel as required. Press R to confirm the selection and return to the Output Setup Menu.

Baud Rate The Baud Rate can be set to 300/600/1200/2 400/4800/9600/14400/19200/28800/38400/ 57600/115200 as required.
From the Output Setup Menu press L, navigate to Baud Rate and press R to enter the Set Baud Rate Menu.
Press R to navigate to the required Baud Rate, press L and select Save or Cancel as required. Press R to confirm the selection and return to the Output Setup Menu.
TxOn Delay and TxOff Delay
Checkpoint TxOn Delay and TxOff Delay are configured in exactly the same way as each other.
The TxOn Delay and TxOff Delay can be set between 0 and 99 ms.
From the Output Setup Menu press L, navigate to TxOn Delay or TxOff Delay as required and Press R to enter the TxOn Delay or TxOff Delay Menu as required.

30

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
Press L to navigate to Increase or Decrease as required. Press R to Increase or Decrease as required. Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Output Setup Menu.
Exit From the Output Setup Menu press L, navigate to Exit, press R to confirm the selection and return to the Main Menu.
4.5.3 Module Setup
This enables you to setup the functional values of the Sentro Module fitted to Sentro Vortex Wireless.
From the Main Menu press L, navigate to Module Setup and press R to enter the Module Setup Menu.
The available menus are as follows: · Scaling · Setpoint 1 · Setpoint 2 · Configuration · Exit
TX5952-UM-EN-01a 31

4.5.3.1 Scaling This enables you to carry-out a setup of the Scaling functions.
From the Module Setup Menu press L, navigate to Scaling and press R to enter the Scaling Setup Menu.
The available menus are as follows: · Sig. Figures · Lower Range · Upper Range · Units · Scale Factor · Exit

Significant Figures The position of the decimal point can be shifted along the displayed number to the best Significant Figures to suit the particular sensor signal being monitored and its optimum measuring range. This can be used to eliminate digit flicker and redundant decimal places.
From the Scaling Setup Menu press L, navigate to Sig. Figures and press R to enter the Significant Figures Menu.

32

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
Press R to move the decimal point to the preferred position to give the number of decimal places required.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Scaling Setup Menu.
Lower Range and Upper Range Set the desired Lower Range and Upper Range of the displayed reading for a given magnitude of input signal. This can be any numeric value and the polarity can be any negative value through to any positive value.
Checkpoint Enter the preferred Significant Figures before setting the Lower Range and Upper Range values.
From the Scaling Setup Menu press L, navigate to Lower Range or Upper Range as required and press R to enter the Lower Range or Upper Range Menu as required.
Press R to change the minus to a plus. Press L to move to the first digit, press R to increment the digit and press L to move to the next digit.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Scaling Setup Menu.
TX5952-UM-EN-01a 33

Units The displayed Units of air flow can be changed according to preference. Two types of Units can be displayed: · Flow Velocity Values – independent of
the cross-sectional area of the flow path · Volumetric Flow Values – relative to the
cross-sectional areas of the flow path
The default Units displayed are m/s (metre/ second). The Units that can be displayed are as follows:
Flow Velocity Values · m/s – metres per second · ft/s – feet per second Volumetric Flow Values · m3/s – cubic metres per second · m3/h – cubic metres per hour · ft3/s – cubic feet per second · ft3/h – cubic feet per hour
From the Scaling Setup Menu press L, navigate to Units and press R to enter the Units Menu.

Press R to change the displayed Units to the preferred Units to be displayed.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Scaling Setup Menu.

34

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
Scale Factor If one of the four Volumetric Flow Value units is selected, it will be necessary to enter a multiplication factor relating to the crosssectional area of the flow path.
Checkpoint The scale Factor is user rangeable between 1.0000 and 9.9999.
From the Scaling Setup Menu press L, navigate to Scale Factor and press R to enter the Scale Factor Menu.
Press R to increment the first digit, press L to move to the next digit, press R to increment the digit and repeat for all digits as required.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Scale Factor Setup Menu.
Exit From the Scaling Setup Menu press L, navigate to Exit and press R to Exit the Scaling Setup Menu and return to the Module Setup Menu.

www.trolex.com

TX5952-UM-EN-01a 35

4.5.3.2 Setpoint 1 and Setpoint 2 This enables you to carry-out a setup of Setpoint 1 and Setpoint 2.
Checkpoint Setpoint 1 and Setpoint 2 are configured in exactly the same way.
From the Module Setup Menu press L, navigate to Setpoint 1 or Setpoint 2 and press R to enter the Setpoint 1 or Setpoint 2 Setup Menu.
The available menus are as follows: · Activation · Level · Exit
Activation The Activation mode of Setpoint 1 and Setpoint 2 can be configured to Over or Under as required.
From the Setpoint 1 or Setpoint 2 Setup Menu press L, navigate to Activation and press R.

36

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
From the Activation Menu press R to set Activation to Over or Under as required.
Press L and navigate to Save or Cancel as required. Press R to confirm the selection and return to the Setpoint 1 or Setpoint 2 Setup Menu.
Level The Level at which Setpoint 1 and Setpoint 2 are activated can be configured.
From the Setpoint 1 or Setpoint 2 Setup Menu press L, navigate to Level and press R.
Press R to increment the digits as required. Press L to move to the next digit. Repeat for all digits and press L.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Setpoint 1 or Setpoint 2 Setup Menu.
Exit From the Setpoint 1 or Setpoint 2 Setup Menu press L, navigate to Exit, press R to confirm the selection and return to the Module Setup Menu.
TX5952-UM-EN-01a 37

4.5.3.3 Configuration This enables you to setup the Configuration of the sensing module.
From the Module Setup Menu press L, navigate to Configuration and press R to enter the Configuration Setup Menu.

The available menus are as follows: · Set Duty Text · Set Update · Exit
Set Duty Text The Duty Text can be set according to preference, by default it reads Airflow.
From the Configuration Setup Menu press L, navigate to Set Duty Text and press R to enter the Set Duty Text Menu.

From the Set Duty Text Menu press R to increment a character as required and press L to move to the next character.
Checkpoint The characters are in the sequence A to Z, 0 to 9 and a Blank Space.

38

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
Checkpoint If you wish to clear all text press L, navigate to Clear Text and press R to clear all Duty Text as required.
Checkpoint The maximum number of characters that can be entered in the Duty Text field is 16.
Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Configuration Setup Menu.
Set Update The value of the analogue input signal is averaged and up-dated at periodic intervals. You can configure the up-date period in the Set Update Menu.
Checkpoint A low Set Update setting will give rapid reaction to the input signal and a higher setting may be entered where damping of a fluctuating input is necessary, or simply as a means of applying a delay to the input. This is particularly useful in electrically noisy environments.
From the Configuration Setup Menu press L, navigate to Set Update and press R to enter the Set Update Menu.

www.trolex.com

TX5952-UM-EN-01a 39

Press L to navigate to Increase or Decrease as required. The field is configurable between 0 and 99 seconds.
Press R to Increase or Decrease as required. Press L and select Save or Cancel as required. Press R to confirm the selection and return to the Configuration Setup Menu.
Exit From the Configuration Setup Menu press L and navigate to Exit. Press R to confirm the selection and return to the Module Setup Menu.
4.5.3.4 Exit From the Module Setup Menu press L, navigate to Exit and press R to confirm the selection and return to the Main Menu.

40

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
4.5.4 CommTrac
This displays the system settings of the CommTrac wireless communication system fitted the Sentro Vortex Wireless sensor.
From the Main Menu press L, navigate to CommTrac and press R to enter the CommTrac Setup Menu.
The available menus are as follows: · Comms · Firmware Versions · CN RSSI · Xmit Freq · Voltages · I/O #1 · I/O #2 · Location Msg Interval · Sensor Msg Interval · Sensor Polling Interval · Mute Alarm · Exit
4.5.4.1 Comms From the CommTrac Setup Menu press L, navigate to Comms and press R to enter the Comms Menu.
This displays the Node ID of the Sentro Vortex Wireless sensor on the CommTrac wireless network. It also displays the Number of Received Comm Node which is the number of nodes that the Sentro Vortex Wireless can see on the CommTrac wireless network.
TX5952-UM-EN-01a 41

4.5.4.2 Firmware Versions From the CommTrac Setup Menu press L, navigate to Firmware Versions and press R to enter the Firmware Versions Menu.
This displays the software versions for the PIC Software and CC1110 Software for the CommTrac wireless network system.
4.5.4.3 CN RSSI From the CommTrac Setup Menu press L, navigate to CN RSSI and press R to enter the CN RSSI Menu.
This displays the strength of the wireless signal the Sentro Vortex Wireless is receiving from the CommTrac wireless node. The value displayed will be between -100 (weak signal) to 0 (strong signal).
4.5.4.4 Xmit Freq From the CommTrac Setup Menu press L, navigate to Xmit Freq and press R to enter the Xmit Freq Menu.
This displays frequency in MHz that the Sentro Vortex Wireless has been configured to transmit to the CommTrac wireless node on. The range displayed will be 868 to 925 MHz.
Checkpoint This parameter is configured during manufacture. It is user configurable, but Trolex strongly recommends that users DO NOT alter the configured frequency.

42

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
4.5.4.5 Voltages From the CommTrac Setup Menu press L, navigate to Voltages and press R to enter the Voltages Menu.
This displays voltages for the Sentro Vortex Wireless, including the Battery Voltage, External Voltage and Power Source type.
The Battery Voltage would normally be in the range 0 to 6.5 V. If the Sentro Vortex Wireless is operating from the internal battery the External Voltage would be displayed as 0 V.
4.5.4.6 I/O #1 and I/O #2 From the CommTrac Setup Menu press L, navigate to I/O #1 or I/O #2 and press R to enter the I/O #1 or I/O #2 Menu.
Checkpoint I/O #1 and I/O #2 are configured in exactly the same way.
This displays the configuration and status of I/O #1 and I/O #2 of the CommTrac wireless module fitted to the Sentro Wireless. The configuration is on of the following: · Alarming · Non Alarming · Confidence Alert · Visual Alarm · Sounder Alarm
TX5952-UM-EN-01a 43

Press L to start a Test to verify if the Sentro Wireless is communicating with the wireless network. A Test result of Busy, Passed, Failed or Timed Out will display once the Test is completed.

4.5.4.7 Location Msg Interval From the CommTrac Setup Menu press L, navigate to Location Msg Interval and press R to enter the Location Msg Interval Menu.
This is a user configurable parameter. This is how often (in minutes) the I/O board will queue a CommTrac location message. The default value for this parameter is 1440 minutes. The range is 1 to 32767. This parameter can also be set via a CommTrac over-the-air message.
Press R to increment the digits as required. Press L to move to the next digit. Repeat for all digits, press L and select Save or Cancel as required. Press R to confirm the selection and return to the CommTrac Setup Menu.

4.5.4.8 Sensor Msg Interval From the CommTrac Setup Menu press L, navigate to Sensor Msg Interval and press R to enter the Sensor Msg Interval Menu.
This is a user configurable parameter to define how often (in seconds) the I/O board will queue a CommTrac sensor message when there are no alarms. If there are alarms a sensor message is generated as soon as the I/O board sees them via polling of the Sentro Wireless. The default value for this

44

TX5952-UM-EN-01a

www.trolex.com

www.trolex.com

TX5952 User Manual
parameter is 90 seconds. The range is 10 to 32767. This parameter can also be set via a CommTrac over-the-air message.
Press R to increment the digits as required. Press L to move to the next digit. Repeat for all digits, press L and select Save or Cancel as required. Press R to confirm the selection and return to the CommTrac Setup Menu.
4.5.4.9 Sensor Polling Interval From the CommTrac Setup Menu press L and navigate to Sensor Polling Interval, press R to enter the Sensor Polling Interval Menu.
This is a user configurable parameter to define how often (in seconds) the I/O board polls the Sentro Wireless for sensor data, alarms and parameter changes. Between polling the Sentro Wireless, the I/O board is in a low power mode. Any changes made to this parameter via the Sentro Wireless controls will not be applied, the value is currently hard coded at 5 seconds.
4.5.4.10 Mute Alarm From the CommTrac Setup Menu press L, navigate to Mute Alarm and press R to enter the Mute Alarm Menu.
This will clear any I/Os that are set as Alarming I/Os until another event re- sets that Alarming I/O
Press R to change the configuration between Alarm Muted and Alarm Not Muted as required.
TX5952-UM-EN-01a 45

Press L and navigate to Save or Cancel as required. Press R to confirm the selection and return to the CommTrac Setup Menu.
4.5.4.11 Exit From the CommTrac Setup Menu press L, navigate to Exit, press R to Exit and return to the Main Menu.
4.5.5 Exit
From the Main Menu press L, navigate to Exit and press R to confirm the selection and return to the Main Display.
4.6 Support
If you need technical support to operate this product, or would like details of our after sales technical support packages, please contact your local Trolex service agent or service@trolex.com.

46

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
5. Operation
In the normal mode of operation the Sentro Vortex Wireless will display the air flow rate on the LCD screen in the preferred Units of measurement, this is the Main Display.
If the Confidence Alert has been enabled it will flash every 15 seconds.

www.trolex.com

TX5952-UM-EN-01a 47

6. Diagnostics and Maintenance
6.1 Diagnostic Messages
Sensor Over-range If the Sentro Vortex Wireless goes overrange then the following message will be seen on the LCD screen.
Loss of Signal From the Sensor If there is a loss of signal from the sensing module to the Sentro Vortex Wireless an error message will be shown.
Module Not Fitted If the sensing module has been removed from the Sentro Vortex Wireless and is out for more than 10 seconds, an error message will be shown.

48

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual

Equipment Name
Sentro Vortex Wireless
Sentro Vortex Wireless Batteries
Sentro Vortex Wireless Sensing Probe Sentro Vortex Wireless Sensing Probe

6.2 Maintenance
6.2.1 Introduction
To keep your Sentro Vortex Wireless in the best possible condition and minimise downtime, Trolex strongly recommends that you carry out regular planned preventative maintenance and keep records of the maintenance carried out.

The planned preventative maintenance for Sentro Vortex Wireless consists of a number of tasks carried out at regular intervals on a cumulative basis, ie. at 12 months do the 1 month task, the 3 month task, the 6 month task AND the 12 month task. These tasks are listed in the maintenance schedule below:

Task Type Check Replace

Task Number
6.2.2
6.2.3

Interval
1 month 200 operating
hours

Clean

6.2.4

3 months

Function Test

6.2.5

12 months

www.trolex.com

TX5952-UM-EN-01a 49

6.2.2 Sentro Vortex Wireless Check
1. Check the exterior of the Sentro Vortex Wireless for cracks, penetration, water ingress and other signs of damage.
2. Check that the front cover is free from damage and is securely fitted.
3. Check the LCD screen is clear and free from damage.
4. If any part of the Sentro Vortex Wireless shows any signs of damage, deformation or missing parts, contact your local Trolex service agent or service@trolex.com for advice on repair or replacement.
5. After the completion of all maintenance, update the maintenance records.
6.2.3 Sentro Vortex Wireless Batteries – Replace
1. On the back of the Sentro Vortex Wireless remove the two captive screws located in the top corners of the back panel.
2. Swing the back panel down. 3. Remove the four D cell batteries located
in the battery box. 4. Fit four new D cell batteries to the
battery box.

Checkpoint Only fit the same brand and type of batteries. DO NOT mix battery brands and types. Only fit batteries as sets of four. DO NOT mix old and new batteries.
5. Swing the back panel into place and secure using the two screws.

50

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
6. Tighten the screws firmly but do not overtighten.
7. Check the is showing an airflow reading on the screen.
8. Check no error messages are being displayed.
9. After the completion of all maintenance, update the maintenance records.
6.2.4 Sentro Vortex Wireless Sensing Probe – Clean
1. Remove the sensor and assess its condition.
2. Clean the sensing head with a soft brush or cloth if necessary.
Checkpoint Do not use sharp tools as this may cause damage to the ultrasound transducers and the transverse strut.
3. After the completion of all maintenance, update the maintenance records.

www.trolex.com

TX5952-UM-EN-01a 51

6.2.5 Sentro Vortex Wireless Sensing Probe – Function Test
1. Under normal circumstances, the calibration of the sensing probe will not change significantly.
2. Check the accuracy by comparing the display reading with a reference value of flow velocity. If the values do not correspond return the Sentro Vortex Wireless to your local Trolex service agent, for checking and calibration across the full operating spectrum.
OR 2. Alternatively the Sentro Vortex Wireless
can be removed and returned to your local Trolex service agent, for checking and calibration across the full operating spectrum. Contact service@trolex.com for further information. 3. After the completion of all maintenance, update the maintenance records.
6.3 Disposal
Part of the ethos of Trolex is sustainable design. Sentro Vortex Wireless contains materials that can be recovered, recycled and reused.
At the end of its useful life ensure that the Sentro Vortex Wireless is recycled in accordance with local laws and bylaws for the geographic area where it is located.

52

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual
The end of its useful life is to be determined by the owner/operator of the equipment and not Trolex.Ensure that the Sentro Vortex Wireless is recycled by licenced waste contractors with the appropriate licences for handling metal, plastic and electronic waste in the geographic area where the Sentro Vortex Wireless is located.
Checkpoint Consult your local Trolex service agent or the Trolex Product Support Department if you require assistance with disposal: service@trolex.com
6.4 Maintenance Records
Implement a planned preventative maintenance process and keep good maintenance records.
Consult your local Trolex service agent or the Trolex Product Support Department: service@trolex.com for help in implementing a planned preventative maintenance process.
The `Maintenance and Calibration Log’ gives an example of a typical maintenance record system.

www.trolex.com

TX5952-UM-EN-01a 53

6.5 Maintenance and Calibration Log

Order Reference: TX5952 Serial Number: Location:

Date

Scheduled Check

Fault

Date Purchased: Flow Rate:

Recalibrate

Return to Trolex

Comments

54

TX5952-UM-EN-01a

www.trolex.com

TX5952 User Manual

Disclaimers
The information provided in this document contains general descriptions and technical characteristics of the performance of the product. It is not intended as a substitute for and is not to be used for determining suitability or reliability of this product for specific user applications. It is the duty of any user or installer to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use. Trolex shall not be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments, or find errors in this publication, please notify us at marketing@trolex.com.

No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Trolex.

All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only Trolex or its affiliates should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions must be followed.

Trademarks
© 2015 Trolex® Limited. Trolex is a registered trademark of Trolex Limited. The use of all trademarks in this document is acknowledged.

Document History
Issue 01 26 January 2014

Original publication of this document – 1st draft

Contact Details
Trolex Ltd, Newby Road, Hazel Grove, Stockport, Cheshire, SK7 5DY, UK +44 (0) 161 483 1435 sales@trolex.com

www.trolex.com

TX5952-UM-EN-01a 55

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals