dormakaba XL150-80 Premium DM Recessed Mount Installation Guide
- June 18, 2024
- dormakaba
Table of Contents
- XL150-80 Premium DM Recessed Mount
- Specifications:
- Technical Data:
- Tools Required:
- 1. Installation of DORMOTION unit:
- 2. Adjusting start/stop pin height (if necessary):
- 3. Secure drop ceiling extrusion:
- 4. Installation of recessed cover clips:
- 5. Installing brush profile:
- 6. Installing view protection clips:
- 7. Cover spacers:
- 8. Installing cover and view protection profile:
- 9. Install end caps:
- Q: What are the weight specifications for single and double
- Q: What tools are required for installation?
XL150-80 Premium DM Recessed Mount
“`html
Specifications:
Technical Data:
- Ceiling mount
- Door leaf weight:
- XL150: 330lbs [150kg]
- XL80: 176lbs [80kg]
Tools Required:
- 6 mm Ratching/combo (optional)
- Metric hex key set
- M4 long bit
- Tape measure
- Flat head screwdriver
- M4 short bit
- Drill
- 5/16 drill bit (for floor guide installation)
Product Usage Instructions:
1. Installation of DORMOTION unit:
Follow the instructions provided to install the DORMOTION unit
correctly.
2. Adjusting start/stop pin height (if necessary):
If required, adjust the start/stop pin height according to the
guidelines.
3. Secure drop ceiling extrusion:
Ensure the drop ceiling extrusion is securely in place to cover
the designated area.
4. Installation of recessed cover clips:
Install the recessed cover clips as per the provided
instructions for a secure fit.
5. Installing brush profile:
Place and secure the brush profile in the designated position
for proper functionality.
6. Installing view protection clips:
Follow the instructions to correctly install the view protection
clips for added safety.
7. Cover spacers:
Use the cover spacers as needed to ensure a proper fit and
finish.
8. Installing cover and view protection profile:
Securely install the cover and view protection profile to
complete the assembly.
9. Install end caps:
Finish by installing the end caps to complete the installation
process.
Frequently Asked Questions (FAQ):
Q: What are the weight specifications for single and double
door configurations?
A: The XL150 single door can support up to 330lbs [150kg], while
the XL80 single door can support up to 176lbs [80kg]. For double
doors with sidelites on both sides, the weight capacity doubles
accordingly.
Q: What tools are required for installation?
A: The tools required include a 6 mm Ratching/combo (optional),
metric hex key set, M4 long bit, tape measure, flat head
screwdriver, M4 short bit, drill, and a 5/16 drill bit for floor
guide installation.
“`
MUTO Premium XL150/80
Recessed mount Ceiling mount with Dormotion and Sidelites (Wood door)
Installation Manual
936057 – 11/2023 Original document
EN
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites Installation
Instructions
Table of contents
Table of Contents
1 Technical specifications 1.1 Overview
1.1.1General information 1.1.2Intended use 1.1.3Glass requirements and
fittings 1.1.4Requirements for glass panel 1.1.5Safety instructions
1.1.6Symbols used – Safety/Installation 1.1.7Maintenance, care, repair
1.1.8Disposal 1.2 Specifications – technical data 1.3 Tools required
2 2.1 2.2 2.3 2.4 2.5
2.6
2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20
Installation instructions Overall Installing end stops Securing gasket to track Securing sidelite section profile to track Securing track and sidelite extrusion into ceiling (and drop ceiling extrusion, if supplied) Specifications for securing track to mounting surface Door/wall dimensions Installing u-channel for sidelite Installing sidelite glass Installing sidelite glass filler panel Installing sidelite glass gasket Securing wood door adaptor Installing roller carriers Installing DORMOTION start/stop Disengaging the anti-jump Install door/rollers in track Install floor guide Engaging anti-jump Adjustment door height Adjustment end stop location: LEADING end stop Adjustment end stop location: TRAILING end stop
3 2.21 Install DORMOTION unit
17
3 2.22 Adjust start/stop pin height (if necessary) 19
3 2.23 Secure drop ceiling extrusion to cover
20
3 2.24 Install recessed cover clips
21
3 2.25 Install brush profile
21
3 2.26 Install view protection clips
22
3 2.27 Cover spacers
22
3 2.28 Install cover and view protection profile
23
3 2.29 Install end caps
23
3
4 3 Optional applications
24
4
5 5 6 6 6
7
8 9 10 10 11 11 11 12 13 13 14 14 15 15
16
2
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
Technical specifications
1 Technical specifications
1.1 Overview
These instructions are for installation of MUTO PREMIUM sliding door system
XL150/80 for wood doors for the following mounting and style versions:
1. Recessed mounting
1.1.1 General information · dormakaba requires use of tempered monolithic or
tempered laminated glass. · dormakaba glass hardware is not suitable for
application
in rooms where chemicals (e.g. chlorine) are used as indoor swimming pools,
saunas or salt-water pools. · Never move sliding panels faster than walking
speed and always stop the door manually before it reaches end position. · Do
not slide doors with excessive force. Install limiting stop to prevent door
from opening too far.
1.1.2 Intended use · For sliding door in dry indoor areas only · For manual
slowly opening and closing only
· Only properly qualified and specially trained staff are authorized to mount
dormakaba glass hardware.
· Due to crushing hazards and possible injury caused by breakage of glass
during mounting, corresponding protective clothing (especially gloves and
protective goggles) is required.
· Never clamp metal fitting hardware directly to glass surface.
1.1.6 Symbols used – Safety/Installation
CAUTION
Mounting components must meet the requirements of substructure/wall and door
weight. Please read the technical information for fittings.
WARNING
Risk of breaking glass. When installing the door, support the door panel with
a block of wood or similar object.
1.1.3 Glass requirements and fittings · The substructure/wall must be able to
bear permanent
loads and be level (max. tolerance: 1/16″ [2] per 39″ [1m]). · Fasteners must
be sufficiently dimensioned for the substructure/wall and weight of the door.
· When adjusting glass components, always stick to the required clearance for
the respective hardware. Adjust clearance so glass does not come in contact
with any hard surfaces such as glass, metal or concrete. · Do not use
excessive force when installing the glass (avoid over tightening screws).
1.1.4 Requirements for glass panel · dormakaba requires use of fully tempered
glass, which
complies with ASTM C 1036 and ASTM C 1048. Secondary heat soaking processes
are recommended but not required. This applies to both tempered monolithic and
tempered laminated glass. · Clamping area must be flat and uncoated (no
selfcleaning coating!) · Never use glass with conchoidal fractures and/or
damaged edges.
1.1.5 Safety instructions · Installation requires two people. · Always wear
protective clothing.
TIPS AND RECOMMENDATIONS
Information note
CLOSING EDGE
1.1.7 Maintenance, care, repair · Immediately replace damaged parts. · Always
use original dormakaba parts. · Clean clamping area with alcohol-based
standard
commercial cleaning agent before mounting the glass hardware. · Use a damp
clothe for occasional cleaning, especially the track. · Always use silicone –
and oil-free cleaners (e.g. acetone). · Check glass hardware at regular
intervals for proper positioning and smooth operation and correct adjustment.
· High traffic door systems require inspection by properly qualified staff
(specialized companies or installation firms.)
1.1.8 Disposal Disposal in accordance with local, state and national
regulations.
MUTO Premium Recessed Mount
936057
11-2023
3
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
1.2 Specifications – technical data
Ceiling Door leaf weight lbs [kg] mount
- Including weight of auxiliary hardware.
Single door
XL150
330lbs [150]
XL80
176lbs [80]
Technical specifications
Sidelites on both sides
XL150
XL80
2 x 330lbs [2 x 150]
2 x 176lbs [2 x 80]
1.3
Tools required
6 mm Ratching/ combo (optional)
Metric hex key set
M4 long bit
Tape measure
Flat head screw driver
M4 short bit
Drill
5/16 drill bit (for floor guide installation)
4
MUTO Premium Recessed Mount
936057
11-2023
5
11-2023
936057
MUTO Premium Recessed Mount
1.1 1.2 1.3
1.9
1.8 1.10 1.6
1.4
1.5 1.11 1.12
1.1 Cover 1.2 Brush strip 1.3 Track 1.4 Sidelite section
profile
1.5 Filler panel 1.6 Roller carrier 1.7 Recessed cover clips 1.8 End stop
1.9 1.10 1.11 1.12
Dormotion unit Start/stop guide Floor guide U-channel
1.15 1.9 1.8 1.13 1.7 1.17 1.14
1.16
1.13 1.14 1.15 1.16 1.17
View protection clips View protection profile Sidelite glass gasket U-channel gasket Wood door adaptor
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2 Installation instructions
2.1 Overall
Fig. 1
Overall
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.2
Fig. 2
Installing end stops
Set screw
Track
End Stops Sidelite gasket Sidelite profile
Set screw
End stops
2.2.1 Slide end stops into each end of the track. NOTE: Loosen bottom section
of end stop for easier install.
2.3 Securing gasket to track
Fig. 3
Track
Hex key size XL150/80 4mm
Bottom section of
end stop
NOTE: FOR XL150 end stops, be sure set screw is flush with back of end stops.
NOTE: Exact location/adjustments will be determined in the Adjustment End Stop
Location step.
Adhesive gasket
2.3.1 Ensure the track is cut to proper length. NOTE: SEE DIMENSION
INSTRUCTIONS ON PAGE 9.
Sidelite glass
2.3.2 Cut adhesive gasket equal to sidelite glass width. 2.3.3 Adhere gasket
along bottom edge of back of
track.
2.4 Securing sidelite section profile to track
Fig. 4
Sidelite profile
Track
NOTE: LEAVE EVERY OTHER HOLE EMPTY ONLY if securing drop ceiling extrusion.
2.4.1 Align sidelite profile holes with track profile holes. NOTE: Holes will be predrilled every 7-7/8″ [200]. 2.4.2 Secure with 9/16″ (14) fasteners provided.
NOTE: Be sure fastener heads are flush with track to avoid rollers catching protruding fasteners.
6
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.5 Securing track and sidelite extrusion into ceiling (and drop ceiling
extrusion, if supplied)
Fig. 5
OPTION 1: If recessed ON BOTH SIDES; DRYWALL VERTICALLY MOUNTED, reference the
following images:
Option 1
Wood blocking
Metal frame
Header mounting surface
Track
min. 3-3/4″ [95]
Sidelite profile
Drop ceiling extrusion 1/4″
OPTION 2: If recessed ON BOTH SIDES; MAY BE DROP CEILING PROFILE OR
Option 2
REINFORCED DRYWALL, reference the following images:
See other Optional Applications at back of installation instructions.
Drop ceiling extrusion
2.5.1 Drill 1/4″ pilot holes through remaining empty holes in track, through sidelite profile.
2.5.2
Secure drop ceiling extrusion to track and sidelite profile with 1-3/8″ [35] fasteners provided.
Metal frame
Header mounting surface
Track
Sidelite profile
Drop ceiling extrusion
MUTO Premium Recessed Mount
936057
Track
Pre-drill through track groove
1-3/4″ [45]
Track groove
11-2023
7
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
Track
2.6 Specifications for securing track to mounting surface
2.6.1 Ensure the track is properly level and secure it to the header mounting
surface per the appropriate measurements on the following page.
NOTE: SEE DIMENSION INSTRUCTIONS ON NEXT PAGE FOR REFERENCE.
2.6.2 Use appropriate fasteners according to the following recommendations.
NOTE: OVERHEAD REINFORCEMENT: The overhead reinforcement must be a minimum of ¼” [6] x 3″ [76] steel angle, 16 gauge metal stud, or two pieces of 1 1/2″ [38] thick wood blocking (double stacked), secured to studs or joists on a maximum 16″ [406] centers for the length of the track. The overhead reinforcement may be flush on the overhead surface or on the interior of this surface.
Track mounting screws must fully penetrate the steel angle, metal stud, or at
a minimum of 2″ [51] into wood blocking, utilizing the predrilled holes in the
MUTO track.
Consult with a structural engineer to determine if reinforcement is adequate
for your specific application or to meet specific codes in your location.
8
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.7 Door/wall dimensions
Single sidelite mount
(DW)
Wood door panel
(FPW)
Sidelite glass
1-3/16″ [30] clear opening width (CW)
Multiple sidelite mount
(FPW) Sidelite
glass
1-3/16″ [30]
(DW)
Wood door panel
(FPW2) Sidelite
glass
1-3/16″ [30]
clear opening width (CW)
MUTO Premium Recessed Mount
936057
Technical specifications
Back of track to center of mounting hole in track
7/8″ [23]
1/2″ [13] Bottom of glass to floor
3/8″ [10] Bottom of wood door to floor
Back of track to center of mounting hole in track
7/8″ [23]
1/2″ [13] Bottom of glass to floor
3/8″ [10] Bottom of wood door to floor
11-2023
9
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.8 Installing u-channel for sidelite
Fig. 6
U-channel gasket
U-channel Sidelite glass
Orient gasket(s) as shown.
2.8.1 Install gaskets as shown. Trim to correct length. 2.8.2 Secure u-channel
to floor using appropriate
fasteners.
2.9
Fig. 7
Installing sidelite glass
Drop ceiling extrusion
U-channel NOTE: Ensure u-channel is plumb and the back of the u-channel
profile aligns with back of sidelite profile. NOTE: Gaskets are pre-installed.
Sidelite profile
Sidelite glass
Lift up into sidelite profile
U-channel
Lower down into u-channel
U-channel setting blocks
Sidelite glass
1/8″ gap
Sidelite glass
Wall
2.9.1 Place setting blocks into u-channel. 2.9.2 Spray inside of u-channel with glass cleaner. 2.9.3 Lift glass up and into sidelite profile. 2.9.4 Lower glass into u-channel.
10
MUTO Premium Recessed Mount
936057
2.9.5 Ensure there is 1/8″ [3] gap between wall and edge of sidelite glass.
2.9.6 If using tempered laminated glass, gently press glass against u-channel
gasket, and dispense silicone along full length of non-gasket side of
u-channel.
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.10 Installing sidelite glass filler panel
Fig. 8
Track
Filler panel Sidelite gasket Wood door adaptor
Filler panel
Sidelite glass
2.10.1 Fit filler panel between empty section of track and sidelite profile,
on door side.
2.11 Installing sidelite glass gasket
Fig. 9
Sidelite profile
Sidelite profile
Filler panel
2.11.1 Cut gasket to length.
Sidelite gasket
Drop ceiling extrusion
Sidelite gasket location
Sidelite glass
2.11.2 Press gasket in between sidelite glass and sidelite profile.
2.12 Securing wood door adaptor
Fig. 10
XL150/80
XL150/80
Wood door adaptor
Every 4th hole
Every
Every
4th hole 4th hole
Every 4th hole
1/2″ [13]
NOTE: Top of door must be reinforced to secure wood door adapter.
2.12.1 Prepare door properly for wood door adaptor.
NOTE:
Seal top and bottom of door to minimize warping (use wood door manufacturer’s recommendations).
MUTO Premium Recessed Mount
936057
Wood door
2.12.2 Cut wood door adapter to be equal width of door.
2.12.3
Secure the two wood door adaptor pieces to top of wood door with #10 x 3″ wood screws.
NOTE: Be sure screws are always secured in the first four and last four holes of the adaptor, along with every fourth hole in between.
11-2023
11
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.13 Installing roller carriers
Fig. 11
DETERMINE THE LEADING (X) VERSUS TRAILING (Z) EDGE OF THE GLASS. “LEADING IS
SIDE CLOSEST TO LATCH CLOSED.”
Z
Roller carriers X
Secure
Roller location on wood door with DORMOTION unit
XL150/80
Single door X
3-1/8″ [80]
Double door X
1-9/16″ [40]
Single door Z
1-9/16″ [40]
Double door Z
2-3/8″ [60]
Roller carrier
Legend Closing edge of door
Torque values XL150/80 10ft lbs
[14Nm] Hex key size XL150/80 4mm
(Front of) Wood door
(Front of) Wood door
NOTE: FULLY CLEAN SURFACE OF ADAPTOR WITH AN ALCOHOL-BASED MILD GLASS AND SURFACE CLEANER. ENSURE GASKET IS FREE OF DEBRIS. ENSURE ROLLER CARRIER WHEELS ARE FREE OF DEBRIS.
2.13.1 2.13.2
Slide roller carriers onto wood door adaptor.
Slide gasket and metal shim between adaptor and roller carrier.
NOTE: Orient with gasket facing the adaptor.
2.13.3
Secure roller carriers to wood door adaptor using appropriate-size hex key at 10ft lbs (14 Nm).
12
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.14 Installing DORMOTION start/stop
Fig. 12
PRODUCT SHIPPED WITH 7/8″ [22] PIN INSTALLED. PIN CAN BE CHANGED TO 1″ [25] IF NECESSARY.
Start/stop pin
Images not to scale
Hex screws
7/8″ [22] =
1″ [25] =
Start/stop Anti-jump
Torque Set screws
3 ft lbs [3 Nm]
Hex key size Set screws 3 mm Hex screws 3 mm
Set screws
Start/stop
Glass gasket
NOTE:
2.14.1 · · · ·
Determine a pin length based upon how square and plumb the opening is. If required, change pin in start/stop assembly. Remove hex screws. Remove existing pin and plate. Swap in appropriate pin and plate. Replace hex screws.
2.14.2 2.14.3 2.14.4
NOTE:
Slide start/stop onto glass. Center equally between the carriers. Slide glass gasket between start/stop and glass. Orient with gasket facing glass.
2.14.5 Secure start/stop via set screws.
2.15 Disengaging the anti-jump
Fig. 13
1/4 turn
Antijump
Antijump
NOTE: Anti-jump shipped engaged.
7/8″
2.15.1 Disengage the anti-jump on roller carrier.
MUTO Premium Recessed Mount
936057
1-1/4″
Anti-jump adjustment screw
Bit size
XL150/80 4mm x 7/8″ 4mm x 1-1/4″
NOTE: Using optional ratchet and [one of the] provided bits, push anti-jump adjustment screw IN and turn COUNTER-CLOCKWISE 90° to disengage anti-jump.
11-2023
13
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.16 Install door/rollers in track
Fig. 14
Track Floor guide
NOTE: WOOD DOOR ADAPTOR NOT SHOWN IN IMAGES
Track Rollers
ENSURE ROLLERS AND TRACK ARE FREE OF DEBRIS.
2.16.1 Tip wood door and rollers upward and rest rollers on track.
2.17 Install floor guide
Fig. 15
Wood door
Wall
Sidelite glass
5/16″ [7]
Wood door
Floor guide
=
=
U-channel
Floor guide
1-1/[43″2]
2.17.1
2.17.2 2.17.3
REMEMBER ANTI-JUMP IS DISENGAGED! Temporarily slide floor guide into bottom groove of wood door. Be sure the door is plumb. Mark appropriate floor guide measurements.
2.17.4
2.17.5 2.17.6 2.17.7
TEMPORARILY REMOVE WOOD DOOR AND ROLLERS FROM TRACK (TO ALLOW FOR DRILLING
SPACE).
Pre-drill into mounting surface using a 5/16″ drill bit.
Secure floor guide with included fasteners.
SET WOOD DOOR AND ROLLERS BACK ONTO TRACK.
14
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.18 Engaging anti-jump
Fig. 16
Antijump
1/4 turn
Antijump
Anti-jump Height adjustment
7/8″
Anti-jump adjustment screw
2.18.1 Engage anti-jump on roller carrier.
1-1/4″
Bit size XL150/80 4mm x 7/8″
4mm x 1-1/4″
NOTE: Using the optional ratchet and [one of the] provided bits, push anti-
jump adjustment screw IN and turn CLOCKWISE 90° to engage anti-jump.
2.19 Adjustment door height
Fig. 17
5/16″ [7] =
U-channel
+3/16″ [5] -3/16″ [5] Wood door =
Door height adjustment tolerance
XL150/80
+3/16″ [+5] -3/16″ [-5]
3/8″ [10]
7/8″
use 1-1/4″ Height bit Adjustment screw
XL150/80 torque 10 ft lbs [14 Nm] 1-1/4″
Bit size XL150/80
Height adjustment locking screws use
7/8″ bit 4mm x 7/8″ 4mm x 1-1/4″
2.19.1 2.19.2
Set height of wood door. Using the optional ratchet and [one of the] provided bits, loosen height adjustment locking screws of carrier.
2.19.3
Using optional ratchet and [one of the] provided bits, turn height adjustment screw CLOCKWISE or COUNTER-CLOCKWISE to raise or lower wood door.
NOTE: Be sure glass is level during this adjustment.
MUTO Premium Recessed Mount
936057
11-2023
15
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.20 Adjustment end stop location: LEADING end stop
Fig. 18
0mm
END STOP LOCATION: LEADING EDGE
NOTE: bi-folding: Be sure there is a 1/4″ [6] gap between the right and left hand sets.
End stops
Hex key size XL150/80 3mm
End stop
Bumper
Door overlap on wall
max. 1-3/16″ [30] Wood door edge
Jamb edge
Edge of roller carrier
Door pull
Door closed
Door pull to jamb distance. Verify with local jurisdiction.
Torque XL150/80
3 ft lbs [4 Nm]
Set end stop locations: 2.20.1 Slide end stop
to desired location on track. Bumper should touch edge of roller carrier.
Bumper
Secure
Adjustment end stop location: TRAILING end stop
Fig. 19
0mm
END STOP LOCATION: TRAILING EDGE
NOTE: bi-folding: Be sure there is a 1/4″ [6] gap between the right and left hand sets.
Hex key size XL150/80 3mm
Edge of roller carrier
Wood door edge
End stop Bumper
Jamb edge
Door opened
Door pull
Door pull to jamb distance. Verify with local jurisdiction.
Torque XL150/80
3 ft lbs [4 Nm]
Set end stop locations: 2.20.1 Slide end stop
to desired location on track. Bumper should touch edge of roller carrier.
Bumper
Secure
16
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.21 Install DORMOTION units
Fig. 20 Fig. 20.1 RH DM unit
Fastening plate
DM end stop
Hook
Fig. 20.2 RH DM unit fastening plates rotated
Dormotion unit
RH Dormotion -door closed
2.21.1 Rotate RH DM fastening plates.
·
Using 4 mm hex key, loosen
fastening plate hex screws.
·
Rotate fastening plates until they
are parallel to the DM unit (Fig. 20.2)
·
Snug hex screws.
2.21.2 ·
Move door to close position. For installation of RH DM unit, door must be in the closed position against bumper.
Fig. 20.7 RH DM unit aligned in track
Fig. 20.3 RH DM unit inserted in track
DM unit DM trigger block
Door closed
Fig. 20.4 DM unit hook positioned in trigger
DM hook DM end stop
Trigger
Roller carrier Bumper
RH DM unit
Door closed
Fig. 20.5 DM unit end stop and hook separation adjustment
Adjustment tool Fork
Fork gap DM end stop
DM hook Trigger
Bumper RH DM unit
Door closed
Fig. 20.6 RH DM unit fastening plates secured in track
Plates rotated
Fastening plates
SHCS
SHCS
2.21.3 Align DM unit in track, engage DM hook in DM trigger.
·
Align DM unit in track (Fig. 20.7).
·
Slide DM unit over the DM trigger
block until the DM hook engages
the DM trigger (Fig. 20.4)
2.21.4 · · ·
Use adjustment tool to set DM unit final position. Place adjustment tool flat against DM unit with fork between DM hook and DM end stop (Fig. 20.5). Slide DM unit over until hook and DM end stop are against the fork. This sets 5 mm gap (fork gap). Trigger height: Adjust so trigger sets on top of adjustment tool (Para. 2.22).
2.21.5 Secure the DM unit in position.
·
NOTE: Insure door is fully closed
against bumper before performing
this step.
·
Using 4 mm hex key, tighten DM
unit fastening plate socket head
cap screws . Fastening plates must
engage the track (Fig. 20.6 and .8).
Torque Socket head cap screws 3 ft lbs [4 Nm]
Fig. 20.8 RH DM unit installed in track
Plates rotated
MUTO Premium Recessed Mount
936057
11-2023
17
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
Fig. 20 DM unit installation (Con’t) Fig. 20.9 LH DM unit
Fastening plate
Hook
DM end stop
Fig. 20.10 LH DM unit fastening plates rotated
Dormotion unit
LH Dormotion -door open 2.21.6 Rotate DM fastening plates.
·
Using 4 mm hex key, loosen
fastening plate hex screws.
·
Rotate fastening plates until they
are parallel to the DM unit (Fig. 20.10)
·
Snug hex screws.
2.21.7 Move door to open position.
·
For installation of LH DM unit, door
must be in the open position
against bumper.
Fig. 20.15 LH DM unit aligned in track
Fig. 20.11 LH DM unit inserted in track
LH DM unit
DM trigger block
Door open
Fig. 20.12 DM unit hook positioned in trigger
Trigger
DM hook DM end stop
Roller carrier Bumper
LH DM unit
Door open
Fig. 20.13 DM unit end stop and hook separation adjustment
Adjustment tool Fork
DM hook Trigger
Fork gap DM end stop
LH DM unit
Bumper
Door open
Fig. 20.14 LH DM unit fastening plates secured in track
Plates rotated
Fastening plates
SHCS
SHCS
2.21.8 Align DM unit in track, engage DM hook in DM trigger.
·
Align DM unit in track (Fig. 20.15).
·
Slide DM unit over the DM trigger
block until the DM hook engages
the DM trigger (Fig. 20.12)
2.21.9 ·
·
·
Set DM unit final position.
Place adjustment tool flat against DM unit with fork between DM hook and DM
end stop (Fig. 21.13). Slide DM unit over until hook and DM end stop are
against the fork. This sets 5 mm gap (fork gap). Trigger height: Adjust so
trigger sets on top of adjustment tool (Para. 2.22).
2.21.10 Secure the DM unit in position.
·
NOTE: Insure door is fully open
against bumper before performing
this step.
·
Using 4 mm hex key, tighten DM
unit fastening plate socket head
cap screws . Fastening plates must
engage the track (Fig. 20.16).
Torque Socket head cap screws 3 ft lbs [4 Nm]
Fig. 20.16 LH DM unit installed in track
Plates rotated
18
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.22 Adjust start/stop pin height (if necessary)
Fig. 21
Hex screw
Hex screw
NOTE: WOOD DOOR ADAPTOR NOT SHOWN IN IMAGES
Start/stop
Start/stop pin
2.22.1
· ·
Adjust HEIGHT of start/stop
pin, if necessary:
Loosen hex screws.
Slide pin and plate up or down.
Hex key size
Hex
3 mm
screws
CORRECT PIN HEIGHT/ ORIENTATION
MUTO Premium Recessed Mount
936057
11-2023
19
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
2.23 Secure drop ceiling extrusion to cover
Fig. 22
APPLICATION OPTION: Drop ceiling on inside AND outside of door panel.
See Optional Applications section for more choices.
Sidelite section profile
Header mounting surface
Metal frame
Drop ceiling extrusion
Drop ceiling extrusion
Cover Drop ceiling
Cover
2″ [51]
12″ [305]
12″ [305]
12″ [305]
Cover groove
1-3/4″ [45]
2.23.1 Pre-drill holes through cover groove into drop ceiling extrusion.
Pre-drill through cover
12″ [305]
12″ [305]
12″
[305]
2″
[51]
Drop ceiling extrusion
·
End holes: approximately 2″ [51] from end of
cover
·
All other holes: approximately 12″ [305] apart
20
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.24 Install recessed cover clips
Fig. 23
Drop ceiling extrusion hidden for easier viewing.
Cover clip
Screw
Recessed cover clips Brush profile
2.24.1 Slide cover clips on from end of cover. 2.24.2 Tighten with screw. Be
sure not to damage
cover.
2.25 Install brush profile
Fig. 24
Cover
NOTE: 1 clip per two feet of cover extrusion.
Brush
2.25.1 Measure and cut brush to appropriate length.
2.25.2 Slide brush into cover.
MUTO Premium Recessed Mount
936057
11-2023
21
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.26 Install view protection clips
Fig. 25
TO BE USED WITH ONE OR MULTIPLE SIDELITE APPLICATIONS.
View protection clips Cover spacers
Empty sliding portion of track
(Slide door panel) Wood door panel
View protection clip
Sidelite glass
View protection profile
View protection clips
NOTE: WOOD DOOR ADAPTOR NOT SHOWN IN IMAGES
Cover
2.26.1 2.26.2
Measure and cut view protection profile to fit into empty sliding portion of track – 3/16″ [5]. Snap view protection clips onto inside of cover as shown.
2.26.3 Use minimum 1 clip per foot of profile. Exception: If profile is minimum of 1 foot [305] in length, use 2 clips.
2.27 Cover spacers
Fig. 26
Cover spacer
Cover spacer
2.27.1 Tip cover spacers into outter most edge of track.
22
MUTO Premium Recessed Mount
936057
Hex key size
XL150
2.5mm
2.27.2 Place one at each end of track as shown. 2.27.3 Tighten at at 1 ft lbs [1Nm] or hand tighten.
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
2.28 Install cover and view protection profile
Fig. 27
Track groove
Back prong lip
Front prong lip
Recessed cover clip
View protection clip removed for easier viewing of cover installation.
View protection profile
Cover End caps
Note: If necessary, engage clip to track with flat screw driver (minimum 3/16″
wide blade) until snapped into place.
NOTE: WOOD DOOR ADAPTOR NOT SHOWN IN IMAGES
Cover
2.28.1 Install cover: · Insert back prong lip of recessed cover clip into
groove first. · Rotate cover assembly up and then snap front
prong lip of clip into track groove.
2.28.2 Once cover is in place, tip view protection profile up in between track
and cover.
2.28.3 Snap down into cover and onto track as shown.
2.29 Install end caps
Fig. 28
Sidelite profile end cap
Wood door
Cover end cap
Wood door
2.29.1 Snap sidelite profile end caps into sidelite profile.
MUTO Premium Recessed Mount
936057
Sidelite profile end cap
2.29.2 Snap end caps into cover.
Cover end cap
11-2023
23
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door)
Installation Instructions
3 Optional applications
Fig. 29
Option 3 Recessed both sides; drop ceiling profile one side/ flush vertical
drywall other side.
Drop ceiling extrusion
Sidelite section profile
Drop ceiling extrusion
Optional applications
Option 4 Recessed one side only; drop ceiling profile one side/ vertical
drywall above.
Cover
Track
Option 5 Recessed both sides; drop ceiling profile one side/ reinforced drywall other side.
Drop ceiling extrusion
Option 6 Recessed one side only; drop ceiling profile cover side/ reinforced
drywall above side lite profile
Drop ceiling extrusion
Sidelite section profile
Drop ceiling extrusion
Cover
Option 7 Recessed one side only; drop ceiling profile one side/ reinforced
drywall above cover.
Cover
Track
NOTE: Required blocked for proper securing of drywall not shown.
24
MUTO Premium Recessed Mount
936057
11-2023
dormakaba MUTO Premium DM Recessed Mount XL150/80 with Sidelites (wood door) Installation Instructions
Blank page