MAJESTIC SR36A 36 Inch Radiant Wood Burning Fireplace Owner’s Manual

July 6, 2024
Majestic

MAJESTIC SR36A 36 Inch Radiant Wood Burning Fireplace

Safety Information

Please read this manual before installing and using FIREPLACE.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard and will void the warranty.

Description

  • The SR/SC Series “A” fireplaces are solid fuel, wood-burning premium fireplaces. The SR36A/42A are radiant clean-face models and the SC36A/42A are circulating models with removable grilles (louvers). Both models are fully insulated fireplaces.

Precautions

MHSC fireplaces and parts have been highly tested and will operate safely when installed by instructions provided in this manual. Carefully read and understand all instructions before beginning installation.
If you notice any damage to fireplace or parts, immediately report damage to your MHSC Fire-places dealer.
Only use MHSC components or the warranty will be voided and a fire hazard may be created.
MHSC warranty will be voided by and MHSC disclaims any responsibility for the following actions:

  • Installation by any other than a qualified installer, preferably NFI or WETT (Canada) certified.
  • Installation of any damaged fireplace or chim-ney component;
  • Modification of fireplace, chimney assembly or any parts thereof; (except for chase flashings as detailed in Chimney Top installation instructions).
  • Installation other than as instructed by MHSC; or
  • Installation and/or use of any part not manufactured or approved by MHSC in combination or assembly with an MHSC Fire-places fireplace system, notwithstanding any independent testing laboratory or other third-party approval of such parts or ac-cessory.

Any such action may cause a fire hazard. Consult local building codes to ensure that you comply with installing the fireplace. Fireplaces must be vented to the out-of-doors.
Do not obstruct or modify air inlets/outlets in any manner.

  • Do not install combustible materials on any of the black fireplace surrounds.
  • Burn only solid wood fuel or gas logs.
  • Do not install a solid fuel burning insert or other products not specified for use with this fireplace.
  • Proposition 65 Warning: Fuels used in gas, wood-burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
  • California Health & Safety Code Sec. 25249.6
  • WARNING: Check with your electronics manufac-turer before installing a television or other electronic device above this fireplace.

Drafts

  • The fireplace should not be located in areas that create drafts (ie: frequently opened doors and central heating air inlets/outlets) that hamper the normal flow of air into the fire.

Gas Logs

  • If you plan to install a gas log, the gas line should be installed before framing the fireplace. The gas line must be installed by a certified gas line installer.

SR36A / SR42A SC36A / SC42A Listed

  • UL127 / ULC-S610
  • Standard for factory-built fireplaces

SR36A Series Woodburning Fireplace

SC36A Series Woodburning Fireplace — Circulating Model

SR42A Series Woodburning Fireplace

SC42A Series Woodburning Fireplace — Circulating Model

Chase Installation

Chimney Requirements – Offset Installations

Notes: G + H cannot exceed 20 feet.
Air Space Clearances: SK8 (2-wall) = 1¹⁄₂” and “S” Series (3-wall) = 2″

Illustration Key
The following safety rules apply to offset installations (letters correspond with the illustration above):

  • A. Height of the chimney is measured from the hearth to the chimney exit.
    SR/SC36A SR/SC42A

    • Maximum: 90’0″ 90’0″
    • Minimum:
    • Without Elbows 12′ 6″ 12′ 6″
    • With 2 Elbows* 14′ 6″ 14′ 6″
    • With 4 Elbows* 21′ 0″ 21′ 0″
  • B. Do not use more than 4 elbows per chimney.
    Attach the straps of the return (top) elbow to a structural framing member. The offset (first) elbow of any pair does not have straps. IWF269

  • C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.

  • D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)

  • E. A chimney support (Model SKCS8) is required every 6 feet of an angled run of the chimney. Chimney supports are required for every 30 feet and 60 feet (SK8 pipe) or 20 feet and 40 feet (3-wall pipe) of vertical chimney height above the hearth.

Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling.
Note: This offset distance may not be your full offset distance. See Examples 2 and 3.

30° elbow Offsets

1′| 1 ¹⁄₂ | 3′| 4′| Chimney Support| Offset| Rise
0| 0| 0| 0| 0| 3″| 11″
1| 0| 0| 0| 0| 8¹⁄₄”| 20″
0| 1| 0| 0| 0| 11¹⁄₄”| 25¹⁄₄”
2| 0| 0| 0| 0| 13¹⁄₂”| 29¹⁄₄”
1| 1| 0| 0| 0| 16¹⁄₂”| 34¹⁄₄”
0| 0| 1| 0| 0| 20¹⁄₄”| 40³⁄₄”
2| 1| 0| 0| 0| 21³⁄₄”| 43¹⁄₂”
0| 0| 0| 1| 0| 26¹⁄₄”| 51¹⁄₄”
0| 1| 1| 0| 0| 28¹⁄₂”| 55¹⁄₄”
1| 0| 0| 1| 0| 31¹⁄₂”| 60¹⁄₄”
0| 1| 0| 1| 0| 34¹⁄₂”| 65¹⁄₂”
0| 0| 2| 0| 0| 37¹⁄₂”| 70³⁄₄”
1| 1| 0| 1| 1| 41¹⁄₂”| 77³⁄₄”
0| 0| 1| 1| 1| 45″| 83³⁄₄”
0| 1| 2| 0| 1| 47¹⁄₄”| 87¹⁄₂”
0| 0| 0| 2| 1| 51″| 94″
0| 1| 1| 1| 1| 53¹⁄₄”| 98″
0| 0| 3| 0| 1| 56¹⁄₄”| 103¹⁄₄”
0| 1| 0| 2| 1| 59¹⁄₄”| 108¹⁄₂”
0| 0| 2| 1| 1| 62¹⁄₄”| 113¹⁄₂”
0| 1| 3| 0| 1| 64¹⁄₂”| 117¹⁄₂”
0| 0| 1| 2| 1| 68¹⁄₄”| 124″
0| 1| 2| 1| 1| 70¹⁄₂”| 128″
0| 0| 0| 3| 1| 74¹⁄₄”| 134¹⁄₂”
0| 1| 1| 2| 2| 78″| 140³⁄₄”
0| 0| 3| 1| 2| 81″| 146″
0| 1| 0| 3| 2| 84″| 151¹⁄₄”
0| 0| 2| 2| 2| 87″| 156¹⁄₂”
0| 1| 3| 1| 2| 89¹⁄₄”| 160¹⁄₄”
0| 0| 1| 3| 2| 93″| 166³⁄₄”
0| 1| 2| 2| 2| 95¹⁄₄”| 170³⁄₄”
0| 0| 0| 4| 2| 99¹⁄₄”| 177³⁄₄”
0| 1| 1| 3| 2| 101¹⁄₄”| 181³⁄₄”
0| 0| 3| 2| 2| 104¹⁄₄”| 186¹⁄₄”
0| 1| 0| 4| 2| 107¹⁄₄”| 191¹⁄₂”
0| 0| 2| 3| 2| 110¹⁄₄”| 196³⁄₄”
0| 1| 3| 2| 3| 114″| 203¹⁄₄”
0| 0| 1| 4| 3| 117³⁄₄”| 209³⁄₄”
0| 1| 2| 3| 3| 120″| 213¹⁄₂”
0| 0| 0| 5| 3| 123³⁄₄”| 220″

Planning Information

Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a fireplace will be set and how the chimney system will be run.

Mounting the Fireplace
A fireplace may only be mounted on the following surfaces:

  1. A flat combustible surface.
  2. A raised wooden platform.
  3. A concrete block or other solid object is placed beneath each of the four (4) corners of the fireplace.

The fireplace must be spaced 1/2″ (13 mm) from a combustible back wall and 1/2″ (13 mm) from a combustible side wall or support. (Page 14, Fig. 20)

Planning the Chimney Run

Determine how the chimney will be run, the length of run and the chimney components required to complete the job. (Fig. 6) Never install a chimney below minimum heights.
In planning a chimney system, it is important to know:

  1. The height of a chimney is measured from the hearth to the exit point on the termination.
  2. A chimney cannot be offset more than 30° from a vertical plane.
  3. A chimney may run straight up or it may be necessary to offset it to avoid obstructions.
  4. The maximum length of an angled run (total chimney system) is 20′ (6m).
  5. No more than 2 offsets (4 total 30° elbows in the U.S./or 2 total 45° elbows in Canada) per fireplace may be used.
  6. A guy wire stabilizer is required for chimneys extending more than 6′ (1.8m) above a roof line.

The Ten-Foot Rule
Major U.S. building codes specify a minimum chimney height above the rooftop. The “Ten Foot Rule” is a fire safety rule and not a draft rule. To ensure a proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high-pitch roof. (Fig. 8)
The key points of the “Ten Foot Rule” are:

  1. If the horizontal distance from the chimney to the peak of the roof is 10′ (3m) or less, the top of the chimney must be at least 2′ (610mm) above the peak of the roof, but never less than 3′ (914mm) in height above the highest point where it passes through the roof.
  2. If a horizontal distance from the chimney to the peak of the roof is more than 10′ (3m), a chimney height reference point is established on the surface of the roof a distance of 10′ (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2′ (610mm) above the reference point, but never less than 3′ (614mm) in height above the highest point where it passes through the roof.

Chimney Supports

The chimney system is supported by the fireplace for vertical chimney heights less than 30′ (9m) above the hearth. Chimney supports are required if the vertical height exceeds 30′ (9m) with SK8 chimneys or 20′ (6m) with 3-wall chimneys. Locate chimney supports at ceiling holes or other structural framing at 30′ (9m) (SK8) or 20′ (6m) (3-wall) heights. Spacing between chimney supports must not exceed 30′ (9m) (SK8) or 20′ (6m) (3-wall). Use Chimney Support Model SKCS8. (Note: The SKCS8 can not be mounted directly to the fireplace.) Support provided by elbow straps fulfills the support requirement only if they are spaced as previously described. (A chimney support is 2¹⁄₂” (64mm) long when installed.) Angled chimney runs require support every 6′ (1.8m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 9)

Chase Installation
A chase is a vertical box-like structure that encloses the fireplace and/or chimney. Chases are typically built on the outside of the house with a fireplace opening cut into the outer wall of a room. (Page 5, Fig. 5) If you need help in determining the fireplace location or how the chimney system should be run, contact your MHSC Fireplaces dealer for assistance.

Installation

Insulating Fireplace Enclosure for Cold Climates

  • If you live in a cold climate, it is not required but highly recommended that you insulate a fireplace enclosure to eliminate cold air penetration as much as possible.
  • Insulate the base of the fireplace with noncombustible insulation rated for a minimum of 300°F. Insulating is very important for outside wall installations over a concrete slab. If a fireplace is installed on a platform, insulation should be placed on top of the platform before the fireplace is set. (Fig. 10)
  • When a fireplace is installed in a chase or on an outside wall, the enclosure should be treated like any outside wall in a home. Insulation should be installed on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a firestop at the first ceiling level above the fireplace and enclose the chase with sheeting material. Insulation may then be installed above the sheeting material to ensure the space around the fireplace is protected. (Fig. 5)
  • When installing the chimney, DO NOT caulk between the outer pipe and the firestop. Some air must be allowed to flow through this very thin gap.
  • CAUTION: WHEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE, BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED. (Page 14, Fig. 20)

Framing
Framing can be constructed before or after the fireplace is set in place, however, most installers build the frame before setting the fireplace.
Frame fireplace with 2 x 4 lumber or heavier materials.
Refer to framing dimensions in Figures 1, 2, 3 or 4 for basic fireplace specifications.
Note: Framing should be positioned to accommodate wall covering and fireplace-facing material.

Installing Electrical Wire (for Circulator Models)

  • If a circulating fireplace is to be installed, run the 120 VAC, 60 Hz wiring to the left side of the installation. Wiring must be completed before the fireplace is secured and finish material applied.
  • Remove the cover plate and electrical knockout on the lower left side of the fireplace and set aside. Follow the instructions on Page 10 for proper wiring and installation of the EB1.
  • If the fan kit is not being installed with the fireplace, it is highly recommended that 120 VAC supply be made available since someone may elect to install a blower at a later date.

Option For Circulating Models Only — EB 1 (Receptacle) Hook-Up

  • The wiring should be installed by a certified electrician.
  • Turn off the circuit breaker before wiring models.

Once the fireplace is secured, complete wiring the fan kit. Remove the knockout in the center of the back of the EB1 and install the listed cable clamps. Feed electrical wire through the listed cable clamp leaving approximately six (6) inches of wire exposed through the EB1. Secure the listed cable clamp to the wire.
Attach white wire from power source to one (1) wire of receptacle and secure with nut. Attach black wire from the power source to the other wire of the receptacle and secure it with nut. Be sure the nuts are secured tightly.
Secure the EB1 assembly to the inside of the electrical box coverplate using two screws. Attach the cover to the face of the EB1 while being careful to position excess wire completely within the EB1, then attach the cover plate to the fireplace.

Install Fan Kit Assembly
Refer to optional Model FK12 fan kit assembly installation instructions for field installation.

Chimney Setup
Since you have already preplanned the chimney run, you should know exactly how the installation is to be accomplished — how much pipe is required, the number of elbows, if any, and type of termination to be used. CAUTION: REPORT TO YOUR DEALERS ANY PARTS DAMAGED IN SHIPMENT, SPECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS.
NOTE: Fireplaces may use MHSC model SK8 or Model S (three-wall) chimney systems. The SR/SC Series “A” Fireplace will accept the SK8 chimney system as is; but a TWABR adapter collar is required when using the Model S (triple wall) chimney system. The installation procedure described in this manual applies only to the SK8 system. Either chimney system may be used, but may not be mixed.

Straight-Up Chimney Installation
To mark the centerline of the flue, put the fireplace in final position and measure out from the wall: 9¹⁄₄” (235mm). Mark a spot on the ceiling directly above the fireplace. Draw a line parallel to the back wall through this mark. (Fig. 11) Using a plumb bob positioned directly over the center point of the fireplace flue collar, mark the ceiling to establish the chimney center point. (Fig. 11)

Offset Installation
To clear an obstruction, it may be necessary to offset the chimney from vertical. This is accomplished by using MHSC elbows. Use the 30° Offset Elbow table on Page 6 to determine the proper offset and parts required. Each offset requires two (2) elbows. The second elbow

is equipped with support straps. It is very important to install the second elbow in each offset as close to the ceiling or support as possible so that the elbow straps can be secured to framing members to help support the weight of the chimney. Determine the offset distance of your chimney arrangement from the centerline of a fireplace to the centerline of a chimney where it is to pass through the ceiling. Locate the center point of the chimney on the ceiling as though a straight-up chimney arrangement is to be used. Measure your offset dimension from a straight-up chimney center point on the ceiling.

Ceiling Chimney Hole/Possible Obstructions

The size of the hole in the ceiling will vary with the angle at which the chimney passes through the ceiling.
Drive a nail up through ceiling at the marked chimney center point. Go to floor above and see where the hole will be cut. Check to see where existing ceiling joists and other possible obstructions are located…i.e. wiring, plumbing etc… If necessary, reposition the chimney and/or fireplace to avoid obstructions.

Cutting the Hole
Cover the fireplace collar opening and cut a proper-sized chimney hole in the chimney. The SK8 pipe allows you to run pipe through a typical 16” on-center joist without cutting joists.

Framing the Ceiling Hole
Frame the ceiling chimney hole as shown in Figure 12. It is good practice to use framing lumber that is the same size as the ceiling joists; this is a requirement at attic level.

The following table gives firestop spacer model numbers:

Size of Chimney Angle of Chimney at Ceiling
Vertical 30°

8″ Flue

“SK” Series

| SKFS2A

14¹⁄₂” x 14¹⁄₂” (368mm x 368mm)

| SKFS6A

14¹⁄₂” x 25¹⁄₂” (368mm x 648mm)

8″ Flue

“S” Series 3-Wall

| FS2A

17¹⁄₂” x 17¹⁄₂” (445mm x 445mm)

| FS6A

17⁷⁄₈” x 29⁵⁄₈” (454mm x 753mm)

Fig. 13 Ceiling chimney hole sizes necessary for installing firestop spacer

The inside dimension of the frame must be the same as the hole size selected from Figure 13 in order to provide required the 1¹⁄₂” (38mm) of air space between the outside diameter of the chimney and the edges of the framed ceiling hole.

Positioning, Safety Strips, Securing the Fireplace

  • Slide the fireplace into position.
  • Lift the fireplace front slightly and slide the metal safety strips under the front bottom edge about 1¹⁄₂” (38mm), allowing the remainder to extend in front of the firebox. Overlap strips at least 1/2″ (13mm) to provide a positive joint. (Flat safety strips are packed with a fireplace.) (Fig. 14)

Safety strips are used to ensure that any combustible materials in front of the fireplace are protected even though a noncombustible hearth extension is required.
If the fireplace is to be elevated above the floor, a “Z” shaped metal safety strip must be fabricated and used to protect combustible surfaces in front of the fireplace. This “Z” shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1¹⁄₂” (38mm) wide and equal in length to the metal strips provided with the fireplace.

NOTE: Safety strips are not required over noncombustible floors where all supports at the base of the fireplace are noncombustible.
Four (4) nailing flanges are incorporated on each corner of the surround. Bend the nailing flanges out, level the box, then secure it firmly in place by nailing the flanges to the framing members as shown in Figure 15.

Installing Outside Air Kit

An outside air kit is installed in all SR/SC Series Fireplaces. If desired, or if local codes mandate the use of an air kit, then an AK-MST is required to complete the installation (from air kit to the outdoors). If the outside air kit is to be used, the AK-MST MUST be installed BE-FORE the fireplace is enclosed. Refer to the AK-MST instructions for field installation.
NOTE: For Canada installations, model CCE-SK Chimney Collar Enclosure must be used on this fireplace with Model SK8 double wall chimney systems.

Installing the Chimney System
Start by attaching the first chimney section to the collar on top of the fireplace.
Install the pipe as pictured in Figure 16. When you get a good lock, you will hear the pipe snap together. Once sections are snap-locked in place, it is extremely difficult to get them apart. Make sure the pipe is firmly snapped and locked together as each pipe section is mounted.
When installing elbows, only the outer pipe will snaplock. Middle pipes simply slide into position. Be sure to always attach straps on the upper elbow to a structural framing member. (Fig. 17)

Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.

Installing the Firestop Spacer in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly and is required for safety.
Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spacers provide a minimum required air space to chimney pipe for ceiling thickness up to 8″ (203 mm). When the combined thickness of ceiling material, ceiling joists and flooring material exceeds 8″ (203 mm), adjustments must be made in framing to assure that minimum air spaces to the chimney are maintained.

Proper Firestop Spacer Installation

  • Figure 18 shows different installation procedures for both an area that is an attic and an area that is not an attic.
  • If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole. If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.
  • Firestop spacers are not available for nor are they required on vertical walls.
  • DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.

Canadian Requirements for Insulation Shield

In Canada, an attic insulation shield is required to prevent attic insulation from contacting the chimney section. NOTE: If the attic insulation shield is used, the firestop is not required in the attic installation. Framing dimensions for the chimney hole should measure 14¹⁄₂” x 14¹⁄₂” (368 x 368 mm). An attic shield MUST be installed on top of attic joists (above the floor level). (Fig. 19)

NOTE: In the U.S., it is a good idea, although not always required, to install an attic insulation shield where blown-in insulation is planned to be used in the attic. Install the attic insulation shield with the flanges on its base extending down into the framing hole. Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails. Attic shields are not required at the roof.

Continue Installing Pipe to Complete Run
Continue attaching pipe sections to complete the system to the next level always being careful that the pipe is firmly snapped and locked in place before proceeding to the next pipe section.

Chimney Supports
If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to adjacent structural framing, as shown on, Page 8, Fig. 9. Bend straps as necessary and make sure they are secure so they will support the weight of the chimney. A chimney support is 2¹⁄₂” (64 mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.
NOTE: Chimney supports are generally used in long runs in a chase installation.

Additional Ceilings
If you encounter additional ceilings, repeat the same steps required for the first ceiling installation. Refer to the firestop illustration on Page 12, Figure 18.

Penetrating the Roof
Run pipe to the roofline. Since the chimney system must be vented to the out- of-doors, you must use an approved termination.
If a chase is used, refer to the installation manual provided with the termination cap.
Locate Chimney Centerpoint On Roof
Use the same procedure detailed in locating the centerpoint of the flue system.
Drive a nail up through the roof at the center point. This will determine the center point on the outside of the roof.

Cut and Frame Roof Hole

  • Size of roof hole varies with the type of chimney termination installed. Refer to the installation instructions provided with the chimney termination to find the correct size of roof hole.
  • There must be a 1¹⁄₂ (38 mm) air space between the outermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materials such as: ceiling members, joists, flooring, combustible insulation and roof structures.) WARNING: DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER MATERIALS.
  • Mark an outline of the roof hole around the center of the point nail. NOTE: The hole dimensions given in the chimney top installation instructions are horizontal; therefore, the hole size must be marked on the roof accordingly.
  • Cover the opening of the installed chimney so debris cannot get into the system.
  • Cut and frame the hole. It is good practice to use framing lumber that is the same size as the rafters. Install the frame securely because the chimney top and flashing anchored to the frame must be able to withstand heavy winds.

Install Remainder of Chimney Sections

  • Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.
  • Check the chimney top installation instructions for details on how high above the rooftop the chimney sections (all pipes) should extend.

Installing Top Housing or Termination

  • Follow the installation instructions provided with the chimney termination you have selected.

Installing Chimney In a Chase

  • Refer to Page 5, Figure 5 for an illustration of a typical chase installation.
  • CAUTION: Treatment of firestop spacers and construction of chase may vary with type of building. These instructions are not a substitute for local building codes. You must check your local building codes to determine specific requirements for your city or state. NOTE: Other building materials may be required in addition to Firestop Spacers.

Finishing
CAUTION: All joints between the finished wall and the fireplace surround (top/sides) must be sealed with noncombustible material to prevent cold air leakage into the room. Only noncombustible material may be applied to the facing of the fireplace surround. (Black painted area) (Fig. 20)

Finish Wall
Finish the wall with the material of your choice. Do not install a combustible mantel shelf less than 12″ (305 mm) from the top of the fireplace opening for radiant models and 12″ (305 mm) from top of grille opening for circulating models. Do not install a mantel face plate less than 6″ (159 mm) from top of the fireplace opening for radiant models and 6″ (159 mm) from top of the grille opening for circulating models. (Fig. 22) If a combustible material is used below a flat mantel shelf, consult your local building codes for minimum clearance from top of the fireplace opening to the bottom of the mantel shelf.
All joints (top, bottom and sides) where wall or decorative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 21 and 22)
NOTE: No side wall protection is required for fireplaces installed at 45° to two (2) side walls (corner installation). Often a decorative surround or vertical portion of the mantel is desired. If this is constructed of any combustible material it must be within the safe zone indicated in Figure 23.

Side Wall Protection

Adjacent combustible side walls that are within the minimum dimensions shown in Figure 23 of the fireplace opening must be protected with MHSC Wall Shield Model SP40 or a specifically built wall shield described below. The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation

  1. Manville – CERAFORM 126, K=.27, 1/2 inches thick
  2. MHSC – EH2416, K = .458, 1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible floor in front of the fireplace. Refer to Figure 23 for minimum dimensions and mounting detail.
NOTE: Hearth Extension must not cover the air inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a durable noncombustible material with a minimum (total) Rt value of 1.09; refer to Figure 24 for examples. The overall height (above a combustible floor), depth and width must be as indicated, with the extension centered to the fireplace opening.
The top of the insulation must be covered with a noncombustible decorative covering or a piece of .018” minimum sheet metal, to protect hearth extension material. (Fig. 23)
Secure the hearth extension to the floor to prevent shifting, using trim molding or other similar means at three (3) outer edges. Seal crack between the fireplace hearth and hearth extension with a noncombustible material. (Figs. 23 and 25)

WARNING: HEARTH EXTENSION MUST BE IN-STALLED UNDER FIGURE 23 AND MUST NOT COVER THE BOTTOM FRONT OPENING OF THE CIRCULATING MODEL.

Alternate noncombustible materials may be used providing the (total) thermal resistance (Rt value) of the alternate material employed is greater than or equal to R = 1.09. Thermal resistance (R) or thermal conductivity (K), may be obtained from the manufacturer of the material.
Factors are related by the formula K = 1/R.

  • T = given thickness
  • R = thermal resistance for a given thickness (T)
  • K = thermal conductivity

Noncombustible material with a lower R-value may be used, provided the thickness of the material is sufficiently greater to maintain an equivalent (total) thermal resistance (Rt).

Example of Determining Hearth Extension Equivalents

To determine the thickness required for any new material:

  • NEW K of new material (per inch) thickness
    required = X of listed

  • thickness K of listed material (per inch) material

Example for Common Brick
T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required thickness).

Installing Line for Gas Logs

  • MHSC fireplaces are designed to accept a 1/2″ (13 mm) gas line for the installation of an approved gas appliance.
  • (MHSC manufactures a wide variety of gas logs for use in MHSC fireplaces.)
  • Be sure to have the appliance installed under building codes.
  • Gas connections may enter from either the left or right side of the fireplace.
  • Locate the appropriate gas line in the outer casing of the fireplace and remove insulation from the gas line tube. (Fig. 26)
  • From inside the fireplace, locate the knockout on the firebrick — be sure you are on the appropriate or “gas line” side of the fireplace. Using a flat-bladed screwdriver or small chisel and hammer, carefully tap around the knockout until it loosens and falls out.
  • Install 1/2″ (13 mm) certified gas pipe through the opening.
  • After the gas pipe installation is complete, use insulation that was removed from the gas line tube to repack space around the pipe. The material should be inserted from outside of the fireplace and packed tightly to totally seal between the pipe and tube.
  • NOTE: Gas pipe should not come in contact with any wood structures until it has reached a point at least one (1) inch away from the fireplace side.
  • NOTE: When installing an ANSI Z21.11.2 ventless appliance the finishing material used for the mantel must be rated at 250°F or greater.
  • BTU input of a gas appliance installed in a fireplace should be rated less than 100,000 BTU/Hr.
  • Gas pipe installation is intended for connection to a decorative gas appliance only when (1.) incorporating an automatic shutoff device and (2.) complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces (ANSI Z21.60) or
  • CSA draft requirements for Gas-Fired Log Lighters for Woodburning Fireplaces (Draft No. 4, August 1993).
  • Decorative gas appliances should be installed under the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 (latest edition).

CAUTION: WHEN USING DECORATIVE GAS APPLIANCES, THE FLUE DAMPER MUST BE SET IN A FULLY OPEN POSITION. IF YOU HAVE GLASS DOORS ON THE FIREPLACE, THEY MUST ALSO BE FULLY OPENED.
WARNING: DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIREPLACE WITH THE CHIMNEY REMOVED.
WARNING: WHEN INSTALLING AN UNVENTED GAS LOG SET, THE MHSC MODEL CABL OR CABR 4″ ADJUSTABLE HOOD MUST BE USED.

If installing an unvented gas log set, refer to the statement below:

Only unvented gas log sets that have been found to comply with the Standard for Unvented Room Heaters, ANSI Z21.11.2, are to be installed in this fireplace.

MHSC reserves the right to make changes in design, materials, specifications, and prices and discontinue colors and products at any time, without notice.

SR36A/42A, SC36A/42A SERIES

Ref. Description SR/SC36A SR/SC42A
1. Damper Weld Assembly RP199 RP199
2. Damper Bracket 3030176 3030176
3. Screen Rod (two per fireplace) 26D0138 61D0500
4. Screen Assembly (two per fireplace) 61D0001 61D0003S
5a. Firebrick – Hearth 20005621 20005421
5b. Firebrick – Rear 20005627 20005462
5c. Firebrick – Right Side 20005626 20005461
5d. Firebrick – Left Side 20005625 20005460
5e. Firebrick – Ashlip 20005619 20005418
6. Top Brick Retainers (three per fireplace) 3030172 3030172
7. Cable Clips (two per fireplace) 7512135 7512135
8. Outer Collar Assembly (SK8 Chimney) 3030143 3030143
9. Top Louvre Assembly (SC Only) 87D0007 87D0020
10. Bottom Louvre Assembly (SC Only) 87D0004 87D0017
11. Basket Grate 3041130 3041130
12. O.S.A. Assy. 20003076 20003076

The following accessories for this appliance are available from your local MHSC Fireplaces distributor. Should you need additional information beyond what your distributor can furnish, contact: MHSC, 149 Cleveland Drive, Paris, KY 40361, Attn: Technical Services.
CAUTION: This fireplace and chimney assembly is a highly engineered system, and, as such, must be operated only with MHSC-approved components. If you use an unapproved component to make any modifications, you may create a possible fire hazard and will void the MHSC warranty. In addition, such action may void the coverage provided by the owner’s insurance.

Accessory Description Model Number
Glass Door — Standard Bi-Fold door set Brushed Brass finish

(SR/SC36A)

42GDKBBSR (SR/SC42A)

Black finish| 36GDKBKSR (SR/SC36A)

42GDKBKSR (SR/SC42A)

Polished Brass finish| 36GDKDPSR (SR/SC36A)

42GDKDPSR (SR/SC42A)

Pewter finish| 36GDKSSR (SR/SC36A)

42GDKSSR (SR/SC42A)

Fan Kit| Provides forced airflow| FK12
Variable Speed Control| Provides speed adjustment of fans| SCVS
Outside Air Termination| Completes connection from air kit to out-of-doors| AK-MST
Chimney Adapter| Converts fireplace to 3-wall system| TWABR
Hearth Extension Insulation| Provides hearth extension floor protection| EH2416
Grate SR/SC36A/42A| Holds firewood in the firebox| RSBG36
Hearth Patch Compound| Patch cracks in the heart| HPC-1

Contact your MHSC Fireplaces distributor or dealer for finishing Marble and Mantels, available in a wide selection of styles.

Chimney Components

U.S.

Component Description Model Number
Round Top Termination Top used to terminate chimney at the roof. (Flashing
not included.) RLTSK8
Round Top Termination – Extended Top used to terminate chimney at chase.
(Flashing not included.) RLTSK8L
Flashing Metal finishing is required around Contemporary Termination to
prevent rain leakage. 8-6-12 with 8″ flue:

0-6/12 pitch

8-12-12 with 8″ flue: 6/12-12/12 pitch

Square Termination Housing| Top housing of simulated brick pattern available in red, tan or white. An appropriate adapter is required. Flashing included.| S20B (R, T, W)

Must also include: PLTSK8 or SLTSK8

Adapter Kit| Unites Square Termination with chimney pipe (required).| CF8CA
Housing Extensions| Extends Square Termination on steep pitched roofs.| 202036
Square Chase Termination| Housing used to terminate chimney through a chase top. The appropriate adapter is required. (Flashing not included.)| CT100
Adapter Kit| Unites Square Chase Termination with chimney pipe (required).| CTSK
Chase Top Housing| Low profile pyramid-style chimney cap used to terminate chimney through a chase. Includes adapter. (Flashing not included.)| PLTSK8
Chase Top Housing| Square chimney cap used to terminate chimney through a chase. Terra Cotta Masonry. Includes adapter. (Flashing not included.)| SLTSK8
SK8 Chimney Sections| Pipe used to build 8″ (SK8) flue systems.| SK81 (1′ Long)

SK818 (1¹⁄₂’ Long) SK83 (3′ Long)

SK84 (4′ Long)

SK8 Chimney Elbows| The elbow is used to create an offset in an 8″ chimney system. Only 30˚ elbows are available. Packaged 2 per carton (offset and return).| SK830-2
Firestop| Required at each floor level of chimney installation. (Plus attic on multi-story installation.)| SKFS2A —

(8″ straight flue) SKFS6A —

(8″ 30˚ inclined flue)

Chimney Support| Used to support chimney for each of: 30′ vertical height and 6′ of angled chimney run.| SKCS8

Canada

Component Description Model Number
Chimney Collar Enclosure Installs on the “over the chimney collar” of the
fireplace; provide outside air to assist in cooling the chimney system. CCE-

SK
Attic Insulation Shield| Used to prevent insulation from coming in contact with the chimney system.| AIS-SK
SK8 Chimney Sections| Used to build chimney systems exposed above the roof.| SK818CAN (1¹⁄₂’ Long) SK84CAN (4′ Long)
45˚ Chimney Elbows| Provides 45˚ offset and return. For Canadian installations only. For use with SK8 chimney only. (Maximum use of 2, or 1 pair.)| SK845/2

LIMITED WARRANTY

Factory-Build Fireplace and Components (Except Blowers)

What is Covered and For How Long
Five-Year Coverage: For five years from the date this fireplace and components are first purchased for use, MHSC will, at its option, repair or replace any defective part of this fireplace or components, or refund to you a sum not to exceed the factory retail price in effect at the time of purchase.
Ten-Year Coverage: From the sixth through the tenth year following the date this fireplace or accessory is first purchased for use, MHSC will make available to you, at our factory, a free replacement for any defective part in this fireplace or accessory.
Twenty-Five-Year Availability of Replacement Parts: From the eleventh through the twenty-fifth year following the date this fireplace or accessory is first purchased for use, MHSC will make available at our factory replacement parts for this fireplace or accessory, which you may purchase for the list price current at the time your purchase order is received.

What is Not Covered

  • This limited warranty does not cover:
  • Transportation or shipping cost.
  • The cost of a service call to diagnose trouble.
  • Painted surfaces.
  • Damage or defect caused by improper installation, accident, misuse, abuse or alteration.
  • Poor ventilation of smoke or gases caused by air-conditioning and heating systems, exhaust fans, or pressure differentials produced by wind.
  • Broken glass components.
  • Cracks in ceramic and castable parts that do not affect safe operation.
  • We do not warrant this fireplace to comply with your local building code. Building codes vary greatly throughout the country, and you should determine whether your local building code contains restrictions on the use of this fireplace before you purchase it.
  • Blowers or fans, are warranted separately.
  • Heat loss is due to the passage of heat or air through or around the fireplace.

Also, under our five-year coverage, we do not pay the cost of removal and replacement of any portion of the structure in which the fireplace is situated, made necessary by the repair, removal or re-installation of the fireplace. And under our twenty-five-year warranty of availability of replacement parts, we only promise to maintain a supply of replacement parts at our factory for you to purchase.

Limitations and Exclusions

  1. No one has the authority to add to or vary this limited warranty, or to create for MHSC any other obligations of liability in connection with this fireplace and accessory.
  2. MHSC shall not be liable for incidental, consequential, special or contingent damages you might suffer as a result of its breach of this written warranty or any implied warranty. Some states do not allow the exclusion of limitation of incidental or consequential damages, so the above limitations may not apply to you.
  3. This warranty applies only to a fireplace sold and used in the United States.