  • Cooling Efficiencies up to: 15.2 SEER2/9.8 EER2
  • Nominal   Sizes: 2 to 5 Ton [7.0 to 17.6 kW]
  • Cooling Capacities: 22.8 to 56.0 kBTU [6.68 to 16.4 kW]
  • FORM NO. AFR-336

Features and Benefits

  • 3-speed operation when installed with a 24V two-stage thermostat
  • Provides precise temperature control, advanced humidity control, and greater efficiency

Model Number Identification Brand| Product Category| SEER2| Region| Refrigerant Capacity BTU/HR| Major Series| Voltage| Type| Controls| Minor Series
---|---|---|---|---|---|---|---|---|---
A| All| 15 – 15.2 SEER2| Z – R-410A| 24 – 24,000 [7.03 kW] 36 – 36,000 [10.55 kW] 48 – 48,000 [14.07
kW] 60 – 60,000 [17.58 kW]| A – 1st Design| J – 1ph, 208-230/60| 3 – 3+ Stage| C – Communicating| A – 1st Design

General Data Model No.| Nominal Tonnage| Valve Connections| Number of blades| Motor hp| CFM| RPM| watts
---|---|---|---|---|---|---|---
FRA15AZ24AJ3| 2.0| 3/8| 3/4| 91| 11.79| —| 0.276 1 24
FRA15AZ36AJ3| 3.0| 3/8| 7/8| 119| 14.4| —| 0.276 1 24
FRA15AZ48AJ3| 4.0| 3/8| 7/8| 130| 16.42| —| 0.276 1 24
FRA15AZ60AJ3| 5.0| 3/8| 7/8| 154| 17.88| —| 0.276 1 24

Electrical Data

  • Line Voltage Data (Volts-Phase-Hz): 208/230-1-60
  • Rated load amps: 10 (FRA15AZ24AJ3), 15 (FRA15AZ36AJ3), 20 (FRA15AZ48AJ3), 25 (FRA15AZ60AJ3)
  • Locked rotor amps: 65 (FRA15AZ24AJ3), 70 (FRA15AZ36AJ3), 96 (FRA15AZ48AJ3), 119 (FRA15AZ60AJ3)

Accessories Model No.| Compressor crankcase heater*| Low ambient control| Compressor sound cover| Low-pressure control| High-pressure control| Liquid Line Solenoid (24 VAC, 50/60 Hz)| Solenoid Valve Solenoid Coil| Liquid Line Solenoid (120/240 VAC, 50/60 Hz)| Solenoid Valve Solenoid Coil
---|---|---|---|---|---|---|---|---|---
FRA15AZ24AJ3| N/A| 47-102709-10| 68-23427-27| 47-103454-01| 47-103669-02| 200RD2T3TVLC| 61-AMG24V| 200RD2T3TVLC| 61-AMG120/240V
FRA15AZ36AJ3| N/A| 47-102709-10| 68-23427-28| 47-103454-01| 47-103669-02| 200RD2T3TVLC| 61-AMG24V| 200RD2T3TVLC| 61-AMG120/240V
FRA15AZ48AJ3| N/A| 47-102709-10| 68-23427-29| 47-103454-01| 47-103669-02| 200RD2T3TVLC| 61-AMG24V| 200RD2T3TVLC| 61-AMG120/240V
FRA15AZ60AJ3| N/A| 47-102709-10| 68-23427-29| 47-103454-01| 47-103669-02| 200RD2T3TVLC| 61-AMG24V| 200RD2T3TVLC| 61-AMG120/240V

Weighted Sound Power Level (dBA) Unit Size Voltage, Series| Standard Rating (dBA)| Low Speed/ High Speed
---|---|---
FRA15AZ24AJ3| 71.7| 35.9, 47.9, 55.3, 53.2, 50.4, 47.1, 43.8
FRA15AZ36AJ3| 72.9| 38.5, 48.0, 53.8, 49.2, 45.9, 47.0, 47.4
FRA15AZ48AJ3| 76.2| 42.3, 45.9, 53.5, 48.9, 45.8, 59.1, 36.4
FRA15AZ60AJ3| 76.7| 39.7, 49.0, 58.2, 54.5, 52.2, 53.8,

Features and Benefits

  • EcoNet® Enabled: Automatic system configuration and optimization
  • PlusOne® Diagnostics & Bluetooth®1 Connectivity: With the Friedrich® Contractor & EcoNet® Apps, built-in technology makes advanced set-up, monitoring, troubleshooting, and repairing the product easier than ever before
  • PlusOne® Variable Speed Twin Rotary Compressor & Inverter Drive:
  • Features Inverter operation from 40 to 70% capacity or 100% capacity via line voltage with the EcoNet® Smart Thermostat
  • 3-speed operation when installed with a 24V two-stage thermostat
  • Provides precise temperature control, advanced humidity control, and greater efficiency
  • Swept Wing Fan Technology: Features quieter operation and improved unit acoustics
  • 7mm Condenser Copper Coil: Requires less refrigerant allowing for a smaller and lighter footprint while enhancing reliability
  • P lusOne® Expanded Value Space: 3 in. – 4 in. – 5 in. service valve space—provides a minimum working area of 27 square inches for easier access
  • PlusOne® Triple Service Access: 15 in. wide, industry leading corner service access, two fasteners, removable corner, and individual louver panels–makes repairs easier and faster

Air Conditioners

FRIEDRICH-F-Series-Plus-iM-Air-Conditioners-
FIG-1

  • FR – Friedrich® A – Air Conditioners 15 – 15.2 SEER2 A – All Z – R-410A 24 – 24,000 [7.03 kW] A – 1st Design J – 1ph, 208-230/60 3 – 3+ Stage C – Communicating A – 1st Design
  • 36 – 36,000 [10.55 kW]
    • 48 – 48,000 [14.07 kW]
  • 60 – 60,000 [17.58 kW]

Designates Metric Conversions

Available Models Description
FRA15AZ24AJ3CA Endeavor™ Line F-Series Plus 2 ton EcoNet® Enabled 3+ Speed

iM Air Conditioner – 208/230/1/60
FRA15AZ36AJ3CA| Endeavor™ Line F-Series Plus 3 ton EcoNet® Enabled 3+ Speed iM Air Conditioner – 208/230/1/60
FRA15AZ48AJ3CA| Endeavor™ Line F-Series Plus 4 ton EcoNet® Enabled 3+ Speed iM Air Conditioner – 208/230/1/60
FRA15AZ60AJ3CA| Endeavor™ Line F-Series Plus 5 ton EcoNet® Enabled 3+ Speed iM Air Conditioner – 208/230/1/60
Standard Equipment

R-410A Refrigerant
Variable Speed Twin Rotary Compressor
Field Installed Filter Drier
Front Seating Service Valves
Internal Pressure Relief Valve
Internal Thermal Overload
Long Line capability
Low Ambient capability with Kit
3-4-5 Expanded Valve Space
Composite Basepan
2 Screw Control Box Access
15″ Access to Internal Components
Quick-release louver panel design
No fasteners to remove along the bottom
Optimized Venturi Airflow
Single-row condenser coil
Powder coated paint
Rust resistant screws
QR code
External gauge ports
Service trays
General Data

Model No.| FRA15AZ24AJ3| FRA15AZ36AJ3| FRA15AZ48AJ3| FRA15AZ60AJ3
Nominal Tonnage| 2.0| 3.0| 4.0| 5.0
Valve Connections|
Liquid Line O.D. – in.| 3/8| 3/8| 3/8| 3/8
Suction Line O.D. – in.| 3/4| 3/4| 7/8| 7/8
Refrigerant (R410A) furnished oz.¹| 91| 119| 130| 154
Compressor Type| Twin Rotary
Outdoor Coil|
Net face area – Outer Coil| 11.79| 14.4| 16.42| 17.88
Net face area – Inner Coil| —| —| —| —
Tube diameter – in.| 0.276| 0.276| 0.276| 0.276
Number of rows| 1| 1| 1| 1
Fins per inch| 24| 24| 24| 24
Outdoor Fan|
Diameter – in.| 20| 24| 24| 26
Number of blades| 3| 3| 3| 3
Motor hp| 1/5| 1/5| 1/3| 1/2
CFM| 2908| 4138| 4529| 5274
RPM| 1075| 1000| 1075| 1075
watts| 170| 267| 294| 370
Shipping weight – lbs.| 174| 198| 230| 251
Operating weight – lbs.| 167| 191| 223| 244
Electrical Data
Line Voltage Data (Volts-Phase-Hz)| 208/230-1-60| 208/230-1-60| 208/230-1-60| 208/230-1-60
Maximum overcurrent protection (amps)²| 20| 30| 40| 50
Minimum circuit ampacity³| 12| 20| 25| 32
Compressor|
Rated load amps| 10| 15| 20| 25
Locked rotor amps| 65| 70| 96| 119

  1. Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
  2. HACR type circuit breaker of the fuse.
  3. Refer to the National Electrical Code manual to determine wire, fuse, and disconnect size requirements.

Accessories

Model No.| FRA15AZ24AJ3| FRA15AZ36AJ3| FRA15AZ48AJ3| FRA15AZ60AJ3
---|---|---|---|---
Compressor crankcase heater*| N/A| N/A| N/A| N/A
Low ambient control| 47-102709-10| 47-102709-10| 47-102709-10| 47-102709-10
Compressor sound cover| 68-23427-27| 68-23427-28| 68-23427-29| 68-23427-29
Low-pressure control| 47-103454-01| 47-103454-01| 47-103454-01| 47-103454-01
High-pressure control| 47-103669-02| 47-103669-02| 47-103669-02| 47-103669-02
Liquid Line Solenoid (24 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC
Solenoid Coil| 61-AMG24V| 61-AMG24V| 61-AMG24V| 61-AMG24V
Liquid Line Solenoid (120/240 VAC, 50/60 Hz)| Solenoid Valve| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC| 200RD2T3TVLC
Solenoid Coil| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V| 61-AMG120/240V

  • Crankcase Heater recommended with Low Ambient Kit.

Weighted Sound Power Level (dBA)

Unit Size – Voltage, Series| Standard Rating (dBA) Low Speed/ High Speed| TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)| Sound Power Level [dB(A)] with Sound Blanket
---|---|---|---
125| 250| 500| 1000| 2000| 4000| 8000
FRA15AZ24AJ3| 63.3| 35.9| 47.9| 55.3| 53.2| 50.4| 47.1| 43.8| ****



Sound Blankets – Standard

71.7| 46.1| 59.1| 63.2| 60.8| 58.7| 56.5| 47.9
FRA15AZ36AJ3| 61.4| 38.5| 48.0| 53.8| 49.2| 45.9| 47.0| 47.4
72.9| 47.5| 59.5| 64.9| 60.7| 62.6| 57.0| 49.6
FRA15AZ48AJ3| 63.8| 42.3| 45.9| 53.5| 48.9| 45.8| 59.1| 36.4
76.2| 49.4| 61.4| 68.1| 53.9| 60.8| 57.4| 48.5
FRA15AZ60AJ3| 65.7| 39.7| 49.0| 58.2| 54.5| 52.2| 53.8| 41.3
76.7| 49.3| 64.6| 68.1| 65.1| 62.6| 58.6| 53.0

NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Unit Dimensions


Model No.

| Operating| Shipping
---|---|---
H (Height)| L (Length)| W (Width)| H (Height)| L (Length)| W (Width)
Inches| mm| Inches| mm| Inches| mm| Inches| mm| Inches| mm| Inches| mm
FRA15AZ24AJ3| 27.00| 686| 29.75| 756| 29.75| 756| 28.50| 724| 32.38| 822| 32.38| 822
FRA15AZ36AJ3| 27.00| 686| 33.75| 857| 33.75| 857| 28.50| 724| 36.38| 924| 36.38| 924
FRA15AZ48AJ3| 31.00| 787| 33.75| 857| 33.75| 857| 32.50| 826| 36.38| 924| 36.38| 924
FRA15AZ60AJ3| 31.00| 787| 35.75| 908| 35.75| 908| 32.50| 826| 38.38| 975| 38.38| 975

FRIEDRICH-F-Series-Plus-iM-Air-Conditioners-FIG-2

Designates Metric Conversions

CLEARANCES

FRIEDRICH-F-Series-Plus-iM-Air-Conditioners-
FIG-3

Control Wiring

FRIEDRICH-F-Series-Plus-iM-Air-Conditioners-
FIG-4

Application Guidelines

  1. Intended for outdoor installation with free air inlet and outlet. The outdoor fan external static pressure available is less than 0.01 -in. WC.
  2. The minimum outdoor operation air temperature for a cooling mode without a low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, the unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at the unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed.

Refrigerant Line Size Information

15/16 SEER2 Variable Speed Air Conditioners



Unit Size

| ****


Allowable Liquid Line Size

| ****

Allowable Vapor Line Size

| Outdoor Unit ABOVE or BELOW Indoor Unit Equivalent Length (Feet)
< 25| 26-50| 51-75| 76-100| 101-125| 126-150
Maximum Vertical Separation / Capacity Multiplier



2.0 Ton

**SEE NOTE 3

| 1/4″| 5/8″| 25/1.00| 50/0.99| 32/0.98| 40/0.97| NR| NR
5/16″| 5/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
3/8″| 5/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.95
1/4″| 3/4″| 25/1.00| 50/1.00| 32/0.99| 40/0.99| NR| NR
5/16″| 3/4″
| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98
3/8″| 3/4″**| 25/1.00| 50/1.00| 50/0.99| 50/0.99| 50/0.99| 50/0.98



3 Ton

| 5/16″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 37/0.91| NR
3/8″| 5/8″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
5/16″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 37/0.97| 22/0.96
3/8″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96
1/2″| 3/4″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.97| 50/0.96



4 Ton

| 3/8″| 3/4″| 25/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.94| 50/0.93
1/2″| 3/4″| 25/0.99| 50/0.98| 50/0.97| 50/0.96| 50/0.94| 50/0.93
3/8″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97
1/2″| 7/8″| 25/1.00| 50/0.99| 50/0.99| 50/0.98| 50/0.98| 50/0.97



5 Ton

| 3/8″| 3/4″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
1/2″| 3/4″| 25/0.99| 50/0.97| 50/0.95| 50/0.93| 50/0.91| NR
3/8″| 7/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.98| 50/0.97| 38/0.96
1/2″| 7/8″| 25/1.00| 50/0.99| 50/0.98| 50/0.98| 50/0.97| 50/0.96

NOTES:

  1. Do not exceed 150 ft. linear line length.
  2. Do not exceed 50 ft. vertical separation between indoor and outdoor units.
  3. A 3/4″ suction line should only be used for 2-ton systems if the outdoor unit is below or at the same level as the indoor unit to ensure proper oil return.
  4. Always use the smallest liquid line allowable to minimize refrigerant charge.
  5. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended but are allowed.
  6. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Refrigerant Line Size Information

15/16 SEER2 Variable Speed Air Conditioners



Unit Size

| ****


Allowable Liquid Line Size

| ****

Allowable Vapor Line Size

| Outdoor Unit ABOVE or BELOW Indoor Unit Equivalent Length (Meters)
< 25| 26-50| 51-75| 76-100| 101-125| 126-150
Maximum Vertical Separation / Capacity Multiplier



2.0 Ton

**SEE NOTE 3

| 6.35 [1/4]| 15.88 [5/8]| 8/1.00| 15/0.99| 10/0.98| 10/0.97| NR| NR
7.94 [5/16]| 15.88 [5/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
9.53 [3/8]| 15.88 [5/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.95
6.35 [1/4]| 19.05 [3/4]| 8/1.00| 15/0.99| 10/0.99| 12/0.99| NR| NR
7.94 [5/16]| 19.05 [3/4]
| 8/1.00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.98
9.53 [3/8]| 19.05 [3/4]**| 8/1.00| 15/0.99| 15/0.99| 15/0.99| 15/0.99| 15/0.98



3 Ton

| 7.94 [5/16]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 11/0.91| NR
9.53 [3/8]| 15.88 [5/8]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
7.94 [5/16]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 11/0.97| 7/0.96
9.53 [3/8]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96
12.7 [1/2]| 19.05 [3/4]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.97| 15/0.96



4 Ton

| 9.53 [3/8]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.94| 15/0.93
12.7 [1/2]| 19.05 [3/4]| 8/0.99| 15/0.98| 15/0.97| 15/0.96| 15/0.94| 15/0.93
9.53 [3/8]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15/0.97
12.7 [1/2]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.99| 15/0.98| 15/0.98| 15/0.97



5 Ton

| 9.53 [3/8]| 19.05 [3/4]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
12.7 [1/2]| 19.05 [3/4]| 8/0.99| 15/0.97| 15/0.95| 15/0.93| 15/0.91| NR
9.53 [3/8]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.98| 15/0.97| 12/0.96
12.7 [1/2]| 22.23 [7/8]| 8/1.00| 15/0.99| 15/0.98| 15/0.98| 15/0.97| 15/0.97

NOTES:

  1. Do not exceed 46 meters of linear line length.
  2. Do not exceed 15 meters of vertical separation between indoor and outdoor units.
  3. 19.05mm [3/4 in.] vapor line should only be used for 2-ton systems if the outdoor unit is below or at the same level as the indoor unit to assure proper oil return.
  4. Always use the smallest liquid line allowable to minimize refrigerant charge.
  5. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended but are allowed.
  6. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Additional Oil, Oz.

Lineset Length| 50| 60| 70| 80| 90| 100| 110| 120| 130| 140| 150
2T| N/A| N/A| N/A| N/A| N/A| 1| 2| 3| 5| 6| 7
3T| N/A| N/A| N/A| N/A| N/A| N/A| 1| 2| 3| 5| 6
4T| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A
5T| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A| N/A

Performance Data @ AHRI Standard Conditions – Cooling

Designated Tested Combination (DTC)

Outdoor Unit| Air Handler| Total Capacity BTU/H [kW]| Net Sensible BTU/H [kW]| Net Latent BTU/H [kW]| SEER2| EER2| Indoor CFM [L/s]
FRA15AZ24AJ3| FRH3VZ2417STACN| 22,800 [6.7]| 17,600 [5.2]| 5,200 [1.5]| 15.2| 9.8| 750 [354.0]
FRA15AZ36AJ3| FRH3VZ3617STACN| 34,200 [10.0]| 26,600 [7.8]| 7,600 [2.2]| 15.2| 9.8| 1,125 [530.9]
FRA15AZ48AJ3| FRH3VZ4821STACN| 45,500 [13.3]| 35,500 [10.4]| 10,000 [2.9]| 15.2| 9.8| 1,425 [672.5]
FRA15AZ60AJ3| FRH3VZ6024STACN| 55,500 [16.3]| 43,000 [12.6]| 12,500 [3.7]| 15.2| 9.8| 1,675 [790.5]

NOTE: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, can be accessed from the AHRI website: www.ahridirectory.org.

Integrated Controls

EcoNet® is smart, technology that allows Heating and Cooling, products to communicate with each other on one integrated network.

THE ECONET® SMART THERMOSTAT

  • BUILT-IN WIFI
  • 4.3″ LCD TOUCH SCREEN
  • LOCAL WEATHER – Current conditions plus 6-day forecast
  • 5 OPERATING MODES – Heat, Cool, Auto, Emergency Heat and Fan Only
  • 7-DAY PROGRAMMABLE SCHEDULE – Offers comfort without thought
  • ONE-TOUCH AWAY – Quickly switch to your energy-saving away preferences
  • VACATION SCHEDULING – Allows you to save while you’re away and come home to comfort
  • STANDBY SCREEN – Displays indoor temperature and current weather

OPERATIONAL FEATURES

  • AUTOMATIC CHANGEOVER – Transitions between heating and cooling automatically to keep the house comfortable
  • INTEGRATED WATER CONTROL – Enables easy water heater management
  • SMOOTH ARRIVAL – Prompts the system to start ahead of schedule to ensure the home is at the desired temperature at the scheduled time
  • HUMIDITY CONTROL – Supports humidifier accessories or over-cool-based dehumidification
  • DETAILED OPERATING STATUS – View pertinent equipment status information and run times
  • CONTINUOUS FAN – Offers 5 speeds (Low, Medium Low, Medium, Medium High, High)
  • SHORT-CYCLE PROTECTION – Avoids damage to equipment from short-run cycles
MONITORING & REMOTE CONTROL FEATURES
  • ACTIVE MONITORING – Alerts to problems that need immediate attention
  • REMOTE CONTROL – Allows adjusting of comfort and settings from anywhere using a mobile device
  • SERVICE ALERTS – Sends routine maintenance reminders
  • AIR FILTER MONITORING – Detects when it’s time to replace the air filter
  • ALARM HISTORY – Displays time-stamped alarm codes with clear descriptions

GENERAL TERMS OF LIMITED WARRANTY

  • Friedrich® will furnish a replacement for any part of this product that fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
  • For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.
  • Conditional Parts (Registration Required) …………………………….. Ten (10) Years
  • Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
  • © 2023 Rheem Manufacturing Company. Friedrich trademarks are owned by Rheem Manufacturing Company.
  • In keeping with its policy of continuous progress and product improvement, Friedrich reserves the right to make changes without notice.
  • Friedrich  5600 Old Greenwood Road
  • Fort Smith, Arkansas 72908 www.friedrich.com

Documents / Resources

| FRIEDRICH F-Series Plus iM Air Conditioners [pdf] User Manual
FRA15AZ24AJ3CA, FRA15AZ36AJ3CA, FRA15AZ48AJ3CA, FRA15AZ60AJ3CA, F-Series Plus iM Air Conditioners, F-Series Plus, iM Air Conditioners, Air Conditioners, Conditioners
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

FRIEDRICH User Manuals

Related Manuals