SENECA T201DCH600-MU Current Transducers Instruction Manual

July 3, 2024
SENECA

SENECA T201DCH600-MU Current Transducers

Product Information

Specifications

  • Dimensions: 95 x 75 x 35 mm
  • Weight: 150 g
  • Enclosure: PA6, black

Product Usage Instructions

PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol indicates conditions or actions that could damage the instrument or connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available using the QR-CODE shown on page 1.

The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.

Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

SENECA-T201DCH600-MU-Current-Transducers-fig- \(2\)

Module Layout and Signals
The device features a compact design with dimensions of 95 x 75 x 35 mm and weighs 150 g. It comes in a black PA6 enclosure. The front panel includes LED indicators for power and communication status. The LED PWR/COM in green indicates the device is powered correctly. The D-OUT LED in yellow signifies digital output activation.

  • Dimensions LxHxD: 95 x 75 x 35 mm;
  • Weight: ≈ 150 g;
  • Enclosure: PA6, black

SENECA-T201DCH600-MU-Current-Transducers-fig- \(3\)

SIGNALS VIA LED ON FRONT PANEL

LED STATUS LED meaning
PWR/COM Green ON The device is powered correctly
PWR/COM Green Flashing Communication via USB port
D-OUT Yellow ON Digital output activated

Assembly
The device can be mounted in any position, in compliance with the expected environmental conditions. Use the accessories supplied for fixing on a DIN rail. Attention: magnetic fields of considerable magnitude can alter the measurement: avoid proximity to permanent magnetic fields, solenoids or ferrous masses which induce strong alterations of the magnetic field; possibly, if the zero error is greater than the declared error, try a different arrangement or change orientation.

Attention
Pay attention to the direction of current flow during installation. To increase current measurement sensitivity, insert the cable multiple times into the central hole of the instrument to create coils. Sensitivity is proportional to the number of turns. Please, install the module as shown in the figure. Pay attention to the direction of the current flow. To increase the current measurement sensitivity, insert the cable several times into the central hole of the instrument, creating a series of coils. The current measurement sensitivity is proportional to the number of turns

Technical Specifications

Certifications and Insulation
The module supports insulation up to 3 kVac on bare conductors. It is designed for use in various environmental conditions.

Connections
The device features removable 6-way screw terminals with 5 mm pitch for cables up to 2.5 mm2. It also includes a micro USB port for configuration purposes only.

Power Supply and Communication Port
The module is powered via AC/DC TRMS or DC Bipolar input. It communicates via an RS485 serial port on terminals A+ and B-.

Input Capacity and Analog/Digital Output
The device supports AC/DC True RMS and DC Bipolar measurements with overload protection. It offers analog output on Vout and GND terminals with 13-bit resolution and EMI error less than 0.5%. Digital output is available on DO and GND terminals, with output type selection via software.

CERTIFICATIONS| SENECA-T201DCH600-MU-Current-Transducers-fig-
\(5\)
---|---
INSULATION| Using an insulated conductor, its sheath determines the insulation voltage. An insulation of 3 kVac is guaranteed on bare conductors

ENVIRONMENTAL

| T emperature : Humidity : Altitude:

Storage temperature: Degree of protection:

| -25 – + 70 °C

10%– 90% non-condensing.

Up to 2000 m above sea level with bare conductor

Up to 3500 m above sea level with an insulated conductor

-40 – + 85°C IP20.

CONDITIONS
ASSEMBLY| 35mm DIN rail IEC EN60715, wall mounted with dowels, suspended with ties
CONNECTIONS| Removable 6-way screw terminals, 5 mm pitch for cable up to 2.5 mm2 micro USB (CONFIGURATION ONLY)
POWER SUPPLY| Voltage: on Vcc and GND terminals, 11.5 – 28 Vdc; Absorption: Typical: 21 mA (LOAD EXCLUDED)
COMMUNICATION PORT| RS485 serial port on terminals A+ and B-

INPUT

| Type of measurement :    AC/DC TRMS or DC Bipolar

Crest factor :                     2

Pass-band: 1 kHz

Overload: __ 2000 A impulsive, 3 x IN continuing

CAPACITY| AC/DC True RMS (DIP7=OFF)| DC Bipolar (DIP7=ON)
T201DCH600-MU| 0 – 300A or 0 – 600A| -300 – +300A or -600 – +600A
| Type :                                        0 – 10 Vdc, minimum load RLOAD =2 kΩ.
| Protection :                                Reverse polarity protection and over voltage protection
ANALOGUE| Resolution: __ 13 bit (10000 points)
OUTPUT| EMI error: < 0.5%
on Vout and GND terminals| Temperature coefficient :           < 200 ppm/°C

Hysteresis on measurement :  0.2% of full scale

| Response speed: With «Fast» filter 800 ms. With «Slow» filter 2000 ms.
| The type of output can be selected via software
DIGITAL OUTPUT| Type : active, 0 – Vcc, maximum load 50 mA
on DO and GND terminals| The type of output can be selected via software
ACCURACY| below 2% of full scale| above 2% of full scale
T201DCH600-MU| 1% of full scale at 50/60 Hz, 23°C| 0.5% of full scale at 50/60 Hz, 23°C
OVERVOLTAGE CATEGORIES| Bare conductor: CAT. III 300 V

Insulated conductor: CAT. III 600 V

USB PORT
The module is designed to exchange data according to the modes defined by the MODBUS protocol. It has a micro USB connector on the front panel and can be configured using applications and/or software programs. The USB serial port uses the following communication parameters: 38400,8,N,1 The USB communication port responds exactly like the serial ports, with the exception of the communication parameters. For more information, visit the site shown on page 1

SENECA-T201DCH600-MU-Current-Transducers-fig- \(6\)

Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.

SETTING THE DIP-SWITCHES
The position of the DIP switches defines the Modbus communication parameters of the module: Address and Baud Rate.

The following table shows the values of the Baud Rate and the Address according to the setting of the DIP switches :

SENECA-T201DCH600-MU-Current-Transducers-fig- \(7\)

Note: When DIP switches 3 to 8 are OFF, the communication settings are taken from programming (EEPROM).

ELECTRICAL CONNECTIONSSENECA-T201DCH600-MU-Current-Transducers-fig-
\(7\)

Frequently Asked Questions

Q: Can the module be mounted in any orientation?
A: Yes, the device can be mounted in any position as long as environmental conditions are met. Follow the provided installation instructions for proper orientation.

Q: How can I increase current measurement sensitivity?
A: To increase sensitivity, insert the cable multiple times into the central hole of the instrument to create coils. Sensitivity is directly proportional to the number of turns.

Q: What is the insulation voltage supported by the module?
A: The module guarantees insulation up to 3 kVac on bare conductors.