Friedrich MW, MR Series Split Type Room Air Conditioner
Specifications
INDOOR UNIT | MW09C1F | MW12C1F |
---|---|---|
OUTDOOR UNIT | MR09C1F | MR12C1F |
COOLING CAPACITY | 9,700 BTU/hr | 12,300 BTU/hr |
ELECTRICAL DATA
POWER SOURCE | 115 V | 115 V |
---|---|---|
FREQUENCY | 60 Hz | 60 Hz |
RUNNING CURRENT | 7.6 A | 9.8 A |
INPUT WATTS | 820 W | 1,060 W |
SEER | 14.3 | 13.5 |
MOISTURE REMOVAL | 2.1 Pts/hr (1.0 L/hr) | 3.2 Pts/hr (1.5 L/hr) |
AIR CIRCULATION-HIGH | 560 m3/hr | 660 m3/hr |
COMPRESSOR
TYPE
| Hermetic type, Permanent split condenser, 2 pole, Single phase, Induction
motor
---|---
DISCRIMINATION| EA89X1C-1FZDU1| EA118X1C-1FZDU1
POWER SOURCE| 115V 60Hz| 115V 60Hz
REFRIGERANT R-410A| 1 lb.9 oz ( 700 g )| 2 lb. 2 oz ( 950 g )
FAN MOTOR
POWER SOURCE | 115 V | 115 V |
---|
INDOOR UNIT
| HIGH| 1,250 r.p.m.| 1,450 r.p.m.
MED| 1,100 r.p.m.| 1,250 r.p.m.
LOW| 950 r.p.m.| 1,050 r.p.m.
QUIET| 800 r.p.m.| 850 r.p.m.
OUTDOOR UNIT| 640 r.p.m.| 770 r.p.m.
DIMENSIONS
INDOOR UNIT HxWxD
| 10-13/16 x 31-1/8 x 9-7/16 inch
---|---
275 x 790 x 215 mm
OUTDOOR UNIT HxWxD
| 21-1/4 x 31-1/8 x 11-7/16 inch
540 x 790 x 290 mm
WEIGHT
INDOOR UNIT | Gross / Net | 26 / 20 lbs. | (12/9 kg) |
---|---|---|---|
OUTDOOR UNIT | Gross / Net | 77 / 68 lbs. (35 / 31 kg ) | 86 / 77 lbs. (39 / 35 |
kg )
OUTLINE AND DIMENSIONS
- Unit: inch (mm)
- Models :
- MW09C1F / MR09C1F
- MW12C1F / MR12C1F
INDOOR UNIT
OUTDOOR UNIT
REFRIGERANT SYSTEM DIAGRAM
-
Models :
- MW09C1F / MR09C1F
- MW12C1F / MR12C1F
CIRCUIT DIAGRAM
- Models :
- MW09C1F / MR09C1F
- MW12C1F / MR12C1F
INDOOR PCIRCUITB CIRCUIT DIAGRAM
- Models :
- MW09C1F, MW12C1F
- Models :
- M W09C1F, MW12C1F
OUTDOOR PCB CIRCUIT DIAGRAM
- Models :
- MR09C1F, MR12C1F
- Models :
- MR09C1F, MR12C1F
- CONTROLLER PCB ASSEMBLY ( MAIN PCB )
- MR09C1F : K04DK-0402WUE-C0
- MR12C1F : K04DK-0403WUE-C0
Product Usage Instructions
Installation
- Select a suitable location on the wall for mounting the indoor unit.
- Install the outdoor unit on a stable platform with proper ventilation.
- Connect the indoor and outdoor units using the provided refrigerant lines and electrical connections.
- Ensure proper insulation of the refrigerant lines to prevent energy loss.
Operation
- Turn on the power supply and set the desired temperature using the remote controller.
- Select the fan speed and mode according to your comfort preferences.
- The air conditioner will start cooling the room and maintain the set temperature.
ERROR CONTENTS
Kind of error
| Indication on LED| ****
Indication on wired remote controller
| ****
Contents
---|---|---|---
Operation LED (red)| Timer LED (green)
Communication
| ****
Off
| 0.5 sec / twice| ****
01
| Serial (reverse) error after operation
0.5 sec / three times| Serial (reverse) error during operation
0.5 sec / four times| Serial (forward) error after operation
0.5 sec / five times| Serial (forward) error during operation
Indoor unit Thermistor
| ****
0.5 sec / twice
| ****
0.5 sec / twice
| ****
02
| Room temp. thermistor error
open / short
0.5 sec / three times
| ****
04
| Heat exchange (middle) thermistor error
open / short
Outdoor unit Thermistor
| ****
0.5 sec / three times
| ****
0.5 sec / three times
| ****
06
| Heat exchange thermistor error
open
0.5 sec / four times
| ****
0A
| Outdoor temp. thermistor error
open / short
Indoor unit PCB
| ****
0.5 sec / four times
| ****
0.5 sec / eight times
| ****
21
| Opposite VDD permanent stop protection
(Electric aircleaner, circuit error)
Outdoor unit PCB| 0.5 sec / five times| 0.5 sec / six times| 1b| Outdoor
unit fan control error
Indoor unit fan motor
| ****
0.5 sec / six times
| 0.5 sec / twice| ****
12
| Lock
0.5 sec / three times| r.p.m abnormal
Power supply| 0.1 sec flashing on red and orange LED| No Indication| Power
supply abnormal
Model distinction| 0.1 sec flashing on all LED| 11| Model distinction
error
DISASSEMBLY ILLUSTRATION
INDOOR UNIT
OUTDOOR UNIT
PARTS LIST
INDOOR UNIT
Ref.
No
| Description| Part No.| Ord.
Q’ty
---|---|---|---
MW09C1F| MW12C1F
1| AIR FILTER| 67201200| 67201200|
4| FRONT PANEL COMPLETE| 67201201| 67201201
6| INTAKE GRILLE ASSY| 67201202| 67201202
7| GRILLE CLAMP| 67200936| 67200936
8| LOUVER U| 67201203| 67201203
9| LOUVER Z| 67201204| 67201204
10| LOUVER HOLDER| 67201205| 67201205
11| GEAR-A| 67201206| 67201206
12| CASING ASSY| 67201207| 67201207
13| CASING COVER-F| 67201208| 67201208
14| CASING COVER-B| 67201209| 67201209
15| CROSS FLOW FAN ASSY| 67201210| 67201210
18| SHAFT HOLDER-C| 67200922| 67200922
19| DRAIN HOSE ASSY| 67200913| 67200913
20| DRAIN CAP ASSY| 67201211| 67201211
22| SWITCH BOX ASSY| 67201212| 67201212
23| BOX SWITCH| |
24| EVAPORATOR ASSY| 67201214| 67201214
25| EVAPORATOR SEAL| |
26| JOINT PIPE ASSY| 67201216| 67201216
27| INSULATION ( PIPE) E| 67201217| 67201217
28| HOLDER (EVAP)-L| 67201218| 67201218
29| HOLDER (EVAP)-R| 67201219| 67201219
30| WATER SEAL| 67201220| 67201220
31| EVAPORATOR BRACKET| 67201221| 67201221
32| TERMINAL| 67201222| 67201222
33| CONTROLLER PCB ASSY| 67201223| 67201231
34| DISPLAY PCB ASSY| 67201224| 67201224
38| STEP MOTOR| 67201225| 67201225
39| FAN MOTOR| 67201226| 67201226
40| REMOTE CONTROL| 67201227| 67201227
41| GRILLE GUARD| 67201228| 67201228
42| BUSHING| 67201229| 67201229
43| FRONT PANEL| 67201230| 67201230
44| REMOTE CONTROL HOLDER| 67203202| 67203202
OUTDOOR UNIT
Ref.
No
| Description| Part No.| Ord.
Q’ty
---|---|---|---
MR09C1 F| MR12C1 F
1| COVER ( SWITCH (| 67201300| 67201300|
2| PROTECTIVE NET| 67201301| 67201301
3| BASE PAN| 67201302| 67201302
4| FAN BLADE| 67201303| 67201303
5| PANEL, TOP| 67201304| 67201304
6| MOTOR BRACKET| 67201305| 67201305
7| REM PLATE| 67201306| 67201306
8| CONDENSER ASY| 67201307| 67201338
9| SPACER ( RUBBER )| 67201308| 67201308
10| NUT, SPECIAL ASSY| 67201309| 67201309
11| DISCHARGE TUBE| 67201310| 67201339
12| COMPRESSOR| 67201311| 67201340
13| COMRESSOR BLANKET -A| 67201312| 67201312
14| COMRESSOR BLANKET -B| 67201313| 67201313
15| SUCTION TUBE| 67201314| 67201314
16| CAPILLARY ASSY| 67201315| 67201341
17| 2-WAY VALVE ASSY| 67201316| 67201316
18| 3-WAY VALVE ASSY| 67201317| 67201317
19| BRACKET, VALVE| 67201318| 67201318
20| CABINET, LEFT SIDE| 67201319| 67201319
21| PANEL (FRONT)| 67201320| 67201320
22| RING (FAN)| 67201321| 67201321
23| COVER TERMINAL C| 67201322| 67201322
24| SEPARATER C| 67201323| 67201323
25| BRACKRT CONDUIT| 67201324| 67201324
26| FAN MOTOR| 67201325| 67201325
27| CONTROL COVER| 67201326| 67201326
28| THERMISTOR ( OUTDOOR )| 67201327| 67201327
31| PWB ASSY| 67201328| 67201342
32| CAPACITOR| 67201329| 67201329
33| RELAY| 67201330| 67201330
34| FUSE HOLDER| 67201331| 67201331
35| TERMINAL| 67201332| 67201332
36| CLAMP, CAPACITOR| 67200954| 67200954
37| FUSE| 67201333| 67201333
38| CONTROL BOX ASSY| 67201334| 67201334
39| BRACKET TERMINAL| 67201335| 67201335
40| CABINET RIGHT| 67201336| 67201336
*| EMBLEM REAR, FRIEDRICH| 67201337| 67201337
STANDARD ACCESSORIES
Maintenance
- Clean the air filters regularly to ensure efficient operation.
- Check for any leaks in the refrigerant lines and have them repaired if necessary.
- Schedule annual maintenance checks by a certified technician to keep the unit in optimal condition.
Frequently Asked Questions
Q: How often should I clean the air filters?
A: It is recommended to clean the air filters every 2 weeks during heavy usage
periods.
Q: Can I install the air conditioner myself?
A: For safety and warranty reasons, it is recommended to have a professional
HVAC technician install the unit.