e2S BExCS110-05D Flameproof Combined Sounder Instruction Manual
- October 30, 2023
- e2S
Table of Contents
e2S BExCS110-05D Flameproof Combined Sounder
Product Information
The BExCS110-05D is a flameproof combined sounder and beacon that has a flash energy of 5 joules. It is designed to be used in Zone 1 and Zone 2 areas with gases in groups IIA and IIB and with Temperature Classifications of T1, T2, T3, and T4. The unit has an EC Type examination certificate and has been approved to the following standards:
- EN60079-0: 2006 IEC60079-0:2004 (Ed4) General Requirements
- EN60079-1: 2007 IEC60079-1:2007 (Ed6) Flameproof Enclosure ‘d’
- EN60079-14: 2008 IEC60079-14:2007 (Ed4) Electrical Installations in Hazardous Areas (other than mines)
- EN60079-10: 2003 IEC60079-10:2008 (Ed1) Classification of Hazardous Areas
The unit has a rating label that contains important information such as the unit type number (BExCS110-05D), input voltage (DC Units 12V or 24V or 48V AC Units 230V or 115V), gas groupings (Group IIA and Group IIB), equipment category (2G), temperature classification (T1 400o C, T2 300o C, T3 200o C, T4 135o C), and CE marking (Notified Body No. 0518).
Product Usage Instructions
-
Installation Requirements: The installation of the unit must be carried out by a competent electrical engineer who has the necessary training. The installation should be in accordance with any local codes that may apply.
-
Power Supply Selection: A suitable power supply must be used to run the unit. The power supply should have the necessary capacity to provide input current to all units connected to the system. The sounder and beacon sections can be wired to the same power supply or different power supplies.
-
Location and Mounting: The unit should be fixed to services that can carry its weight. The location of the unit should be made with due regard to the area over which both the sounder and beacon warning signal must be audible and visible.
-
Marking: The unit has a rating label that contains important information such as the unit type number, input voltage, gas groupings, equipment category, temperature classification, and CE marking.
-
Type Approval Standards: The unit has an EC
Type examination certificate and has been approved to the following- standards: EN60079-0:2006 IEC60079-0:2004 (Ed4) General
- Requirements, EN60079-1: 2007 IEC60079-1:2007 (Ed6) Flameproof
- Enclosure ‘d’, EN60079-14: 2008 IEC60079-14:2007 (Ed4) Electrical Installations in Hazardous Areas (other than mines), and.
- EN60079-10:2003 IEC60079-10: 2008 (Ed1) Classification of Hazardous Areas.
Introduction
The BExCS110-05D is a flameproof combined sounder / beacon which is certified to meet the requirements of the ATEX directive 94/9/EC and the IECEx scheme. The sounder section produces loud audio warning signals and the beacon section produces a synchronised visual warning signal. The unit can be used in hazardous areas where potentially flammable atmospheres may be present. Thirty-two different first stage audio alarm sounds can be selected by internal switches, and each one can be externally changed to a second or third stage alarm sound (see tone table on Page 5). The sounder produces output levels in the 110dB(A) range and the beacon has a flash energy of 5 joules. The unit can be used in Zone 1 and Zone 2 areas with gases in groups IIA and IIB and with Temperature Classifications of T1, T2, T3 and T4.
Marking
All units have a rating label, which carries the following important
information:-
Type Approval Standards
The units have an EC Type examination certificate issued by KEMA and have
been approved to the following standards:-
- EN60079-0: 2006 IEC60079-0:2004 (Ed4) General Requirements
- EN60079-1: 2007 IEC60079-1:2007 (Ed6) Flameproof Enclosure ‘d’
Installation Requirements
The unit must be installed in accordance with the latest issues of the relevant parts of the EN60079 specifications or the equivalent IEC specifications – Selection, Installation and maintenance of electrical apparatus for use in potentially explosive atmospheres (other than mining applications or explosive processing and manufacture):-
- EN60079-14: 2008 Electrical Installations in Hazardous
- IEC60079-14: 2007 (Ed4) Areas (other than mines)
- EN60079-10: 2003 Classification of Hazardous Areas
- IEC60079-10: 2008 (Ed1)
The installation of the unit must also be in accordance with any local codes that may apply and should only be carried out by a competent electrical engineer who has the necessary training.
Zones, Gas Group, Category and Temperature Classification
The BExCS110-05D unit has been certified Ex d IIB T4 for Ta –50ºC to +70ºC.
This means that the units can be installed in locations with the following
conditions:-
Area Classification:
Zone 1| Explosive gas air mixture likely to occur in
normal operation.
---|---
Zone 2| Explosive gas air mixture not likely to occur,
and if it does, it will only exist for a short time.
Gas Groupings:
Group IIA | Propane |
---|---|
Group IIB | Ethylene |
Equipment Category: 2G
Temperature Classification:
T1 | 400o C |
---|---|
T2 | 300o C |
T3 | 200o C |
T4 | 135o C |
Ambient Temperature Range: -50°C to +70°C
Location and Mounting
The location of the unit should be made with due regard to the area over which both the sounder and beacon warning signal must be audible and visible. The unit should only be fixed to services that can carry the weight of the unit. The unit should be securely bolted to a suitable surface using the 7mm diameter boltholes in the stainless steel U-shaped mounting bracket (see figure 1). The angle can then be adjusted in the direction such that its warning signals can be both heard and seen. This can be achieved by loosening the two large bracket screws in the side of the unit, which allow adjustment in steps of 18°. On completion of the installation the two large bracket adjustment screws on the side of the unit must be fully tightened to ensure that the unit cannot move in service.
Safety Warning (Electrostatic Hazard)
The acoustic horn section is made of ABS Plastic, therefore to avoid a
possible ELECTROSTACTIC CHARGE the unit must only be cleaned with a damp
cloth.
Access to the Flameproof Enclosure
In order to connect the electrical supply cables to the unit it is necessary
to remove the beacon section to gain access to the flameproof chamber. To
achieve this remove the four M6 hexagon socket head screws (see figure 2) and
withdraw the beacon section taking extreme care not to damage the flameproof
joints in the process. Note the four M6 screws are Class A4-80 stainless steel
and only screws of this category can be used on these units. It is therefore
important that these screws and their spring washers are kept in a safe place
during installation. On completion of the cable wiring installation the
flameproof joints should be inspected to ensure that they are clean and that
they have not been damaged during installation. Also check that the earth
bonding wire between the two casting sections is secure and the ‘O’ ring seal
is in place. When replacing the beacon section casting, ensure that it is
square with the sounder section chamber casting before inserting. Carefully
push the beacon section in place allowing time for the air to be expelled.
Only after the beacon section casting is fully in place should the four M6
Stainless Steel A4-80 cover bolts and their spring washer be inserted and
tightened down. If the beacon section jams while it is being inserted,
carefully remove it and try again. Never use the cover bolts to force the
beacon section casting into position. In case of repair, contact the
manufacturer for information on the dimensions of the flameproof joints.
Power Supply Selection
It is important that a suitable power supply is used to run the unit. The power supply selected must have the necessary capacity to provide the input current to all of the units connected to the system The sounder and beacon sections can both be wired to the same power supply or to different power supplies The following table shows the input current taken by the sounder section and beacon section of the various units:-
Unit Type| Input Voltage| Sounder Current| Max. I/P
Volts
---|---|---|---
BExCS110-05D| 24V DC| 265mA| 30V
BExCS110-05D| 12V DC| 195mA| 15V
BExCS110-05D| 48V DC| 130mA| 58V
BExCS110-05D| 230V AC| 56mA| 264V
BExCS110-05D| 115V AC| 110mA| 126V
Unit Type| Input| Beacon| Max.
The above table also shows the maximum voltages at which the units can be
operated.
Sounder Section
The input current to the sounder section will vary according to the voltage
input level and the frequency of the tone selected. The current levels shown
above are for the 440Hz Continuous tone @ nominal input voltage. The 24V and
48V DC units and the 230V AC, 115V AC units have a switching voltage regulator
circuit and therefore the input current level will decrease slightly as the
input voltage in increased and will increase slightly as the input voltage is
reduced. The 12V units do not have a voltage regulator and therefore their
input current will increase when the input voltage is increased.
Beacon Section
The input current to the beacon section will vary according to the voltage
input level. The current levels shown above are for nominal input voltage. The
12V, 24V, and 48V DC units have a converter circuit and therefore the input
current level will decrease slightly as the input voltage in increased and
will increase slightly as the input voltage is reduced.
Cable Selection
When selecting the cable size consideration must be given to the input current
that each unit draws (see table above), the number of units on the line, and
the length of the cable runs. The cable size selected must have the necessary
capacity to provide the input current to all of the units connected to the
line.
SAFETY WARNING: If the unit is used at high ambient temperatures, i.e.
over +40ºC, then the cable entry temperature may exceed +70ºC and therefore
suitable heat-resisting cables must be used, with a rated service temperature
of at least 110ºC.
Earthing
Both AC and DC units must be connected to good quality earth. The units are
provided with internal and external earthing terminals, which are both,
located on the beacon section of the unit (see Figures 2 and 3).
- When using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure.
- When using the external earth terminal a cable crimp lug must be used. The cable lug should be located between the two M5 stainless steel flat washers. The M5 stainless steel spring washer must be fixed between the outer flat washer and the M5 stainless steel nut to ensure that the cable lug is secured against loosening and twisting.
- The internal earth bonding wire ensures that a good quality earth is maintained between the sounder section casting and the beacon section casting.
Cable Glands
The BExCS110-05D unit has dual cable gland entries which have an M20 x1.5
entry thread as standard. Only cable glands approved for Ex ‘d’ applications
can be used, which must be suitable for the type of cable being used and also
meet the requirements of the Ex ‘d’ flameproof installation standard
EN60079-14: 2008 / IEC60079-14:2007.
SAFETY WARNING: If the unit is used at high ambient temperatures, i.e.
over +40ºC, then the cable entry temperature may exceed +70ºC and therefore
suitable heat resisting cable glands must be used, with a rated service
temperature of at least 110ºC. If a high IP (Ingress Protection) rating is
required then a suitable sealing washer must be fitted under the cable gland.
When only one cable entry is used the other one must be closed with an Ex ‘d’
flameproof blanking plug, which must suitably approved for the installation
requirements.
Cable Connections
The combined sounder beacon unit BExCS110-05D has separate printed circuit
boards in the sounder and beacon sections. The terminals for the sounder are
on the printed circuit board in the sounder section and the terminals for
thebeacon are on the printed circuit board in the beacon section (see figures
4&5 and 6&7). See section 8 of this manual for access to the enclosure and the
wiring diagrams at the end of this manual. The sounder and beacon sections can
be wired to the same input supply so that they operate simultaneously or they
canbe wired to separate input supplies so they can be operated independently
(see diagrams of pages 5 and 6 of this manual). If the sounder and beacon
sections are connected to the same input supply, the incoming cables should be
connected to the input terminals on the beacon board and the two connecting
wires, that are supplied with the unit, should be used to link the supply from
the interconnecting terminals on the beacon board down to the supply terminals
on the sounder board.
SOUNDER SECTION CONECTIONS
On the AC units a two-way terminal block is provided for the live and neutral
mains supply wires and a three way terminal block is provided for linking the
second and third stages, (see figure 7). On the DC units a four way terminal
block is provided for +ve and –ve supply input and second and third stage
modes of operation, (see figure 6). A single wire with a cross sectional area
of up to 4mm² can be connected to each terminal way or if an input and output
wire is required two 2.5mm² wires can be connected to each terminal way. When
connecting wires to the terminals great care should be taken to dress the wire
so that when the beacon section is inserted into the chamber the wires do not
exert excess pressure on the terminal blocks. This is particularly important
when using cables with large cross sectional areas such as 2.5mm² and above.
If the sounder is wired to the same power supply as the beacon always use the
flexible interconnecting wires provided.
BEACON SECTION CONNECTIONS
The cable connections are made into the terminal blocks on the electronic pcb
assembly located in the beacon section enclosure. A four-way terminal block is
provided on both AC and DC beacons. Therefore there are two live terminals and
two neutral terminals for the input and output wiring on AC units. On the DC
units there are two +ve terminals and two – ve terminals for the input and
output wiring. Wires having a cross sectional area of up to 4mm² can be
connected to each terminal way. When connecting wires to the terminals great
care should be taken to dress the wires so that wires do not exert excess
pressure on the terminal blocks. This is particularly important when using
cables with large cross sectional areas such as 2.5mm² and above.
BExCS110-05D AC Beacon Section
BExCS110-05D DC Beacon Section
Tone Selection and 2nd and 3rd Stage Alarms
The BExCS110-05D sounder section has 32 different tones that can be selected
for the first stage alarm. The sounders can then be switched to sound second
and third stage alarm tones. The tones are selected by operation of a DIP
switch on the sounder pcb for both DC and AC units. The tone table on page
five shows the switch positions for the 32 tones and which tones are available
for the second and third stages. To operate the sounder on stage one simply
connect the supply voltage to the normal supply terminals (+ve and –ve for DC
units, L and N for AC units). The operation of the second and third stages is
different for DC and AC units. DC Units Second and Third Stage Tone
Selection
The BExCS110-05D DC sounder section has the facility to use either +ve or
–ve switching to change the tone to the second and third stages. For –ve
switching connect the two headers on the pcb to the left-hand (marked –ve) and
centre pins. For +ve switching connect the headers to the right hand (marked
+ve) and the centre pins. To change to the second stage tone, connect either a
-ve or +ve supply line to terminal S2, depending on which switching mode is
being used while maintaining the dc supply to the +ve and –ve terminals.
Similarly for the third stage tone, connect a -ve or +ve supply line to
terminal S3. The supply to the S3 terminal will automatically override a
supply to the S2 terminal. AC Units Second and Third Stage Tone Selection To
select the second and third stage tones on the BExCS110-05D AC sounder
section, the Common (C) terminal on the three way terminal block on the pcb is
connected to the S2 terminal for the second stage tone and the S3 terminal for
the third stage tone.
BExCS110-05D DC Sounder Section
Volume Control
The BExCS110-05D sounder section, with the exception of 12V DC units, has a volume control to adjust the output level. To set the required output level, adjust the potentiometer on the pcb. For maximum output level the potentiometer should be set to the fully clockwise position.
End of Line Monitoring (DC Units)
On BExCS110-05D DC units, dc reverse line monitoring can be used if required.
All DC units have a blocking diode fitted in their supply input lines on both
the sounder section and the beacon section. An end-of-line monitoring diode or
an end-of-line monitoring resistor can be connected across the +ve and –ve
terminals. If an end of line resistor is used it must have a minimum
resistance value of 3k3 ohms and a minimum wattage of 0.5 watts or a minimum
resistance value of 500 ohms and a min. the wattage of 2 watts. If the sounder
and beacon sections are wired to separate power supplies then an end-of-line
monitoring component can be used in each section.
Synchronized Operation
All BExCS110-05D units that are connected to the same supply line will have a
synchronized sound output and a synchronized flash rate at one flash every
second. To ensure that the units will be synchronized check that the pin
header is not fitted, i.e. the two header pins are not shorted together (see
Figures 4 and 5).
Flip / Flop Operation
Two units can be mounted close to each other to form a flipflop operation,
where the beacons will flash alternately. To achieve this mode of operation,
fit a pin header to the flipflop header pins on the electronics board, i.e.
the two header pins are shorted together, (see figures 4 and 5) on one of the
two beacons. The first flash on the beacon that has the header fitted will be
delayed by ½ second. The two beacons will then flash alternately every ½
second.3
TONE SELECTION TABLE
Tone Selection
| DIP Switch Settings| ****
Stage Selection
---|---|---
Stage 1| Frequency Description| 1| 2| 3| 4|
5| Stage 2| Stage 3
1| Continuous 1000Hz
Toxic gas alarm
| 0| 0| 0| 0| 0| Tone 31| Tone 11
2| Alternating
intervals
| 800/1000Hz at| 0.25s| 1| 0| 0| 0| 0| Tone 17| Tone 5
3| Slow Whoop 500/1200Hz at 0.3Hz
with 0.5s gap repeated
| 0| 1| 0| 0| 0| Tone 2| Tone 5
4| Sweeping 800/1000 at 1Hz| 1| 1| 0| 0| 0| Tone 6| Tone 5
5| Continuous at 2400Hz| 0| 0| 1| 0| 0| Tone 3| Tone 27
6| Sweeping 2400/2900Hz at 7Hz| 1| 0| 1| 0| 0| Tone 7| Tone 5
7| Sweeping 2400/2900Hz at 1Hz| 0| 1| 1| 0| 0| Tone 10| Tone 5
8| Siren 500/1200/500Hz at 0.3Hz| 1| 1| 1| 0| 0| Tone 2| Tone 5
9| Sawtooth 1200/500Hz at 1Hz| 0| 0| 0| 1| 0| Tone 15| Tone 2
10| Alternating 2400/2900Hz at 2Hz| 1| 0| 0| 1| 0| Tone 7| Tone 5
11| Intermittent 1000Hz at 0.5Hz
General alarm
| 0| 1| 0| 1| 0| Tone 31| Tone 1
12| Alternating 800/1000Hz at 0.875Hz| 1| 1| 0| 1| 0| Tone 4| Tone 5
13| Intermittent 2400Hz at 1Hz| 0| 0| 1| 1| 0| Tone 15| Tone 5
14| Intermittent 800Hz 0.25s on 1s off| 1| 0| 1| 1| 0| Tone 4| Tone 5
15| Continuous at 800Hz| 0| 1| 1| 1| 0| Tone 2| Tone 5
16| Intermittent
150mS off
| 660Hz 150mS| on,| 1| 1| 1| 1| 0| Tone 18| Tone 5
17| Alternating 544Hz
(100mS)/440Hz(400mS)
| 0| 0| 0| 0| 1| Tone 2| Tone 27
18| Intermittent 660Hz 1.8s on, 1.8s off| 1| 0| 0| 0| 1| Tone 2| Tone 5
19| 1400Hz to 1600Hz sweep up over
1s – 1600Hz to 1400Hz sweep down over 0.5s
| 0| 1| 0| 0| 1| Tone 2| Tone 5
20| Continuous 660Hz| 1| 1| 0| 0| 1| Tone 2| Tone 5
21| Alternating 554/440Hz at 1Hz| 0| 0| 1| 0| 1| Tone 2| Tone 5
22| Intermittent 554Hz at 0.875Hz| 1| 0| 1| 0| 1| Tone 2| Tone 5
23| 800Hz pulsing at 2Hz| 0| 1| 1| 0| 1| Tone 6| Tone 5
24| Sweeping 800/1000Hz at 50Hz| 1| 1| 1| 0| 1| Tone 29| Tone 5
25| Sweeping 2400/2900Hz at 50Hz| 0| 0| 0| 1| 1| Tone 29| Tone 5
26| Simulated bell sound| 1| 0| 0| 1| 1| Tone 2| Tone 1
27| Continuous 554Hz| 0| 1| 0| 1| 1| Tone 26| Tone 5
28| Continuous 440Hz| 1| 1| 0| 1| 1| Tone 2| Tone 5
29| Sweeping 800/1000Hz at 7Hz| 0| 0| 1| 1| 1| Tone 7| Tone 5
30| 420Hz repeating 0.625s on, 0.625s off Australian alert signal| 1|
0| 1| 1| 1| Tone 32| Tone 5
31| 1200/500Hz at 1 Hz
Prepare to abandon platform
| 0| 1| 1| 1| 1| Tone 11| Tone 1
32| Sweeping 500/1200Hz 3.75s on,
0.25s off 15Hz
| 1| 1| 1| 1| 1| Tone 26| Tone 1
NOTE: Either the +ve or the -ve wire may be made common to both the
sounder and the beacon to reduce the number of cores in the cable.
NOTE: Either the L or the N wire may be made common to both the sounder
and the beacon to reduce the number of cores in the cable.
Manufacturer:
- European Safety Systems Ltd.
- Impress House, Mansell Road, Acton
- London, W3 7QH, UK
- Telephone: +44 (0)20 8743 8880 European Safety Systems Ltd
- Facsimile: +44 (0)20 8740 4200 Company Registration No. 2763350
- E-mail: sales@e2s.com Registered Office: Impress House www.e2s.com Mansell Road, London, UK, W3 7QH, UK
Equipment Type:
- BExCS110-05D, BExDCS110-05D,
- BExCL15-05D, BExDCL15-05D,
- BExCA110-05D, BExDCA110-05D,
- BExCTS110-05D, BExDCTS110-05D,
- BExCTV110-05D, BExDCTV110-05D
- BExCS110L1D, BExDCS110L1D
Directive 94/9/EC: Electrical and Mechanical equipment for use in explosive atmospheres (ATEX)
Notified Body for EC type Examination: KEMA Quality B.V.
- Notified Body No.: 0344 Utrechtseweg 310, 6812 AR Arnhem, The Netherlands
- EC-type Examination Certificate: KEMA 01ATEX2223X
Notified Body for Quality Assurance Notification: Sira Certification Service
- Notified Body No.: 0518 Rake Lane, Eccleston, Chester CH4 9JN, UK
- Quality Assurance Notification: SIRA 05 ATEX M342
Provisions fulfilled by the equipment:
- ll2 G Ex d llB T4
- ll 2 D Ex tD A21 IPGX T100 °C or T115 °C
Standards applied: EN 60079-0:2006
- EN 60079-1: 2007
- EN 61241-0: 2006
- EN61241-1: 2004
Directive 2004/108/EC: Electromagnetic Compatibility Directive (EMC)
- Standards applied: EN 61000-6-1:2007
- EN 61000-6-2: 2005
- EN 61000-6-3: 2007
- EN 61000-6-4: 2007
The standards EN 60079-0: 2006, EN 61241-0:2006 and EN 61241-1:2004 are no longer harmonized. The requirements of these standards have been checked against the harmonized standards EN 60079-0:2009 and EN 60079-31:2009 and there were no major technical changes affecting the latest technical knowledge for the products listed above. On behalf of European Safety Systems Ltd., I declare that, on the date the equipment accompanied by this declaration is placed on the market, the equipment conforms with all technical and regulatory requirements of the above listed directives.
- Martin Streetz: Quality Assurance Manager
- Date and Place of Issue: London, 04/07/2012
- Document No: DC-005-Issue_C
- Telephone: +44 (0)20 8743 8880
- Facsimile: +44 (0)20 8740 4200
- E-mail: sales@e2s.com.
- www.e2s.com.
- European Safety Systems Ltd
- Company Registration No. 2763350
- Registered Office: Impress House
- Mansell Road, London, UK, W3 7QH, UK
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
- sales@e-2-s.com.
- Tel: +44 (0)208 743 8880
- www.e-2-s.com.
- Fax: +44 (0)208 740 4200
- Document No. IS 2441-P Issue G 19-03-10
References
- E2S Warning Signals - Signalling devices for hazardous areas, fire and industrial environments, marine, onshore and offshore applications and wide area sirens and alarms.
- E2S Warning Signals - Signalling devices for hazardous areas, fire and industrial environments, marine, onshore and offshore applications and wide area sirens and alarms.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>