SPACE-RAY SCB30 Time and Temperature Controller Instruction Manual
- September 29, 2024
- SPACE-RAY
Table of Contents
SCB30 Time and Temperature Controller
“`html
Specifications
- Model: SCB30
- Maximum Zones: 4
- Compatible with: Unitary Radiant Tube, Radiant Plaque &
Electric Radiant Heaters
Product Usage Instructions
1. Installation
Follow the installation instructions provided in the manual to
set up the SCB30 time and temperature controller.
2. Setting Up The Controller
-
Language: Set the language for the controller
interface. -
Temperature Scale: Choose between Celsius or
Fahrenheit. -
Number of Heating Zones: Configure the number
of zones to be controlled. -
Date & Time: Set the current date and time
on the controller. -
Setting The Temperature: Adjust the desired
temperature settings for each zone. -
Timer Programs: Create and manage timer
programs for heating schedules.
3. Using The Controller
-
Switching Controller On/Off: Power on or off
the controller as needed. -
Automatic/Manual Operation: Choose between
automatic or manual operation modes. -
Summer/Winter Mode: Switch between summer and
winter modes for heating control. -
Override Function: Override preset settings
for immediate adjustments. -
Zone Enable/Disable: Enable or disable
specific zones for heating control.
Frequently Asked Questions (FAQ)
Q: What is the warranty period for the SCB30 controller?
A: The warranty period for the SCB30 controller is twelve months
from the date of shipment.
Q: How many zones can be controlled by a single SCB30
controller?
A: A maximum of four zones can be controlled by a single SCB30
controller.
“`
INSTALLATION AND OPERATION INSTRUCTIONS
Time and Temperature Controller (max 4 zones) For Unitary Radiant Tube,
Radiant Plaque & Electric Radiant Heaters MODEL SCB30
1
Contents
Page
1. Introduction………………………………………..
3
1.1 Warranty……………………………………. 3
2. Technical Specification………………………….
3
2.1 Main Features…………………………….. 3
2.2 Dimensions………………………………… 3
2.3 PCB Terminals…………………………….. 3
3. Front Panel………………………………………….
4
3.1 Keys ………………………………………….. 4
3.2 Display……………………………………….. 4
3.3 One Heater On One Controller………. 4
4. Installation…………………………………………..
4
5. Setting Up The Controller ……………………..
5
5.1 Language …………………………………… 5
5.2 Setting Temperature Scale ……………. 5
5.3 Setting Number of Heating Zones….. 5
5.4 Setting Date & Time…………………….. 6
5.5 Setting The Temperature……………… 6
5.6 Timer Programs…………………………… 6
5.7 Deleting Timer Programs………………. 7
6. Using The Controller……………………………..
7
6.1 Switching Controller On/Off………….. 7
6.2 Automatic/Manual Operation……….. 7
6.3 Summer/Winter Mode…………………. 8
6.4 Override Function………………………… 8
Page
6.5 Zone Enable/Disable…………………….. 8
6.6
Viewing A Different Heating Zone Temperature………………………………..
9
6.7 Resetting Heaters………………………… 9
6.8
Control Via Key Operated Sensor or BMS……………………………………………
9
6.9 Locking The Keypad……………………… 9
6.10 Keypad Beep………………………………. 10
6.11 Display Text………………………………… 10
6.12 Display Backlight…………………………. 10
6.13 Hour Meter…………………………………. 11
6.13.1 Resetting The Hour Meter…………….. 11
7. Optimiser Function…………………………………… 11
7.1 Optimised Start…………………………… 11
7.2 Optimised Stop…………………………… 11
8. Alarms/Failures……………………………………….. 12
9 Parameter menus Overview………………………. 12
10. Passwords……………………………………………….. 14
11. Firmware Version……………………………………… 14
12. Wiring connections…………………………………… 15
12.1
Single stage U tube, linear & double linear models……………………………….
15
12.2 Single stage SRP models……………….. 16
12.3 Apollo or Eclipse Electric models…… 17
The meaning of the symbol on the material, its accessory or packaging
indicates that this product shall not be treated as regular waste. Please,
dispose of this equipment at your applicable collection point for the
recycling of electrical and electronic equipments waste. In the European Union
and Other European countries which there are separate collection systems for
used electrical and electronic product. By ensuring the correct disposal of
this product, you will help prevent potentially hazardous to the environment
and to human health, which could otherwise be caused by unsuitable waste
handling of this product. The recycling of materials will help conserve
natural resources. Please do not therefore dispose of your old electrical and
electronic equipment with your regular waste.
2
1. Introduction
SCB30 is a programmable time and temperature control-
ler capable of operating single stage (on/off), unitary ra-
diant tube heaters. A maximum of four zones (each with
a local sensor) can be controlled from a single SCB30.
2.2 Dimensions
180mm
1.1 Warranty
Warranty is twelve months from date of shipment. Space-Ray will only repair or
replace products which are
found to be defective after inspection by the manufacturer. Space-Ray will not
accept any liability and gives no warranty due to defects cased through
incorrect installation, misuse or tampering with. All warranty claims must be
authorised prior to return, carriage is customer responsibility.
2. Technical Specification
Power Supply
230Vac +/-10%, use a 315mA fuse
Insulation (power)
Very low voltage parts – re-inforced Relay output – re-inforced
Operation Field
PTC: -50.0 to +110OC or -58.0 to +230OF
Unit Consumption 8 VA
PTC 990 Accuracy
~2OC Between -60OC to +50OC ~5OC Between +500C to +160OC
Housing
Plastic, 180mm x 150mm x 65mm
Fixing
Wall mounted
Data Storage
EEPROM memory
Front Protection IP44
Operating Temperatures
Ambient -10OC to +50OC Storage -20OC to +70OC
Ambient Humidity 30 to 80% without condensation
Connections
Power supply: Screw terminals, max cable size = 4mm2 Lockout lamps/relays: Screw terminals, max cable size = 2.5mm2 min size = 1.5mm2 Sensors: Screw terminals, max cable size = 1.5mm2 min size = 0.5mm2
Display
LCD
Inputs
5 Sensor inputs: PTC 990 @ 25OC P1 to P5 4 Lockout lamp inputs: 250Vac opto- isolated
Outputs
Relay: OUT 1 to 4 Volt-free relay: SPST 16A 250Vac
Insulation (outputs)
Very low voltage parts – re-inforced Between outputs – functional
Serial Communication
iFS Serial interface TTL for: · Controller firmware upgrade · Fast parameter setup (copy/paste)
2.1 Main features
Temperature – Temperature is displayed with one
decimal place between – 99.9 to +99.9 LCD Display – Large LCD display makes
easy viewing of temperature. Scrolling text messages and symbols describe the
operations in progress Enable/Disable – It is possible to enable/disable one
or more heaters
Burner Reset – To reset a burner in lockout, press RST
110mm 150mm
Height = 65mm
156mm Break off plastic lugs
Facia panel
Break off plastic lugs Mounting within another panel
2.3 PCB Terminals
Sensors/ BMS
N & L BLK 1 to 4 Outputs Outside sensor Zone Sensors
P1 C C K1
P2 C C K2
Power supply 230Vac Warning light – burner lockout zone 1 to 4 OUT1 to OUT4
P5 & C
P1 = Zone 1 sensor C = Zone 1 common (sensor & BMS) K1 = Zone 1 Lockable
sensor/BMS volt free contact P2 = Zone 2 sensor C = Zone 2 common (sensor &
BMS) K2 = Zone 2 Lockable sensor/BMS volt free contact
3
Zone Sensors
P3 C C K3
P4 C C K4
P3 = Zone 3 sensor C = Zone 3 common (sensor & BMS) K3 = Zone 3 Lockable
sensor/BMS volt free contact
P4 = Zone 4 sensor C = Zone 4 common (sensor & BMS) K4 = Zone 4 Lockable
sensor/BMS volt free contact
3. Front Panel
3.1 Keys
On/Off: Push for 1sec to switch ON the controller or to put it into standby
mode (only if Hb=YES)
Set-point: Push for 1sec for temperature parameters
Automatic/Manual: Push for 1sec for the automatic/ manual settings. When , ,
or is displayed press key to start/stop the over-ride function for the
relevant zone. To enter the zone Scheduler, set x to AUTO and press ENTER.
Menu: Push briefly for menus:- ALSt, inFo, dSP, Fnc, P-/, P-r, P-L, P-A, P-t,
P-H & tiME.
Enter: During setup, this operates as an Enter button. – To enter the
displayed menu/parameter. – To confirm/start the displayed function.
During normal use press it briefly to see temperature.
Up: During setup use to scroll the menu and parameter lists and to increase
displayed values. During normal use, it scrolls through the available heating
zones.
Down: During setup use to scroll the menu and parameter lists and to decrease
displayed values. During normal use, it scrolls through the available heating
zones.
ESC/RST: During setup this works as an ESC button. During normal use hold it
to reset locked out heaters of the displayed zone.
3.2 Display
Alarm: Alarm detected
Configuration LED: This symbol is illuminated when the display shows
menu/parameter labels. The symbol blinks when the display shows a parameter
value.
Zone: Heating zone to which displayed data refers ie =zone 2.
DAY Day of the week: 1 = Monday, 2 = Tuesday etc…
On/Off: Controller status : Controller ON : Controller OFF (standby) – 230v
still remains. – Reduced set-point (rt) is not maintained – Display shows
CONTROLLER OFF
En-1 En-2 En-3 En-4
Summer: : Controller in summer mode
Winter: : Controller in winter/heat mode
Home: Controller home page
: The display shows temperature of the displayed
.
zone
Zone 1: Enable/Disable En-1 : Zone 1 enabled/disabled
Zone 2: Enable/Disable En-2 : Zone 2 enabled/disabled
Zone 3: Enable/Disable En-3 : Zone 3 enabled/disabled
Zone 4: Enable/Disable En-4 : Zone 4 enabled/disabled
Manual/Automatic mode:
ON: The displayed zone is in manual ON or OFF
.
mode by parameter A-M.
Blinking: The displayed zone is in manual mode by key
.
selector (on sensor) or BMS.
OFF: The displayed zone is in automatic mode.
Over-ride: ON: Over-ride function operating
Heater output(s): ON: Heater on
Timer program ON – SP: Heater timer program ON with set-point temperature SP (SP1 to 4)
Timer program OFF – rt: Heater timer program OFF, the heater maintains the frost protection set-point. rt=0 No frost protection setpoint, heater outputs OFF.
Description line: Name/explanation of the menu/parameter/alarm shown on the display.
Keyboard locked: See section ??
Controller in standby mode
Warning: The controller is still powered even when OFF
.
is shown
4. Installation
WARNING Before operating the controller, please read carefully the
instructions in this manual. Keep this manual in a safe place for future
reference.
Use the controller only for its intended purpose as described in this manual. The Manufacturer declines all responsibility for inappropriate use or incorrect setting of the controls.
To ensure safe operation: · Controller must be properly installed and
maintenance must be performed according to this manual
· Supply voltage and environmental conditions fall within the values specified
on the controller data plate.
WARNING The controller is NOT protected against circuit overload. Ensure power supply input AND outputs are fitted with appropriately sized fuses.
4
· Keep low voltage and line voltage (230Vac) cables apart, do not cross them
over each other.
· Protect the controller power supply and sensor
inputs from electric disturbances. · Disconnect the controller from the power
supply
before carrying out any maintenance; · Do NOT open the controller housing
without
disconnecting the power supply – Remember if the display shows OFF there is
still 230V present.
5. Setting Up The Controller
5.1 Language This is only nessecary if the languague displayed on the screen
is not the desired one.
To show options available:-
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
menu appears.
Press to open the menu. Press or to scroll
through settings available:-
LAn: Language IT = Italian UK = English
Once the desired language is shown, press to display the current setting. To exit, repeatedly press or wait 30sec to return to normal functions.
5.2 Setting temperature scale
To set the temperature scale:-
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
parameters
menu appears, press to select.
The display now shows “PA” followed by the standard
password “00”. Using the & keys enter “95”.
The thermostat stays accessible and password remians
active for 4 minutes.
Press to view the parameters list for the password
entered. Using & until “rEU” is shown, press
to select.
Using or select OC or OF by pressing
5.3 Setting number of heating zones To set the number of heating zones:-
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
parameters
menu appears, press to select.
The display now shows “PA” followed by the standard password “00”. Using the & keys enter “59”. The thermostat stays accessible and password remains active for 4 minutes.
Press to view the parameters list for the password entered. Using & until “H5”
is shown, press
set value to the number of heating zones required.
Pressing once again will display the current setting. To exit, repeatedly press or wait 30sec to return to normal functions.
One heating Zone Set parameter H5=1
Connect heater(s) to OUT1 and the sensor to P1
P1 OUT1
Zone 1 Heater(s)
NOTE: After setting pararmeter H5, controller MUST be restarted
Two heating Zones Set parameter H5=2
Connect:
– Zone 1 heater(s) to OUT1 and sensor to P1 – Zone 2 heater(s) to OUT2 and
sensor to P2
P1
Zone 1
OUT1
Heater(s)
P2
Zone 2
OUT2
Heater(s)
To save changes and exit, repeatedly press 30sec.
or wait
NOTE: After setting pararmeter H5, controller MUST be restarted
After every change of the temperature scale, verify the following
pararmeters:-
· Set-point
· Set-point differential · Alarm thresholds
· Alarm differential
5
Three heating Zones Set parameter H5=3
Connect:
– Zone 1 heater(s) to OUT1 and sensor to P1 – Zone 2 heater(s) to OUT2 and
sensor to P2 – Zone 3 heater(s) to OUT3 and sensor to P3
P1
Zone 1
OUT1 P2
Heater(s) Zone 2
OUT2 P3
Heater(s) Zone 3
OUT3
Heater(s)
NOTE: After setting pararmeter H5, controller MUST be restarted
Four heating Zones Set parameter H5=4
Connect:
– Zone 1 heater(s) to OUT1 and sensor to P1 – Zone 2 heater(s) to OUT2 and
sensor to P2 – Zone 3 heater(s) to OUT3 and sensor to P3 – Zone 4 heater(s) to
OUT4 and sensor to P4
P1
Zone 1
OUT1 P2
Heater(s) Zone 2
OUT2 P3
Heater(s) Zone 3
OUT3 P4
Heater(s) Zone 4
OUT4
Heater(s)
NOTE: After setting pararmeter H5, controller MUST be restarted
Press or to set the current minute. Press to confirm, the day set will then blink (the others remain off). Press or to set the current day, i.e
1 = Monday 2 = Tuesday etc 7 = Sunday
Press to confirm, the digits for year
will blink
Press or to set the current year.
Press to confirm, the digits for month
will
blink.
Press or to set the current month.
Press to confirm, the digits for date of month
will blink.
Press or to set the current date of month
Press to confirm.
To exit, repeatedly press normal functions.
or wait 30sec to return to
5.5 Setting the temperature The SCB30 can control up to four zones, each having it’s own sensor. Therefore each zone will require its temperature to be individually set (temperature value range is determined by rL, rH)
Ensure you are on the home screen
Press the key for approx 1sec. The display now
shows
setting and the light is off.
Press or to scroll through the heating zones connected.
Note: If only one zone is setup in H5 (section 5.3), then only SP1 temperature
will be shown).
SP1 = Temperature setting for heating zone 1 SP2 = Temperature setting for heating zone 2 (if present) SP3 = Temperature setting for heating zone 3 (if present) SP4 = Temperature setting for heating zone 4 (if present)
Briefly press the display now shows the set temperature for approx 3sec. Press or to change the temperature to the required value. Press to confirm.
5.4 Setting date & time
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
menu appears.
Press Press Press
, the hour digits will blink. or to set the current hour. to confirm, the minute digits will then blink.
5.6 Timer programs
This allows you to setup the automatic timer programs for each zone. The SCB30
allows up to 16 programs per zone, these are sorted by day and time and run
cyclically
To access the timer programs.
Ensure you are on the home screen
Press
for approx 1sec.
The display now shows
and the
light is off.
6
If more than one zone is setup on the controller, they will
become visible by pressing or i.e
etc.
Select the heating zone by pressing its settings.
to gain access to
Set
by using
confirm
or and press to
The display shows the first timer program set for that particular zone. If no
programs are present, the display shows
“–:–“. Pressing allows you to scroll existing programs with the first free
slot indicated by “–:–”
Select either an existing timer program, or free slot by pressing for 3sec. When the button is released the hour digits blink.
Press or to select the starting hour
Press to confirm, the digits for minutes “–:–” will
blink.
Press or
to select the minutes (they increase/
decrease by ten at a time).
Press to confirm,
Press or to select the day(s) when the timer should be active i.e
Only 1 = Monday
Weekdays: Mon to Fri
Press to confirm the values. The timer program type will then be displayed:
= Comfort set-point. This is a timer program of outputs ON. If the SCB30 is in heating mode, it is a program of heater ON with set-point.
= Frost protection set point. This is a timer program of outputs OFF. If the SCB30 is in heating mode, it is a program of heater OFF with frost protection set point, only if rt does not = 0.
The display now shows
and the light is off.
If more than one zone is setup on the controller, they will
become visible by pressing or i.e
etc.
Select the heating zone by pressing its settings.
to gain access to
Set
by using
confirm
or and press to
The display shows the first timer program set for that particular zone. If no
programs are present, the display shows
“–:–“. Pressing allows you to scroll existing programs, once the program to be
deleted is displayed, press and hold for 3sec until “–:–” is displayed.
To delete all the timer programs, press and hold for
6sec until
is displayed.
To exit the timer program, wait 10sec.
6. Using The Controller
6.1 Switching controller on/off
To switch the controller On/off hold the key for
approx. 1sec. When the controller is in off mode, the
display shows
, the message “Device off” and
is illuminated.
Note: The controller remains powered even when in Off/ standby mode.
It is possible: · To enable/disable the key from parameter Hb
· To switch On/Off the controller via MODBus.
6.2 Automatic/Manual mode
Parameters
set the
operation mode of heating zones 1 to 4 respectively.
Press or to set the desired timer program
Press to confirm and save the timer program just set. Press to go to the next
timer slot and repeat the above process where nessecary.
To access the
parameters:
Press
for approx. 1sec during normal activity.
Display shows
and the light is off.
Press or to display other zones, if present, and select the required one.
To exit the timer program, wait 10sec.
5.7 Delete timer program This allows you to delete either individual programs,
or
all of them.
To access the timer programs.
Ensure you are on the home screen
Press
for approx 1sec.
Briefly press , display now shows the parameter value for approx. 3sec:
·
The heating zone is in Manual Off mode,
disabled. Heaters in that zone will be Off, they will
just maintain the frost protection setpoint if rt > 0.
·
The heating zone is in Automatic mode.
Heaters are activate according to the timer
program(s).
·
The heating zone is in Manual On mode.
7
· Heaters maintain the temperature set-point SP1, SP2, SP3, SP4.
When the manual OFF or ON function is active, the icon is on.
To change the operating mode, briefly press or to change the mode.
, press
Press to confirm the change. Press 30sec to return to normal functions.
or wait
6.3 Summer/Winter mode
The
parameter sets the summer/winter mode:
=
summer mode. Heater outputs
(OUT1, OUT2, OUT3, OUT4 ) are Off.
=
winter mode. Heater outputs are on
Temperature
· Switching Off the SCB30 by pressing the button. If the SCB30 is in stand-by
mode, heaters do NOT operate to maintain the frost protection set-point rt.
· By the override function, icon is on. · By the zone sensor key selector – if
present. (/Pb=1) · By the BMS contact – if present (/Pb=2).
6.4.1 On/Off manual function
Press the , using or scroll to the
setting and press , using or select either
On or Off by pressing
Press
or wait 30sec to return to normal functions.
SP /rt
SP – rd /rt – rd
Time
On Off
Burner OUT x = Heater x, activates for temperature t SP-rd and turns off when
it reaches the set-point temperature SP = SP1, SP2, SP3, SP4 or rt (if rt does
not =0).
Ensure you are on the home screen
6.4.2 Timed override function
To access the
parameters:
Press
for approx. 1sec during normal activity.
Press or to display other zones, if present, and select the required one.
Briefly press , the icon will illuminate.
To stop an active override period with the icon illuminated.
Briefly press , the icon will turn off.
The above proceedure will need to be carried out for each heating zone if more
than one is installed.
The period of time the override will operate for, is determined by setting t2.
If t2=0 then override function is disabled.
Press key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press to open the menu, at
use or
to switch between
and
select the required mode.
, press to
To exit, press functions.
or wait 30sec to return to normal
6.4 Override timer functions The override function enables the system to operate outside of the timer programs. There are a number of ways this can be carried out:
The override function will always have priority over the Automatic/Manual mode
as well as the key selector Sensor/BMS input.
6.5 Enable/Disable a heating zone Should a heating zone become unoccupied or
does not require heating, that zone can be disabled whilst allowing other
zones to operate as normal.
Enable/disable functions operate as follows: :Enable/disable zone 1: : Zone 1 OFF, disabled : Zone 1 ON, enabled, En-1
:Enable/disable zone 2: : Zone 2 OFF, disabled : Zone 2 ON, enabled, En-2
Note:
· By On/Off manual function for the relevant zone i.e
,
etc.
·
`Manual Off’. Heaters operate to maintain
frost protection set point rt.
·
`Manual On’. Heaters operate to maintain set
point SP.
:Enable/disable zone 3: (not present for two stage heaters)
: Zone 3 OFF, disabled : Zone 3 ON, enabled, En-3
8
: Enable/disable zone 4 (not present for two stage heaters) : Zone 4 OFF, disabled; : Zeater 4 ON, enabled, En-4
Ensure you are on the home screen
Press key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press to open the menu, use or until (or the heating zone requiring enabling/disabling) press
to select, use or to show “On” or Off”,
press to select.
Press
or wait 30sec to return to normal functions.
Note: If a zone is disabled, frost protection is also disabled.
6.6 Viewing a different zone temperature Should the SCB30 be configured to control more than one heating zone, the following instructions enable you to switch zones and view the temperature within that zone.
Temperature within zone
Zone being displayed
If /Pb=1 connect the key selector of a key operated sensor to the contacts Kx-C (with x=1 or 2 or 3 or 4).
The heating zone can be manually started by the key inserted in the zone
sensor, and set to:
· AUTO: The controller activates according to the automatic/manual parameter,
usually activates according to the timer programs set for the selected zone.
· ON: Timer is excluded in the selected zone, heater/s activate to maintain
the comfort set-point SP1
· OFF: timer is excluded in the selected zone, heater/s activate to maintain
the frost protection set-point rt
If /Pb=2 the controller does not execute the timer programs or the
automatic/manual parameter.
Connect a volt free contact of a BMS to the contacts Kx-C (with x=1, 2, 3, 4).
The heating zone can be manually started by the BMS contact:
· If closed: Heater/s activate to maintain the comfort set-point SP
· If open: Heater/s off, they activate only to maintain the frost protection
set-point rt
To access, ensure you are in home screen
Press the key.
Switches off and the dis-
play shows the first menu item.
Whilst at the home screen (shown above), press or to scroll the different
heating zones available. If the
SCB30 has been setup to control only one zone, then only zone 1 will be shown.
6.7 Resetting heaters To reset heater(s) connected to the SCB30:
Press and hold
until
appears, then press
The display will show “00”, using or adjust to
“01” and press
SCB30 will then carryout the heater reset.
Note: This is an electric reset, OUT1 to 4 deactivate for the time equal to
setting L2.
6.8 Control via key operated sensor or BMS An optional key oprated sensor is
available for use with the SCB30, if this or a BMS is fitted follow the
instrustions below:
The /Pb parameter sets the functioning of the K1-C / K2-C / K3-C / K4-C terminals:
NoOtTeE: The key selector/BMS will always have priority over parameter x.. (x = 1, 2, 3, 4)
Scroll the menu using the or key until the menu appears.
Press to select.
The display now shows “PA” the standard password value will be displayed, “00”. Use or to set as “95”, then press
Use Press Press Press
or to scroll the menu until Pb appears to select. Use or to select “1” or “2” to select. or wait 30sec to return to normal functions.
6.9 Locking the keypad
With the keypad locked, the following operations are not permissable:-
· Switching the controller on/off from the keypad
· Checking the temperature scale
· Access to parameters
,
or
· Selecting heating zone to display
· Resetting heaters
9
When the keypad is locked:-
· The message
will be displayed anytime a key
is pressed, except the key.
· If you press briefly, you will enter the alarm list
(if an alarm exists)
· If you keep the key depressed, you will enter the
display menu
To lock the keypad parameter HL=
To access, ensure you are in home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the menu appears.
Press to select.
Once the desired option is shown, press To display the current setting, press
To exit, repeatedly press normal functions.
or wait 30sec to return to
6.11 Display text
This allows you to adjust how the small text is displayed
at the bottom of the main screen.
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
menu appears.
Press to open the menu. Press or to scroll
until “SPd” appears, press This function controls the speed at which long
message text scrolls across the screen. Select either “medium” or “fast” and
press
The display now shows “PA” the standard password value will be displayed,
“00”.
Press or enter any newly set password using or followed by set the password.
The controller
stays accessible and remembers the password for 4 minutes.
The display shows the first parameter of the list enabled by the password.
Press or to scroll through menu options, until HL, press to select.
Select “yes” to lock keypad, or “no” to unlock keypad. Press to confirm.
Press to view current setting.
If you do not want long message text to scroll across the screen and would
rather it appear in one or two lines, then please carryout the following:
Repeat the above process down to where the menu appears.
Press to open the menu. Press or to scroll until “rtn” appears, press This
function determines whether scrolling text or complete line messages appear at
the bottom of the main screen. Select “no” for scrolling text to be activated,
or “yes” for single line text message, note if message is too long for a
single line of text, a second line will appear before reverting back to the
first line.
To exit and save changes, either press 15sec.
, or wait for
Once the desired option is shown, press To display the current setting press
To temporarily unlock the keypad hold and for
at least 3 secs until the message
is displayed. The
keypad re-locks automatically after 15 secs of inactivity.
It is possible to set the function “keypad always locked” by MODBus.
6.10 Keypad beep By default, the keypad beeps everytime a key is pressed, to
remove this follow the instructions below.
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press to open the menu. Press or to scroll through settings “yes” for beep on, or “no” for no beep.
To exit, press functions.
or wait 30sec to return to normal
6.12 Display backlight
The screen backlight automatically fades out after the last key press. There
are however options for screen bricghtness.
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the
menu appears.
Press to open the menu. Press or to scroll
until “Li9” appears, press to select.
Scroll through the options using required option by pressing
or select the
10
Press to display the current setting. To exit, repeatedly press or wait 30sec
to return to normal functions.
6.13 Hour meter The SCB30 is equipped with a feature that monitors heater
activity & status of the output relay. Hour meter values are saved every 3
hours, therefore any power interuptions prior to saving with cause that
periods data to be lost. Maximum number of hours logged is 9,999.
Parameter
,
,
or
=
hour meter of OUT1, OUT2, OUT3 or OUT4.
To view:-
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press until
to open the menu. Press or to scroll appears, press to view hours meter.
Press to go back, press or appears (if zone is present), press meter – repeat this process to view
until to view hours
or
Once complete, press
to exit, or wait for 30sec to
return to normal functions.
6.13.1 Reset the hour meter To reset the hour meter to zero
must be set to
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press until
to open the menu. Press or appears, press select
to scroll using
or , then press
Once complete, press
to exit, or wait for 30sec to
return to normal functions.
7. Optimiser Function
Only available when parameter /P5 = Yes
7.1 Optimised Start When the controller is in Auto mode it is possible to select the working period optimisation. Through this function, it is possible to reach the desired temperature at a fixed
time. This will help reduce energy usage.
This is the result of constantly controlling the ambient temperature in every
zone, of the set point value (which is set by the user for that specific zone)
of the system temperature increase in degrees/hr and the value of the out-
side temperature.
In this way, the system is able to set out and if necessary to revise the pre- start period required to reach the desired temperature. The absence of any connections to external events in defining the starting period erases all possible interferences caused by internal or external climatic changes in the room. In the event of an unexpected increase of the system heating efficiency, due for instance to a different humidity value of the air, the electricity supply will immediately be interrupted until the next analysis of the variables.
The parameters for this function [t0, tr] are set by the manufacturer to standard levels. Please check them with regard to the specific controller.
7.2 Optimised off Through this function, it is possible to maintain the desired temperature during the timer period, but also to avoid excessive temperature in the space when the timer program switches off. This will help reduce energy usage.
During the last t3A*10 minutes of the timed program in progress, the working temperature decreases to SP t3b.
Once an external sensor has been installed: –
Ensure you are in home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or key until the menu appears.
Press to select. The display now shows “PA” the standard password value will be displayed, “00”.
Press or to set the password to “95”. The thermostat stays accessible and remembers the password for 4 minutes.
Press , the display shows the first parameter of the list enabled by the
password.
Press or to scroll through menu options until /P5 appears, press to select.
If external sensor is installed, using or select Yes and press to confirm (if there is no external sensor installed, then select No)
To exit and save changes, either press 15sec.
, or wait for
11
8. Alarms/Failures
In the event of an alarm/failure the display will show the icon and the
message `ALARM’. The SCB30 can
signal up to 10 alarm events.
To access the list of pending alarms/failures press
the display shows the first menu item
(alarms).
Press to select, use or to scroll through
the list.
To mute the buzzer (if Ab=1), press any key. The alarm condition keeps showing
on display until removal of the alarm cause.
Temperature Alarms Temperature
AH AH-Ad
For example, if the display shows it means that the sensor in zone 1, P1 is damaged. Alarm code No. 20.
To exit the alarm menu, repeatedly press 30sec
or wait
SP
AL+Ad AL
Alarm menu
is only available and accessible in
the event of alarm/failures.
Display Icon Description
A 10
Eeprom fault, switch the controller off and on again.
A 13
Clock error, check date and time.
Sensor P1 in short circuit, or not connected, or
A20
temperature exceeds limits. In case of faulty P1
OUT1 is OFF.
Sensor P2 in short circuit, or not connected, or
A 21
temperature exceeds limits. In case of faulty P2
OUT2 is OFF.
Sensor P3 in short circuit, or not connected, or
A 22
temperature exceeds limits. In case of faulty P3
OUT3 is OFF.
Sensor P4 in short circuit, or not connected, or
A 23
temperature exceeds limits. In case of faulty P4
OUT4 is OFF.
Outside sensor in short circuit, or not con-
A 30
nected, or temperature exceeds limits. Check the cable to the sensor. Alarm stops once the
temperature retuns to normal values.
A 40
Temperature alarm.
A 60
Heater lock-out zone 1
A 61
Heater lock-out zone 2
A 62
Heater lock-out zone 3
A 63
Heater lock-out zone 4
A64
Zone 1 high temperature alarm
A65
Zone 1 low temperature alarm
A 66
Zone 2 high temperature alarm
A 67
Zone 2 low temperature alarm
A 68
Zone 3 high temperature alarm
A 69
Zone 3 low temperature alarm
A 70
Zone 4 high temperature alarm
A 71
Zone 4 low temperature alarm
ON HT
OFF
LT Alarm
Parameter AL and AH values are the alarm absolute limits of low temperature Lt and high temperature Ht of all zones. They are fixed and do not track the set- point value when it is changed.
AL=LSL (LSL = bottom end of scale). The low temperature alarm is equal to sensor fault alarm E1. AH=LSH (LSH = top end of scale). The low temperature alarm is equal to sensor fault alarm E1.
Other alarm signals
Keypad locked (see 6.9) Controller is in standby mode. Note power is still .
connected.
9. Parameter Menus Overview
To set the parameters of the controller, access one of the following menus:-
P /: Sensor parameters P r: Regulator parameters, set point settings P L: Output parameters P A: Alarm parameters P t: Timer parameters P H: Other parameters
These menus gather the parameters for the relevant function. Inside each menu, only the parameters enabled by the password entered, will be shown.
To access, ensure you are in home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the Press to select.
or key until the menu appears.
12
The display now shows “PA” the standard password value will be displayed, “00”.
There are 3 parameter lists:
“User”, “Installer” & “Factory”. The “User” password can be set by user via
parameter PA1.
Press or to set the password (for passwords see sect 10.). The thermostat stays accessible and remembers the password for 4 minutes.
Press , the display shows the first parameter of the list enabled by the password.
Press or to scroll through menu options, press
to select. Adjust values using or . Press to confirm and go back to the
parameter list. If only one option is available within a menu, then values
will be shown directly.
To exit and save changes, either press 15sec.
, or wait for
NO access to the menus will be possiblewhen the keypad is locked, or controller is in standby mode.
Cod Description
PA Range
UM Def
P-/: Sensor Parameters
/C1 Sensor P1 calibration
U LLD..LHD OC/OF 0.0
/C2 Sensor P2 calibration
U LLD..LHD OC/OF 0.0
/C3 Sensor P3 calibration
U LLD..LHD OC/OF 0.0
/C4 Sensor P4 calibration
U LLD..LHD OC/OF 0.0
/C5
External sensor P5 calibration
U LLD..LHD OC/OF 0.0
/P5
Presence of external sensor – No/Yes
I No..Yes
–
no
K-C Inputs for sensor with
/Pb
key selector, or for BMS 1 = Key selector on sensor
I
1…2
2 = BMS contact
–
1
/S Inputs reading stability
I 0…5
–
2
P-r: Regulator Parameters/Set point Setting
rd Set point differential
U 0.1..LHD OC/OF 0.5
rEU Temperature scale OC/OF
I OC…OF
–
OC
rt
Safety set point. 0 = Outputs off
U 0…LHD OC/OF 6
rL
Low temperature limit SPx x = 1, 2, 3 or 4
I
-50/-58 …rH
OC/OF
10
rH
High temperature limit SPx x = 1, 2, 3 or 4
I
rL.. 110/230
OC/OF
30
P-L: Output Parameters
L0
Output time delay at power on
F 15…250
S
15
L2 Reset pulse duration
F 1…30
S
3
Cod Description
PA Range
P-A: Alarm Parameters
Activate and mute buzzer
0 = no buzzer when in
Ab alarm
I 0…1
1= buzzer when in alarm
Press a key to mute buzzer
UM Def
–
1
Ad Alarm differential
I 0.1…LHD OC/OF 5
Low temperature alarm. AL It shows the value beyond
which an alarm occurs.
U
-50/50.. AH
High temperature alarm. AH It shows the value beyond
which an alarm occurs.
U
AL. 110/230
OC/OF -50 OC/OF 99.9
A3
Alarm delay at SCB30 power on
P-t: Timer Parameters
Maximum pre-start time t0 of programs. 0= function
of pre-start excluded
tr
Efficiency of heating system
Over-ride function durat2 tion
0=function disabled
U 0…250 min 0
U 0…6 Hours 0 0.1…12 OCHour
I 0.1…24.8 OFHour 3.0 U 0…250 Min 180
t3A Optimisation off duration U 0…6 Min*10 2
t3b
Set point reduction during optimisation off
U
0.1…2.0 0.1…4.0
OC OF
1.0
P-H: Other Parameters
Enable/disable on/off key
Hb 0=On/off key disabled
U No…Yes
–
Yes
1=On/off key enabled
HH
Read only: Firmware release
U
–
–
–
Working mode of SCB30
1= 1 zone. Connect P1
2 = 2 zones.
H5*
Connect P1 & P2 3 = 3 zones.
C 1…4
Connect P1, P2 & P3
4= 4 zones.
Connect P1, P2, P3 & P4
–
1
Enable/disable on/off key
HL 0=On/off key disabled
U No…Yes
–
Yes
1=On/off key enabled
PA1 User parameters password U 0…250
–
0
Note: LLD and LHD are the bottom and top ends of scale. They vary according to
the thermometric scale °C/°F, see parameter rEU. With PTC sensor, they are.
· LLD= -99.9°C / -178°F · LHD= 99.9°C / 178°F ·
(*): Any changes to setting H5 requires the SCB30 to be restarted.
13
10. Parameter passwords
Type Description
PA
U User parameters.
See PA1
I
Installer parameters, carefully read instructions before changing.
95
Factory parameters. These parameters
are factory set, the default values can be different from the suggested ones.
F Modifying these parameters can cause 59 a controller malfunction. Factory
parameters include
Installer and User parameters.
11. Firmware version
To view the firmware and build version:-
Ensure you are on the home screen
Press the key.
Switches off and the display
shows the first menu item.
Scroll the menu using the or menu appears.
key until the
Press to open the menu. Press or through settings to view:-
to scroll
HH3: Press to display firmware version
HH3b: Press to display build version of HH3
Once the desired option is shown, press to display the current setting. To exit, repeatedly press or wait 30sec to return to normal functions.
14
12. Wiring Connections
12.1 Single Stage U, Linear & Double Linear Models
SCB30
Alarm Lamps
Optional External Sensor
CPK
Room Sensor Zone 1
Zone 3
Zone 4
Zone 2
Connect when key operated sensor is used
Volt-free contacts when BMS is used
Repeat above sensor connections for each zone installed
Outputs
OUT1 OUT2 OUT3 OUT4
3A Fused Isolator
Zone 1
U Tube Heaters
3A Fused Isolator
Linear Heaters
3A Fused Isolator
Zone 2
(If fitted)
U Tube Heaters
3A Fused Isolator
Linear Heaters
230Vac
3A Fused Isolator
Maximum of 10 heaters
3A Fused Isolator
3A Fused Isolator
Double Linear Heaters
Maximum of 10 heaters
3A Fused Isolator
Double Linear Heaters
15
12.2 Single Stage SRP Models SCB30
Alarm Lamps
Optional External Sensor
CPK
Room Sensor Zone 1
Zone 3
Zone 4
Zone 2
Connect when key operated sensor is used
Volt-free contacts when BMS is used
Repeat above sensor connections for each zone installed
Outputs
OUT1 OUT2 OUT3 OUT4
3A Fused Isolator
Zone 1
3A Fused Isolator
Zone 2
(If fitted)
3A Fused Isolator
3A Fused Isolator
230Vac
3A Fused Isolator
Maximum of 25 heaters
3A Fused Isolator
Maximum of 25 heaters
16
12.2 Apollo or Eclipse Electric models
SCB30
Alarm Lamps
Optional External Sensor
CPK
Room Sensor Zone 1
Zone 3
Zone 4
Zone 2
Connect when key operated sensor is used
Volt-free contacts when BMS is used
Repeat above sensor connections for each zone installed
Outputs
OUT1 OUT2 OUT3 OUT4
Zone 1
3A Fused Isolator
Coil
1 or 3 phase supply to suit heater rating
Contactor (by others)
Zone 2 (If fitted)
3A Fused Isolator
1 or 3 phase supply to suit heater rating
Coil
Contactor (by others)
230Vac
3A Fused Isolator
Coil
1 or 3 phase supply to suit heater rating
Contactor (by others)
3A Fused Isolator
Coil
1 or 3 phase supply to suit heater rating
Contactor (by others)
Maximum of 15 heaters
Maximum of 15 heaters
17
®
Gas Fired Products (UK) Ltd
Chapel Lane Claydon, Ipswich
Suffolk, IP6 0JL Tel: +44(0)1473 830 551
www.spaceray.co.uk info@spaceray.co.uk
FACTORIES: IPSWICH, ENGLAND – CHARLOTTE, N.C, U.S.A
18
SCB30 Manual May 24
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>