Product Information

Specifications

  • Plenum-rated controllers with line voltage relay(s) and 0-10 volt dimming output(s)
  • Plug n’ GoTM automatic configuration for quick installation and maximum energy efficiency
  • Knockout mounting for easy installation; Class 1 and/or Class 2 connection for 0-10V wiring
  • Available with or without metering (+/- 2% accuracy)

Product Usage Instructions

Description
LMRC-110 series room controllers include one or two relay(s) to switch a total of 10 amps, a high-efficiency switching power supply, and dual 0-10 volt outputs per relay for control of dimmable loads including compatible LED drivers or electronic ballasts. They are the foundation of a Digital Lighting Management (DLM) system and allow integration of occupancy sensors, daylighting controls, and switches for energy-efficient control.

Operation Features

  • Store 16 scene preset levels for each load
  • Support energy-saving manual-on, partial-on, and dimming control strategies
  • Room controllers include circuitry to open their 0-10V signal on loss of LMRC’s power

Plug N’ Go Automatic Configuration

Applications
LMRC-110 series room controllers are ideal for single or multiple zone on/off or dimming control applications including private offices, open offices, conference rooms, and classrooms. Metering models help facility managers who want to track building power usage for lighting or other loads.

FAQ

  • Q: What are the available options for the LMRC-111 series room controllers?
    A: The LMRC-111 series is available as follows:

    • LMRC-111: 1 Relay Room Controller, 0-10V dimming
    • LMRC-111-U: 1 Relay Room Controller, 0-10V dimming, BAA/TAA compliant*
    • LMRC-111-M: 1 Relay Room Controller, 0-10V dimming, with meter
    • LMRC-111-M-U: To be continued…

DESCRIPTION

LMRC-110 series room controllers include one or two relay(s) to switch a total of 10 amps, a high-efficiency switching power supply and dual 0-10 volt outputs per relay for control of dimmable loads including compatible LED drivers or electronic ballasts. They are the foundation of a Digital Lighting Management (DLM) system, and allow the integration of occupancy sensors, daylighting controls and switches for energy-efficient control.legrand-
LMRC-110-Series-Room-Controllers- \(1\)

OPERATION

LMRC-110 series room controllers operate on one 120 or 277-volt, 10-amp feed and provide Class 2 power to sensors and switches via the DLM local network. Once powered up, Plug n’ Go automatically configures system components for the most energy-efficient operation. The room controllers then dim or switch lighting or motor loads in response to input from the communicating devices. When a dimming input is received, the relay switches on when the dimmed level rises above zero, and off when it reaches zero, to coordinate control of power and the 0-10 volt signal to the load. They also monitor the current draw of the total connected load. Each room controller stores up to 16 scene preset levels for each dimmed output. Additionally, the LMCT-100-2 wireless configuration tool can be used for load configuration.

Room controllers include circuity to open their 0-10V signal on loss of LMRC’s power, so any separately powered ballast or driver connected to those 0-10V wires will go to full brightness.

PLUG N’ GO AUTOMATIC CONFIGURATION

DLM room controllers manage Plug n‘ Go automatic system configuration, which establishes functionality based on the installed components. When room controllers are connected only to occupancy sensors, the system defaults to automatic on/off operation. If a wall switch is added to a system with one load, the load defaults to manual-on/automatic-off operation. If there is a wall switch and multiple loads, load one turns on automatically, while additional loads default to manual-on control; all loads turn off automatically. At system startup, default dimming parameters are established including: levels for scene presets 1-4; fade times; and fade and ramp rates. Dimming and system parameters may be customized using Push n’ Learn.

APPLICATIONS
LMRC-110 series room controllers are ideal for single or multiple zone on/off or dimming control applications including private offices, open offices, conference rooms and classrooms. Metering models help facility managers who want to track building power usage for lighting or other loads. A network bridge (LMBC-300) is required to expose DLM local network power measurement readings to a segment manager or BAS.

FEATURES

  • Push n’ Learn™ functionality for personalization without the need for tools or a PC
  • Digital Lighting Management components plug together on a free-topology Cat 5e DLM local network eliminating wiring errors
  • On/Off/Dim local override button for each load
  • LED indicates status of each load
  • 0-10V signal opens on loss of LMRC power
  • Optional lamp burn-in; 12 or 100 hours
  • Optional instantaneous current and voltage measurement of total connected load
  • 2 RJ45 ports; molded cable tie ring for strain relief
  • Zero-crossing circuitry for each relay for reliability and increased product life
  • UL 2043 plenum-rated
  • This product meets the materials restrictions of RoHS
  • BAA/TAA-compliant models available

SPECIFICATIONS

  • Voltage: 120/277VAC; 50/60Hz
  • Maximum 10A combined load per Room Controller; each relay rated for 10A ballast, E-ballast or incandescent
  • Galvanically isolated Class 1 pigtails and Class 2 terminals for 0-10VDC signal; sinks up to 50mA per output (Class 1/Class 2) per channel for control of compatible ballasts (25 if each sources 2mA)
  • In VDC, up to 150mA across 2 RJ45 ports
  • DLM local network parameters:
    • Maximum current: 800mA
    • Category 5e cable: 150’ per device to 1,000’ max.
    • Up to 64 loads
    • Up to 48 communicating devices
    • Maximum 4 LMPB-100, LMPL-101 or LMRC-100 Series Room Controllers
  • Operating conditions: for indoor use only; @120/277V: 32- 131°F (0-55°C); 5-95% RH, non-condensing
  • UL and cUL listed (E101196), Complementary Listed to Emergency Lighting Equipment (UL924)
  • FCC part 15 compliant
  • Five year warranty

CONTROLS & MOUNTING

legrand-LMRC-110-Series-Room-Controllers- \(2\)

Load Parameter (for each dimmed output)| Default Setting| Available Options
---|---|---
High trim| 85%| 1-100%
Low trim| 0%| 0-99%
Preset On Level| 50%| 0-100%
Preset level: Scenes 1-16| 1: 100%, 2: 75%, 3: 50%, 4: 25%, 5-16: 100%| All: 0-100%
Preset fade time| 2 seconds| 0 seconds – 18 hours
Lamp burn in time| 0| 0, 12 or 100 hours

SAMPLE CONNECTION DIAGRAM WITH CLASS 1 & CLASS 2 DIMMING CONTROL WIRING

legrand-LMRC-110-Series-Room-Controllers- \(3\)

Wire Color Function
Black Line In
White Neutral
Red Load A Switched Hot
Yellow Load B Switched Hot
Purple Load A 0-10V (+)
Pink Load A 0-10V (–)
Purple/Yellow Load B 0-10V (+)
Pink/Yellow Load B 0-10V (–)

NOTE: Per UL, starting in 2021, the 0-10V negative dimming wire color has been changed from gray to pink.

ORDERING INFORMATION

Catalog #| Description| Voltage| Total Rating| Class 2 Outputs
---|---|---|---|---
 | LMRC-111| 1 Relay Room Controller, 0-10V dimming|  | 10A ballast, E-ballast or incandescent| 24VDC, 150mA and 0-10VDC (0-10VDC signal also provided as Class 1)
 | LMRC-111-U| 1 Relay Room Controller, 0-10V dimming, BAA/TAA compliant|
 | LMRC-111-M| 1 Relay Room Controller, 0-10V dimming, with meter,|
 | LMRC-111-M-U| 1 Relay Room Controller, 0-10V dimming, with meter,|
BAA/TAA compliant
| 120/277VAC
 | LMRC-112| 2 Relay Room Controller, 0-10V dimming
 | LMRC-112-U| 2 Relay Room Controller, 0-10V dimming, BAA/TAA compliant|
 | LMRC-111-M| 2 Relay Room Controller, 0-10V dimming, with meter,|
 | LMRC-111-M-U| 2 Relay Room Controller, 0-10V dimming, with meter,|
BAA/TAA compliant
|
 | LMCT-100-2| Digital Wireless Configuration Tool|

*Product is compliant with Buy American Act and Trade Agreement Act