Features and Benefits

  • Swept Wing Fan Technology1: Features quieter operation and improved unit acoustics
  • Two-Stage Scroll Compressor2: Features two speeds (high and low) of cooling and heating, providing more precise temperature control, lower humidity and greater efficiency when compared to single stage compressors
  • Inverted Reversing Valve: Allows for faster heat transfer with gravity assist shifting and reduced joint stress for increased reliability
  • PlusOne® Expanded Valve Space: 3 in. ­ 4 in. ­ 5 in. service valve space–provides a minimum working area of 27-square inches for easier access
  • PlusOne® Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels–makes repairs easier and faster

Model Number Identification

Heat Pumps

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual - Heat
Pumps

GENERAL DATA

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual - General
Data

Electrical Data

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
Electrical Data

¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required. ²HACR type circuit breaker of fuse. ³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

Accessories

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
Accessories

Weighted Sound Power Level (dBA)

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
Weighted Sound Power Level

Unit Dimensions

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual - Unit
Dimensions FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual - Unit
Dimensions

CLEARANCES

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
CLEARANCES

Control Wiring

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual - FIGURE
4

NOTES:

  1. Jumper “E” to “W2” to transfer control of supplemental heat to 1st stage when the emergency heat switch is on.
  2. This wire turns on heat for defrost, omit for most economical operation.
  3. Wire with colored tracing stripe.

Application Guidelines

  1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
  2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed.

Refrigerant Line Size Information

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
Refrigerant Line Size Information FRIEDRICH FRP14AZ
Endeavor Line F-Series iM Heat Pumps User Manual - Refrigerant Line Size
Information FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat
Pumps User Manual - Refrigerant Line Size Information FRIEDRICH FRP14AZ
Endeavor Line F-Series iM Heat Pumps User Manual - Refrigerant Line Size
Information

NOTES:

  1. *Do not exceed 200 ft linear line length.
  2. *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit.
  3. *Always use the smallest liquid line allowable to minimize refrigerant charge.
  4. *Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  5. *Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.

Performance Data

Performance Data @ AHRI Standard Conditions ­ Cooling

FRIEDRICH FRP14AZ Endeavor Line F-Series iM Heat Pumps User Manual -
Performance Data @ AHRI Standard Conditions – Cooling

WARRANTY

**GENERAL TERMS OF LIMITED WARRANTY**
Friedrich® will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Parts (Registration Required)……………………………Ten (10) Years

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

© 2023 Rheem Manufacturing Company. Friedrich trademarks owned by Rheem Manufacturing Company. In keeping with its policy of continuous progress and product improvement, Friedrich reserves the right to make changes without notice.

Friedrich · 5600 Old Greenwood Road Fort Smith, Arkansas 72908 · www.friedrich.com

Friedrich · 125 Edgeware Road, Unit 1 Brampton, Ontario · L6Y 0P5

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

FRIEDRICH User Manuals

Related Manuals