Lochinvar SIT600-3000 Squire Stainless Water Heaters Instruction Manual
- June 28, 2024
- Lochinvar
Table of Contents
Lochinvar SIT600-3000 Squire Stainless Water Heaters
Specifications
- Models: SIT600-3000, SDT600-3000
- Material: Stainless steel
- Volume Range: 575 – 3000 liters
- Coil Size: Various sizes available
Product Usage Instructions
Introduction
The Lochinvar Squire stainless steel vessels are designed for use as an
indirect vessel in conjunction with a solar thermal system or a circulating
condensing boiler. They are not suitable for direct connection to an air
source heat pump.n.
FAQ
Q: Can the water heater be directly connected to an air source] heat pump?
A: No, these water heaters are not suitable for direct connection to an air
source heat pump. Contact Lochinvar for alternative solutions.
Installation, commissioning, and maintenance instructions
Warning :
Read and fully understand this manual before attempting to install this Water
heater. It can cause personal injury and damage to the Water heater when you
do not read the manual and/or do not obey the instructions.
| Document Control
---|---
Article| Language| Version| Date| Modified by
Squire stainless Installation Instructions| English| V1| 20-May-24| S.Addis
INTRODUCTION
Lochinvar Squire stainless steel vessels are designed to be used as an
indirect vessel in conjunction with a solar thermal system or with a
circulating condensing Boiler.
These water heaters are not suitable for direct connection to an air source
heat pump, contact Lochinvar for alternative solutions.
There are two versions of the storage vessels.
The SIT range are stainless steel vessels suitable for systems with a maximum
working pressure of up to 6 bar featuring a single indirect coil and a single
immersion heater boss.
The SDT range of stainless steel vessels are suitable for systems with a
maximum working pressure of up to 6 bar featuring two coils. The lower coil is
suitable for a Solar Thermal System or other LZC technology, to be used in
conjunction with a boiler. There is also the option of utilising both coils
with a single boiler to achieve high recovery rates.
GENERAL DESCRIPTION OF SAFETY SYMBOLS USED
Lochinvar Squire stainless steel vessels are fitted with sensor pockets for monitoring the temperature via the solar control and/or BMS. Each vessel is also equipped with a 240v manual re-set overheat thermostat and a suitably sized unvented kit can be supplied as an ancillary if required.
- All installations must conform to the relevant Building Regulations. Health & Safety requirements must also be taken into account when installing any equipment. Failure to comply with the above may lead to prosecution.
- If the equipment is to be connected to an unvented (pressurised) system, care must be taken to ensure all extra safety requirements are satisfied should a high or low-pressure condition occur in the system.
ANCILLARY OPTIONS
- De-Stratification Kit
- Unvented kit
- 6kW 230v Immersion heater 15”
- 9kW 415v Immersion heater 16”
- 9kW 415v Immersion heater 21”
WH9
- Contact Lochinvar for details CSI107
- CSI111
- CSI112
SAFETY GUIDELINES
Carefully read all the instructions before commencing installation.
Keep these instructions near the water heater for quick reference.
This equipment must be installed by a competent person. All installations must
conform to the relevant Building Regulations. Health & Safety requirements
must also be considered when installing any equipment. Failure to comply with
the above may lead to prosecution.
Commissioning, maintenance, and repair must be done by a skilled
installer/engineer, according to all applicable standards and regulations.
Lochinvar Limited is not liable for any damage caused by inaccurately
following these mounting instructions. Only original parts may be used when
carrying out any repair or service work.
This appliance is not intended for use by persons (including children) with
reduced physical, sensory, or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
DIMENSIONAL DRAWINGS
SIT600-3000
Model | Volume | Coil size | Dimension |
---|---|---|---|
A | B | ||
SIT600 | 575 | 54 | 740 |
SIT900 | 840 | 81 | 1080 |
SIT1100 | 1125 | 108 | 1080 |
SIT1400 | 1380 | 108 | 1180 |
SIT1900 | 1875 | 162 | 1380 |
SIT2500 | 2500 | 162 | 1380 |
SIT3000 | 3000 | 162 | 1380 |
SDT600-3000
Model| Volume| Lower Coil size kW| Upper Coil size kW|
Dimension
---|---|---|---|---
A| B
SDT600| 575| 27| 27| 740| 1978
SDT900| 840| 27| 40| 1080| 1595
SDT1100| 1125| 54| 40| 1080| 2100
SDT1400| 1380| 54| 54| 1180| 2120
SDT1900| 1875| 81| 67| 1380| 2050
SDT2500| 2500| 81| 81| 1380| 2600
SDT3000| 3000| 81| 67| 1380| 3040
GENERAL REQUIREMENTS
The Lochinvar Squire stainless steel vessel has been designed to operate
trouble free for many years. These instructions should be followed closely to
obtain the maximum usage and efficiency of the equipment. PLEASE read the
instructions fully before installing or using the appliance.
RELATED DOCUMENTS
The installation should follow the relevant guidance offered in the following
documents. It is not practical to list all relevant information but emphasis
is placed on the following documents, as failure to comply with the guidance
given will almost certainly result in an unsatisfactory installation:
- BS 6700: 1997 Design, installation, testing and maintenance of services supplying water for domestic use within buildings and their curtilages
- BS 7074: 1989 Application, selection and installation of expansion vessels and ancillary equipment for Parts 1and 2 sealed systems
- BS 7671: 2008 Requirements for electrical installations, I.E.E. wiring regulations seventeenth edition
- CP 342: Code of practice for centralised hot water supply-buildings other than dwellings
Part 2 1974
WATER QUALITY
Water supply quality may adversely affect the efficiency performance and
longevity of Water Heaters and Hot Water systems. Hard water may cause the
formation of limescale which will reduce operating efficiency and may cause
early product failure. Please note the following: –
-
Water Hardness – should not exceed 205ppm CaCO3 and Total Dissolved Solids (TDS) of should not exceed 350ppm.
If these values are exceeded a water treatment specialist should be consulted. Water Softeners and Water Conditioners may be considered, but whichever method is selected, it should be suitable for installation with Squire stainless indirect Water Heaters. A maintenance regime will also be required for such systems. -
High hot water temperature and high demand for hot water is likely to cause quicker limescale formation.
The formation of limescale or other solids can cause a blockage within the heat exchanger, which in turn may cause premature failure. Such instances are not regarded as defects in manufacture and will not be covered under the product warranty
WATER CONNECTIONS
GENERAL
- Circulating pipe work should be insulated; cisterns, expansion vessels and pipe work situated in areas exposed to freezing conditions should also be insulated2.
- Drain valves must be located in accessible positions that will permit draining of the entire system.
- Ideally, individual valves should be fitted to each unit to enable isolation from the system.
UN-VENTED SYSTEM
It is the law that unvented hot water systems be installed by an approved
installer.
If the Lochinvar Squire stainless steel vessel is to be used in an unvented
arrangement the system should follow the guidance given in BS6700 and must
comply with The Building Regulations: Part G3 in England and Wales, P5 in
Northern Ireland and P3 in Scotland. A kit of components that have been
suitably sized for the unvented or boosted operation of the appliance is
available from Lochinvar Limited.
If you require a pipe work schematic for multiple appliance/storage vessel
combinations, please contact Lochinvar Limited.
Safety must be provided on indirectly heater systems were the energy input
must be restricted by control and/or other means. On unvented hot water
systems were the heat source is from the primary circuit of a boiler, a two
port motorised valve and high limit stat must be fitted which causes the valve
to close to cut off the energy source.
Lochinvar Ltd reserves the right to change specifications without prior notice. All necessary additional valves and fittings to be determined by those other than Lochinvar Ltd. Lochinvar Ltd may provide technical advice and guidance to assist with best practice, optimisation and installation of Lochinvar products; however, we will not be liable for any duties as Designers under Construction (Design and Management Regulations 2015). In all cases where information is provided, the customer must assess and manage risks associated with the technical information and advice provided.
TYPICAL SCHEMATIC SIT INDIRECT WATER HEATER WITH BOILER
TYPICAL SCHEMATIC SIT INDIRECT WATER HEATER USED AS A SOLAR PRE-HEAT
TYPICAL SCHEMATIC SDT INDIRECT WATER HEATER USED AS A SOLAR PRE-HEAT WITH BOILER
TYPICAL SCHEMATIC SDT INDIRECT WATER HEATER WITH BOILER UTILISING BOTH COILS FOR FASTER RECOVERY
TEMPERATURE AND PRESSURE RELIEF VALVE
A temperature and pressure relief valve is provided in the unvented water system kit. This valve has a lift pressure of 7 bar and a lift temperature of 90°C. The valve must be fitted to the relief valve tapping located on the front of the appliance.
The storage vessel relief valve connection should not be used for any other purpose.
RELIEF VALVE DISCHARGE PIPEWORK
It is important that any discharge water does not collect in the discharge
pipe-work and can run freely to the tundish. The tundish should be mounted in
a vertical and visible position located in the same space as the unvented hot
water storage system and be fitted as close as possible and within 600mm of
the safety device e.g. the temperature relief valve.
The discharge pipe from the tundish should terminate in a safe place where
there is no risk to persons in the vicinity of the discharge, be of metal or
other material that has been demonstrated to be capable of safely withstanding
temperatures of the water discharged and is clearly and permanently marked to
identify the product and performance standard, and Be at least one pipe size
larger than the nominal outlet size of the safety device unless its total
equivalent hydraulic resistance exceeds that of a straight pipe 9m long i.e.
discharge pipes between 9m and 18m equivalent resistance length should be at
least two sizes larger than the nominal outlet size of the safety device,
between 18 and 27m at least 3 sizes larger, and so on. Bends must be taken
into account in calculating the flow resistance.
An alternative approach for sizing discharge pipes would be to follow BS6700
Specification for design installation, testing and maintenance of services
supplying water for domestic use within buildings and their curtilages.
-
Have a vertical section of pipe at least 300mm long, below the tundish before any elbows or bends in the pipe work.
-
Be installed with a continuous fall of at least 1 in 200.
-
Have discharges visible at both the tundish and the final point of discharge but where this is not possible or is practically difficult there should be clear visibility at one or other of these locations.
Examples of acceptable discharge arrangements are:
I.Ideally below the fixed grating and above the water seal in a trapped gulley. -
downward discharges at a low level; i.e. up to 100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that where children play or otherwise come into contact with discharges, a wire cage or similar guard is positioned to prevent contact whilst maintaining visibility.
-
Discharges at a high level; e.g. into a metal hopper and metal down pipe with the end of the discharge pipe clearly visible (tundish visible or not) or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering systems that would collect such discharges (tundish visible).
-
Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to not more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings occupied by blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place.
RELIEF VALVE DISCHARGE PIPEWORK
EXPANSION VESSEL SIZING
The following information is based on an inlet pressure of 3.5 bar. If a
different inlet pressure is to be used, please consult BS6700.
- V V = S V * e
- 0.45
- Where:
- V V = Vessel Volume
- S V = System Volume
- e = Coefficient of Expansion (See Table Below)
Stored Temp.| °C| 30| 35|
40
| 45| 50| 55| 60
---|---|---|---|---|---|---|---|---
e| | 0.005| 0.006| 0.008| 0.01| 0.012| 0.015| 0.017
Stored Temp.| °C| 65| 70| 75| 80| 82|
85| 90
e| | 0.02| 0.023| 0.026| 0.03| 0.031| 0.033| 0.037
COEFFICIENT OF EXPANSION OF WATER AT
BAR INLET PRESSURE
SOLAR EXPANSION VESSEL SIZING
Any solar expansion vessels should be sized, installed and commissioned as per
solar instructions.
DE-STRATIFICATION
GENERAL
The De-stratification Pump Kit works by using a pump to circulate water from
the top of the vessel to the bottom of the vessel. This action ensures that
the water held in the unit is maintained at a consistent temperature
throughout. By achieving a uniformed stored water temperature of at least
60°C, the risk of any bacterial contamination is virtually eliminated.
Systems that have a building loop incorporated onto the vessel may not require
a de-stratification kit, provided the circulation around the building from the
top of the vessel returns back to the bottom. This should provide sufficient
mixing.
REQUIREMENTS
Lochinvar has developed this kit to meet the stringent recommendations of both
the HSE Approved Code of Practice L8 and Department of Health Memorandum HTM
04-01 relating to the control of legionella within solar thermal
installations.
COMMISSIONING AND TESTING
ELECTRICAL INSTALLATION
Any ancillary item that requires an electrical supply should be installed and
commissioned as per instructions.
WATER CONNECTION
For design see Section 5: Water connections.
The system should be thoroughly flushed out with cold water without any
circulating pumps in position. Ensure all the valves are open.
If a building return pump is to be fitted, it should be fitted before the
system is filled and airlocks cleared. Check the system for leaks and repair
as necessary. If the system is configured in an unvented arrangement, check
the expansion vessel cushion pressure.
PRIMARY HEAT SOURCE
The primary heat source operating in conjunction with the indirect water
heater should be installed and commissioned in accordance with the relevant
ICM Instructions provided.
MAINTENANCE
GENERAL
Regular servicing is recommended, preferably by a Lochinvar-appointed person,
to ensure trouble-free operation. Even if a maintenance schedule is determined
to be less than annually, it is important that all controls and safety
features are checked for correct operation on an annual basis.
DRAINING THE WATER SYSTEM
Maintenance and service procedures for the Squire may require draining the
water heater. The water heater must also be drained if it is to be shut down
and exposed to freezing temperatures.
- Turn off the water heater if applicable.
- Connect a hose to the system drain valve.
- Locate hose’s discharge in an area where hot water will not cause any damage or injury.
- Close the cold-water inlet valve to water heater system.
- Open a nearby hot water outlet to vent the system.
- Open the drain valve.
- If the vessel is being drained for an extended shutdown, it is suggested the drain valve be left open during this period.
RE-FILLING THE SYSTEM
- Close the drain valve.
- Open a hot water fixture to allow air to escape.
- Open the cold water supply to water heater and allow the vessel to fill.
- Check for water leakage.
OTHER CHECKS
RELIEF VALVE
At least once a year, the temperature and pressure relief valve and safety
valve should be checked to ensure that they are in operating condition. To
check each valve, lift the lever or turn the screw cap at the end of the valve
several times. The valve should operate freely and seat properly.
If water does not flow, remove and inspect for obstructions or corrosion.
Replace with a new valve of the recommended size as necessary.
USER INSTRUCTIONS
Your Squire Stainless unvented hot water cylinder has been designed to give
many years of trouble free service and is made from hygienic, high grade
stainless steel. Where applicable, it includes a 3kW electric immersion heater
which heats the water to 60°C once pre-heating of the solar system is
completed (SIT models for Solar use only).
The flow temperature of the hot water can be set to your requirements on the
immersion heater (ideally 60°C maximum). Higher temperatures can cause
tripping of the high limit thermostat and introduce more energy loss from the
cylinder.
When a hot tap is turned on there may be a short surge of water, this is quite
normal with unvented systems and does not mean there is a fault.
When you first fill a basin the water may sometimes appear milky. This is due
to very tiny air bubbles in the water which will clear very quickly.
Warning: if cold/warm water exits from the temperature and pressure relief
valve (TPV) or from the pressure relief valve (PRV) call your installer. If
very hot water exits from either valve switch off the heat source immediately
and isolate the electricity supply to the cylinder and separate heat source.
The solar system is configured to heat the water to its maximum economic
temperature which may vary with ambient temperature and weather conditions.
The immersion may be programmed to operate during fixed periods of the day or
night.
If the hot water runs cool it may be necessary to manually switch on the
immersion to heat the water – please see the relevant instructions for your
alternative energy device.
WARRANTY
See warranty terms and conditions document available at www.lochinvar.ltd.uk
APPENDIX 1 TECHNICAL DATA TABLES SIT600-3000
|
Unit
|
---|---|---
SIT600| SIT900| SIT1100| SIT1400| SIT1900|
SIT2500| SIT3000
Storage Capacity| l i tres| 575| 840| 1125| 1380| 1875| 2500| 3000
EFFICIENCY DATA-Part L2
Insulation Thickness| mm| 50| 90| 90| 90| 90| 90| 90
Insulation Type| |
Standing Loss| kWh/ltr/day| 0.005| 0.004| 0.003| 0.003| 0.002| 0.002| 0.002
GENERAL DATA
Max draw off capacity (fi rst hour) at 50oC temperature ri se| l /hr| 1390|
2067| 2759| 2963| 4289| 4789| 5189
Heat-up Time at 50oC temperature ri se| min| 37| 36| 36| 45| 40| 54| 65
Dimensions (height with insulation )| mm| 1978| 1600| 2100| 2120| 2050| 2600|
3040
Dimensions (diameter with insulation)| mm| 740| 990| 990| 1090| 1290| 1290|
1290
Weight (empty)| kg| 114| 162| 195| 241| 291| 370| 427
Weight (full)| kg| 689| 1002| 1320| 1621| 2166| 2870| 3427
Minimum Working Pressure| bar| 0.5| 0.5| 0.5| 0.5| 0.5| 0.5| 0.5
Maximum Working Pressure| bar| 6| 6| 6| 6| 6| 6| 6
Hot Outl et Connection (inches)| BSP| 2| 2| 2| 2| 2| 2| 2
Cold Feed Connection (inches)| BSP| 2| 2| 2| 2| 2| 2| 2
Coil Connection (inches)| BSP| 1| 1| 1| 1| 1½| 1½| 1½
COIL DATA
Coil Rating (80/60oC)| kW| 54| 81| 108| 108| 162| 162| 162
Coil Surface Area| m2| 2| 3| 4| 4| 6| 6| 6
Flow Rate (80/60oC)| l /sec| 0.45| 0.4| 0.35| 0.35| 1.45| 1.45| 1.45
Pressure Loss| kPa| 30| 30| 30| 30| 30| 30| 30
Maximum Coil Temperature| °C| 110| 110| 110| 110| 110| 110| 110
Maximum Coil Pressure| bar| 6| 6| 6| 6| 6| 6| 6
APPENDIX 2 TECHNCIAL DATA TABLES SDT600-3000
|
Unit
|
---|---|---
SDT600| SDT900| SDT1100| SDT1400| SDT1900|
SDT2500| SDT3000
Storage Capacity| l i tres| 575| 840| 1125| 1380| 1875| 2500| 3000
EFFICIENCY DATA-Part L2
Insulation Thickness| mm| 50| 90| 90| 90| 90| 90| 90
Insulation Type| |
Standing Loss| kWh/ltr/day| 2.88| 3.29| 3.6| 3.84| 4.13| 4.56| 4.87
GENERAL DATA
Max draw off capacity (fi rst hour) at 50oC temperature ri se Top coil| l /hr|
924| 1360| 1588| 2033| 2652| 3393| 3552
Heat-up Time at 50oC temperature ri se Top coil| min| 50| 37| 59| 54| 49| 65|
104
Dimensions (height with insulation )| mm| 740| 1080| 1080| 1180| 1380| 1380|
1380
Dimensions (diameter with insulation)| mm| 1978| 1595| 2100| 2120| 2050| 2600|
3040
Weight (empty)| kg| 114| 162| 195| 241| 291| 370| 427
Weight (full)| kg| 689| 1002| 1320| 1621| 2166| 2870| 3427
Minimum Working Pressure| bar| 0.5| 0.5| 0.5| 0.5| 0.5| 0.5| 0.5
Maximum Working Pressure| bar| 6| 6| 6| 6| 6| 6| 6
Hot Outl et Connection (inches)| BSP| 2| 2| 2| 2| 2| 2| 2
Cold Feed Connection (inches)| BSP| 2| 2| 2| 2| 2| 2| 2
Coil Connection (inches)| BSP| 1| 1| 1| 1| 1| 1| 1
COIL DATA
Coil Output (80/60 °C) Bottom/Top| kW| 27/27| 27/40| 54/40| 54/54| 81/67|
81/81| 81/67
Coil Surface Area Bottom/Top| m2| 1.0/1.0| 1.0/1.5| 2/1.5| 2.0/2.0| 3.0/2.5|
3.0/3.0| 3.0/2.5
Flow Rate (80/60 °C) Bottom/Top| l /sec| 0.33/0.33| 0.33/0.495| 0.45/0.495|
0.45/0.45| 0.4/0.43| 0.4/0.4| 0.4/0.43
Pressure Loss Bottom/Top| kPa| 12.2/12.2| 12.2/14.3| 30/14.3| 30/30| 30/30|
30/30| 30/30
Maximum Coil Temperature| °C| 110| 110| 110| 110| 110| 110| 110
Maximum Coil Pressure| bar| 6| 6| 6| 6| 6| 6| 6
APPENDIX 3 ErP SPECIFICATION DATA SHEETS
Information| Unit|
---|---|---
Trade mark| –| Lochinvar Limited
Model Identifier| ****
–
| SIT600| SIT900| SIT1100| SIT1400| SIT1900
Energy efficiency class| –| N/A| N/A| N/A| N/A| N/A
Standing loss| W| 120| 137| 150| 160| 172
Storage volume| litres| 575| 840| 1125| 1380| 1875
Information| Unit|
Trade mark| –| Lochinvar Limited
Model Identifier| –| SDT600| SDT900| SDT1100|
SDT1400
| ** SDT1900
Energy efficiency class| –| N/A| N/A| N/A| N/A| N/A
Standing loss| W| 120| 137| 150| 160| 172
Storage volume**| litres| 575| 840| 1125| 1380| 1875
8 Lomoard wav. Ine MxL Centre, banbury. Uxon, Oxzo 415 el: +44 0 1295 209 981 Fax: 444 0 1295 20. 640 Email: into@lochinvar.ltd.uk www.lochinvar.c.uk
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>