Eltako DALI-2 Motion Brightness Sensor Office Installation Guide
- June 24, 2024
- Eltako
Table of Contents
DALI-2 Motion Brightness Sensor Office
“`html
Specifications:
- Type: DALI-2 motion/brightness sensor office
- Article Number: DL2-BH98B-pm 33000031
- Application Standard: office
- Protection Class: IP 20
Product Information:
The DALI-2 motion/brightness sensor office, DL2-BH98B-pm, is
designed for use in office environments. It is directly connected
to the DALI bus and powered by it, eliminating the need for an
additional power supply. The sensor features a light sensor with a
range of 0-2047 lux and a motion detector with a detection range of
X-Y cross-section at 3 meters.
Dimensions: 98×47 mm
Installation Depth: 30 mm
Colour: Polar White Mat (similar to RAL9010)
Installation Instructions:
-
Connect the DL2-BH98 to the DALI bus without worrying about
polarity. -
Use wires with cross-sections from 0.5 mm2 to 1.5 mm2 for
connection. -
Ensure the voltage drop on the DALI cable does not exceed 2V at
maximum length and bus load. -
Mount the sensor on the electrical installation box
securely.
Usage Instructions:
The factory setting is suitable for simple applications, but
device settings can be adjusted using the DALI Cockpit. The sensor
operates in motion-controlled mode without constant light control.
External on/off commands can activate/deactivate motion detection
until the next command.
Motion Sensor Settings:
- Effective Range: Broadcast
- Holding Time: 10 min
- Absence Value: None
- Absence Holding Time: 0 s
Light Control Settings:
- CLC: Inactive
- Front LED (motion indicator): Active
Instance Basic Settings:
- Dead Time: 0.00 sec
- Report Time: 1 sec
- Holding Time: Active device addressing
Frequently Asked Questions (FAQ):
Q: What is the maximum wire cross-section supported by the
terminals?
A: The terminals support wires with cross-sections from 0.5 mm2
to 1.5 mm2.
Q: Can the sensor be used in outdoor environments?
A: The sensor is designed for indoor use and has a protection
class of IP20.
Q: How can I adjust the settings of the sensor?
A: The settings can be changed via the DALI Cockpit or manually
using the DALI command ENABLE INSTANCE.
“`
GB
33 000 031 – 1
DALI-2 motion/brightness sensor office DL2-BH98B-pm
Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!
Transport and storage temperature: -20°C … +70°C Operating temperature: -20°C … +60°C rel. humidity, non-condensing: 15% … 90%
DALI-2 motion/brightness sensor office. Application controllers and instances. Protection class: IP 20.
Installation and assembly The DL2-BH98 is connected directly to the DALI bus
and powered by it. A DALI bus power
supply is required; no additional power supply is required. The connection to
the DALI terminals can be made without paying attention to the polarity. The
terminals are suitable for wires with cross sections from 0.5 mm2 to 1.5 mm2.
Mounting box: Attach the mounting ring directly to the electrical installation
box, the
housing can then simply be plugged onto the mounting ring, the recessed sensor
head fits into the electrical installation box. Installation on hollow walls
and false ceilings with spring clip in the housing GZD-BH98-pm Item number:
33000032 Surface mounting in the GAP-BH98-pm housing Article number: 33000033
Alignment to the desired detection area through a 40° vertical tilt 360°
rotation axially Installation may only be carried out when the system is in a
de-energised state and by qualified specialist personnel National regulations
for the construction of electrical systems must be observed. The DALI cables
can be designed with standard low-voltage installation material. No special
cables are required.
!
Attention: Cable cross section, the voltage drop on the DALI cable must not exceed 2 V at
maximum length (300 m) and maximum bus load (250 mA).
4 operating modes: – Movement triggered – Movement triggered with constant light control – Constant light control – Light control (4 thresholds) Operating modes can be changed via scenes and external DALI commands. Corridor function second light value for dimming down before switching off. Optional use as an active DALI lighting control unit or as a sensor unit for integration into building management systems. Bidirectional integration via the FD2G71L-230V into the EnOcean building radio or FD2G14 into the 14 series. Multiple sensor modules can be installed within a DALI system. Automatic synchronisation of multiple sensors with the same effective range.
Dimensions: 98×47 mm Installation depth: 30 mm Colour: polar white mat (similar to RAL9010).
Specification, characteristics Type Article number Application standard
DL2-BH98B-pm 33000031 office
Electrical data Supply Terminal designation Max. current consumption Power consumption max. Control
from DALI bus (DALI voltage according to IEC62386) DA, DA 3.5 mA
<100 mW DALI
Technical data Motion detector principle Detection range (at >8°C temperature difference) Installation height Zones Horizontal Vertical Min. temperature difference Details
PIR
2.3 m/3 m 3 m
36/48 ±44°/±90° ±44°/±90°
4°C Fig. 1
Light sensor (62386-304) Function
range: 0-2047 lux (11bit), resolution: 1 lux Event:0-2047 lux(10bit),
resolution: 2 lux
programmable
Terminals Connection type Connection capacity solid Connection capacity fine- wire Connection capacity with wire end sleeves Stripping length of connecting wires
spring-loaded terminal 0.5 … 1.5 mm2 (AWG20 … AWG16) 0.5 … 1.5 mm2 (AWG20 …
AWG16)
0.25 … 1.5 mm2 8.5 … 9.5 mm
Standards EMV
Electrical safety
Markings
EN 61547 EN 55015 EN 61347-2-11 EN 61347-1 ENEC-11, CE
Motion detection (Art. No.: 33000031) Detection range: X-Y cross section at 3
m
Dimensions of mounting ring
Factory setting The factory setting is sufficient for simple applications. Device settings can be changed via the DALI Cockpit and adapted to the current application.
DALI-2 Setting
Application Controller Master Mode
Operating mode
Motion controlled without constant light control, an external on command deactivates motion detection until the next external off command
Effective range
Broadcast
Switch-on command
Recall Max
Holding time
10 min
Absence value
None
Absence holding time
0 s
Switch-off command
Off
Switch-on threshold
None
Switch-off threshold
None
Power Up Verhalten
No action
Light control (CLC)
inactive
Front LED (motion indicator)
active
Motion detector instance event messages
inactive
Light sensor instance event messages
inactive
Instance basic settings In order to use the motion sensor instance or light sensor instance in combination with a master, the following instance settings are required, these are set in the delivery state, only event messages need to be activated, this is done automatically by the DALI-2 master (it is also possible to activate event messages manually without the DALI Cockpit via the DALI command ENABLE INSTANCE):
Instance #0 Motion: Event messages Event schema Event filter
Dead time Report time Holding time
Instance #1 Light: Event messages Event schema Event filter Dead time Report
time Hysteresis Min Hysteresis
active device addressing
Occupied Unoccupied
0.00 sec not applicable
1 sec
active device addressing
lighting level 0.8 sec unused 5 Lux 5 %
Motion detection In order to detect motion, there is a need for a temperature
difference of at least 4°C between the moving object and the environment. Heat
sources such as printers, radiant heaters, etc. can have a negative in uence
on motion detection.
Relatively large areas can be covered with just one sensor head. With opening
angles of 92° and 102° and 92 detection zones, over 100 m2 of area can be
covered at an installation height of 5 m. The distance between the sensor and
the object to be detected should be less than 12 m, which corresponds to an
installation height of around 8 m. See Fig. 1.
Standard detection area
h [m]
a [m]
b [m]
A1 [m2]
2.0
4
4
12.5
2.2
4.4
4.4
15.2
2.5
5
5
19.6
3.0
6
6
28.2
Correspondence between mounting height and area
Slight motion detection area
l [m]
A2 [m2]
1.6
2.56
1.8
3.24
2
4
2.4
5.76
Timing motion detection The motion report is always processed according to the following time schedule:
Process when motion is detected
States: 1: Fade In Time Dim up to 1st light level 2: Hold Time / Hold Time
3: Fade Time dimming to 2nd light level 4: 2nd Hold Time (2nd Light Level) /
Hold Time 5: Fade Out Time dim to off P: Ongoing motion detection
(retrigger) 7: Off If motion is detected, the sensor module switches the area
to be controlled to an adjustable brightness value. As long as motion is
detected (P) or the hold time is running (2), this area remains switched on at
a fixed brightness value or the brightness is regulated when the constant
light control is activated. If no motion is detected during this time, it is
not switched off directly, but rather the absence value (2nd light level) is
called up for a defined time (4). The absence value is a fixed brightness
value (without constant light control). If motion is detected during this
absence time, the sensor switches back on to the predefined brightness value
(1, P). Recommendation: low to avoid it being higher than the value set by the
constant lighting control. Areas 1, 3 and 5 regulate the transitions between
states 7/P/2/4/7.
Light sensor
Light intensity measurement All DL2-BH98 versions have a light sensor. This
measures the re ected illuminance in a range from 0 to 2047 lux, the
resolution is 2 lux. The incident light is evaluated using the spectral light
sensitivity curve of the human eye and is therefore a measure of the
subjective perception of brightness. The incident light is measured in the
area of the lens area covered and can be viewed as the average value in this
area. A relative reference to the re ective surface below the sensor can be
established using a reference measurement and adjustable offset.
Function In principle, a distinction is made between an application controller
and the DALI-2 instances. The Application Controller leads to direct DALI
control commands that are immediately executed by the DALI drivers. The DALI-2
instances generate event messages that are interpreted and further processed
by higher-level control units (e.g. DL2-BH98 in master mode, FD2G14 or FD2G71L
gateway). Configuration of the instances is described in the ‘Instances’
section. DL2-BH98 can be used both as an application controller, as a master,
and in instance mode, as a slave. All operating modes and setting options
described in the document are available for the Application Controller.
Operating modes The sensor supports 4 operating modes. Motion control, motion
control with constant light control, constant light control only or light
threshold control. The operating behavior of the sensor can also be in uenced
using external commands (e.g. when operated via another control device). The
reaction to external commands is explained in detail for each operating mode.
Operating mode 1 motion control When there is motion, the light value is
switched on to a fixed value When motiont is detected, the sensor switches the
light on to a fixed value and starts the time sequence. After switching on,
the light value remains active until no more motion is detected and the hold
time has expired. The system then switches to the fixed 2nd light value. It
can also be set that the process only starts above or below a defined
threshold. The operating behavior can be in uenced by external on/off/dimming
and scene commands.
Operating mode 2 motion control with constant light control Constant light
control is activated when there is motion Second light value is a user-defined
fixed value. When there is motion, the timing is activated. After switching
on, the constant light control is active until no more motion is detected and
the holding time has expired. The system then switches to the fixed 2nd light
value (no constant light control). It can also be set that the motion and
light control is only active above or below a defined threshold. The operating
behavior can be in uenced by external on/off/dimming and scene commands.
Operating mode 3 – constant light control Constant light control No motion
detection In this operating mode, only the light sensor is used; motion
detection is inactive. The constant lighting control can be switched on and
off using DALI commands (e.g. from an operating device). The operating
behavior can be in uenced by external on/off/dimming and scene commands.
Operating mode 4 light threshold control Light control via light threshold
values No motion detection In this operating mode only the light sensor is
used. Both motion detection and constant light control are inactive. 4 light
thresholds can be defined which, if exceeded, trigger the sending of DALI
commands to the effective range. 2 of the 4 adjustable thresholds can be used
to send repeated commands. The commands are sent at a user-defined interval
until the threshold condition is no longer fulfilled. The operating behavior
can be in uenced by external scene commands.
Additional functions
Behavior when receiving external DALI commands The behavior of the control
system for external commands can be adjusted via the DALI Cockpit. Depending
on the operating mode, the behaviors described in the following document are
available to choose from. The following commands to the effective range (1st
target address) are interpreted as an on command: RECALL MAX RECALL MIN ON AND
STEP UP DAP>0% GOTO SCENE X (if the command was defined as a switch-on command
for the motion
detector)
The following commands to the effective range are interpreted as off commands:
OFF DAP=0 GOTO SCENE X (if the command was defined as a switch-off command or
a command to
call up the 2nd light value for the motion detector) Dimming commands: You can
also specify how the motion or light control should behave when manual dimming
commands (UP/DOWN) occur in the effective range (1st target address.
Switch-on and Bright Out threshold In order to adapt the motion detector to
the ambient lighting conditions, there are two threshold values for
brightness. Switch-on threshold: Depending on the setting, the time sequence
is started when motion is detected regardless of the light value (default) or
only below or above the switch-on threshold. For a running time sequence, you
can also specify whether detected motion is only triggered below the bright-
out threshold. Bright Out – Application example: The lighting in a parking lot
should switch off during the day (only ON if the measured light value <
70Lux), even if motion is detected during the transition period.
Power-on behavior In order to achieve a defined operating state after a power-
on (switching the bus voltage back on), either an adjustable DALI command or a
quick run-through of the motion detectors time sequence can be activated as behavior. Multiple sensors in the same group Several sensors can have the same effective range, e.g. to cover the detection area with several sensors. The sensor addresses for motion detection and for recording the light value can be set in the DALI Cockpit software (,Synchronisation
tab). The parameters of the
sensors should be coordinated, especially the follow-up times.
Manuals and documents in further languages:
https://eltako.com/redirect/DL2-BH98B-pm
1. App 2.
3. www.
Must be kept for later use!
ELTAKO GmbH
D-70736 Fellbach Technical Support English:
+49 711 943 500 25 technical-support@eltako.de eltako.com
18/2024 Subject to change without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>