RAB AerobayCooper Electric Installation Guide

June 24, 2024
RAB

RAB AerobayCooper Electric

RAB-AerobayCooper-Electric-product

Product Information

Specifications

  • Models: ARL, ARM, ARS, ARXS
  • Voltage: 120-277V
  • Mounting Options: V-Hook, Pendant (ARP)

Product Usage Instructions

V-Hook Mounting

  1. Use the provided V-Hooks for mounting.
  2. Connect to two lengths of chain suitable for the mounting surface.
  3. Determine fixture mounting height and spacing based on application requirements.
  4. Remove Access Plate, feed supply wires through, make electrical connections per wiring diagram.
  5. Reinstall Access Plate and secure with Access Plate Knob.

Pendant Mounting (ARP)

  1. Choose the appropriate length of Pendant Stem.
  2. Separate the Mounting Plate from the Pendant Cover Assembly.
  3. Attach the Pendant Cover Assembly to the Pendant Stem and tighten with Locknuts.
  4. Install the Mounting Plate on the Housing and secure with provided Screws.
  5. Hang Housing by hooking the Mounting Plate onto the Pendant Cover Assembly.
  6. Feed the supply wires through the Pendant Stem and make electrical connections per wiring diagram.

FAQ

Q: What should I do if I encounter difficulties during installation?
A: If you face any challenges during installation, please contact our Marketing Department at 888-RAB-1000 or email marketing@rablighting.com for assistance.

INSTRUCTIONS
AEROBAY® FIELD-ADJUSTABLE INSTALLATION

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside. Suitable for Damp location. Min. 90°C supply conductors.

V-HOOK MOUNTING

Mount Housing to sturdy ceiling structure as follows:

  1. V-Hooks (2) are provided for mounting (Fig. 1).
  2. Connect to two (2) lengths of chain (by others) and/or appropriate hardware (by others) suitable for the mounting surface to suspend the Housing from (2) V-HOOKS.
  3. Fixture mounting height and spacing should be determined by application requirements.
  4. Remove Access Plate by turning the Access Plate Knob and feed supply wires with strain relief or conduit connector through the opening in the Access Plate. Make electrical connections as shown in wiring diagram (Fig. 7). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Center Housing Channel. Be careful not to pinch wires.
  5. Reinstall Access Plate and secure with Access Plate Knob (1).

RAB-AerobayCooper-Electric- \(1\)

PENDANT MOUNTING (ARP)
Mount Housing to ceiling using Pendant Stem (by others) and Pendant Cover Assembly (ordered separately: Model #ARP) as follows:

ARP Non-Adjustable Pendant Kit (applicable models) :
Use with: ARM
ARL 120-277V
  1. Choose length of 3/4” Pendant Stem (by others).

  2. Separate the Mounting Plate from the Pendant Cover Assembly by pulling the End Cap away from the Pendant Cover Assembly to release the Pin holding the Mounting Plate in place as shown in Fig. 2.

  3. Remove Access Plate, attach the Pendant Cover Assembly to the Pendant Stem and tighten with Locknuts (by others) as shown in Fig. 3 and 4.

  4. Install the Mounting Plate on the Housing and secure with (4) Screws ( provided).

  5. RAB-AerobayCooper-Electric- \(2\)Hang Housing by hooking the Mounting Plate onto the Pendant Cover Assembly ( Fig. 4).

  6. Feed the supply wires through the Pendant Stem.

  7. Make electrical connections as shown in wiring diagram (Fig. 7).
    Use approved wiring connectors and wire to local NEC codes.
    Push all wires back into Housing. Be careful not to pinch wires.

  8. Push connections into the Pendant Cover Assembly.

  9. Rotate the Fixture up and slide the End Cap/Pin Assembly closed. Push the End Cap tight and check that it sits flush with the Pendant Cover Assembly to ensure it is fully locked. RAB-AerobayCooper-Electric- \(3\)

PENDANT MOUNTING (ARP-ADJ)
Mount Housing to ceiling using Pendant Stem (by others) and Adjustable Pendant Cover Assembly (ordered separately: Model # ARP-ADJ) as follows:

ARP-ADJ Adjustable Pendant Kit (applicable models) :
Use with: ARXS 120-277V
ARXS 480V
ARS 120-277V
ARM 480V
ARL 480V
  1. Choose length of 3/4” Pendant Stem (by others).
  2. Separate the Mounting Plate from the Pendant Cover Assembly by pulling the End Cap away from the Adjustable Pendant Cover Assembly to release the Pin holding the Mounting Plate in place as shown in Fig. 2.
  3. Remove Access Plate, attach the Adjustable Pendant Cover Assembly to the Pendant Stem and tighten with Locknuts (by others) as shown in Fig. 3.
  4. Install the Mounting Plate on the Housing and secure with (4) Screws ( provided).
  5. Hang Housing by hooking the Mounting Plate onto the Adjustable Pendant Cover Assembly.
  6. Feed the supply wires through the Pendant Stem.
  7. Make electrical connections as shown in wiring diagram (Fig. 7). Use approved wiring connectors and wire to local NEC codes. Push all wires back into Housing. Be careful not to pinch wires.
  8. Rotate the Fixture up and slide the End Cap/Pin Assembly closed. Push the End Cap tight and check that it sits flush with the Pendant Cover Assembly to ensure it is fully locked.
  9. Loosen the Thumb Screw on side of Adjustable Pendant Cover Assembly as shown in Fig 5. Use the Thumb Screw to slide the weight to balance the fixture to hang straight. Tighten Thumb Screw to secure in place.RAB-AerobayCooper-Electric- \(4\)

FIELD-ADJUSTMENT
Color Temperature (CCT) Selection:
This product is equipped with 5000K or 4000K CCT Color Temperature selection. For maximum light output use the 4000K Color Temperature (CCT).

Power (%) Selection:
This product is equipped with 50%, 75% and 100% power output selection.
Follow instructions below to change Color Temperature (CCT) and/or Power (%) from factory settings.
Factory Settings: 100% Power, 4000K CCT.

1. Locate Field-Adjustable Switches on the Fixture Center Housing Channel as shown in Fig. 6.
2. Select Color Temperature (CCT) and/or Power (%) by sliding the respective switch to the desired value (Fig. 6).RAB-AerobayCooper-Electric-
\(5\)

0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V through 277V, 50 or 60 Hz. Units ordered with /480 suffix are 480V ONLY.
For 0-10V dimming follow the wiring directions as shown in Fig. 7.

  1. Connect the black fixture lead to the LINE supply lead.
  2. Connect the white fixture lead to the COMMON supply lead.
  3. Connect the GROUND wire from fixture to supply ground.
  4. Connect the purple fixture lead to the (V+) DIM lead.
  5. Connect the pink fixture lead to the (V-) DIM lead.

NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink) to line voltage or supply ground.

RAB-AerobayCooper-Electric- \(6\)

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.

  1. Lens can be washed only after removing from fixture and only in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Do not use chemicals to clean Lens or fixture.
  2. Do not open fixture to clean the LED. Do not touch the LED.

TROUBLESHOOTING

  1. Check that the line voltage at the fixture is correct.
  2. Be sure the fixture is grounded properly.

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

BATTERY BACKUP MODELS

WIRING

CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join BATTERY connector until installation is complete and AC power is supplied to the emergency driver (Fig. 8).
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required. The emergency driver must be fed from the same branch circuit as the LED driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 Hz.

  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
  3. If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
  4. For 0-10V dimming, connect DIM (+) purple and DIM (-) pink leads to dimming connections.
  5. All unused leads must be capped and insulated.
  6. After installation is complete, supply AC power to the fixture and connect the BATTERY.
  7. When power is on, the fixture should be on and the CHARGING INDICATOR LIGHT should illuminate to indicate the battery is charging.
  8. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the Test Button as shown in Fig. 9.
  9. After the battery has charged for 24 hours, a long duration test can be performed by disconnecting power to the fixture.

RAB-AerobayCooper-Electric- \(7\)

OPERATION

  1. When AC power is applied the charging indicator light is illuminated indicating that the BATTERY is being charged.
  2. When power fails the standby power automatically switches to emergency power (internal battery) operating at reduced illumination.
  3. When AC power is restored the emergency driver automatically returns to charging mode.

MAINTENANCE

Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

  1. Visually inspect the charging indicator light monthly. It should be illuminated
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Be sure the fixture is grounded properly.
  2. If the charging indicator light does not illuminate after pressing the Test Button (Fig. 9), check if battery is connected properly.

RAB-AerobayCooper-Electric- \(8\)

Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered o © 2024 RAB LIGHTING Inc. nline or by request

AEROBAY XS-S-M-L – IN – 0624
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty.P-100771

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

RAB User Manuals

Related Manuals