legrand LE11299BD Three-Phase Meter Instruction Manual

June 3, 2024
Legrand

4 120 92
4 120 93



The instructions for installation and use must be strictly observed in order to avoid the risk of electric shock or fire.

• Wiring diagrams

legrand LE11299BD Three-Phase Meter A02

• Input/Output
U 3x230V / 3x400V ± 15% CAT III
I Imin= 0,25A Itr= 0,5A Iref= 5A Imax= 63A
cl. 4 120 92
4 120 93 B (EN 50470-1,3)

LED| 1 Wh/imp.
COM| | RS485 Modbus|

L1-L2-L3

| 11 mm          MAX

1 x 10 mm2
1 x 10 mm2
1 x 16 mm2

|

Recommended torque 1,6 to 2Nm COMBI PZ2

__

1 C



RS485


| 8 mm           MAX

  1 x 1 mm2
  1 x 1 mm2
  1 x 1,5 mm2

| Recommended torque 0,2Nm 0,5 x 2,5mm

__| -25°C ) – (70°C)

• Positions for lead plating

legrand LE11299BD Three-Phase Meter A05

• RS485 wiring diagram

legrand LE11299BD Three-Phase Meter A06

(1)RS485:
Prescribed use of Cable Belden 9842, Belden 3106A (or equivalent) for a maximum length of 1000 m or Category 6 cable (FTP or UTP) for a maximum length of 50 m;

*Resistance not furnished with the article 4 120 92 – 4 120 93

legrand LE11299BD Three-Phase Meter A07 Modbus Address: 5
Baud Rate: 19,2 kbps
Parity

Complete documentation is available at www.e-catalogue.legrandgroup.com Type “4 120 92 – 4 120 93” in the search field.”

EU DECLARATION OF CONFORMITY

n° 10 0066 02

We
LEGRAND FRANCE
128, Avenue du Marechal de Lattre-de-Tassigny – 87045 LIMOGES CEDEX – FRANCE

declare under our sole responsability that the product:

trade mark :
LEGRAND
4 120 92      4 120 93

designation :
3-phase meter 4M 63A direct – MID

manufactured by :
LEGRAND
BP 30076
87002 LIMOGES CEDEX FRANCE

is in conformity with the relevant Union harmonisation legislation :

2014/35/EU of 26-02-2014 (Low Voltage)

and 2014/30/EU of 26/02/2014 (Electromagnetic Compatibility)

and 2014/32/UE du 26-02-2014 (Mesuring Instrument) and 2011/65/EU of 08/06/2011 modified by 2015/863 of 31/03/2015 (ROHS 2)

on condition that it is used in the manner intended and/or in accordance with the current installation standards and/or with the manufacturer’s recommendations.

These provisions are ensured by conformity to the following standards :

EN 50470-1:2006; EN 50470-3:2006;

The product match the product described in the EU type examination certificate N° 0120/SGSO447 issued by the Notified Body 0598

This declaration state that the fulfilment of the essential requirements set out in the annexe I and in the relevant instrument specific annexes has been demonstrated

Marcello RE

Phone :+ 33 (0)5 55 06 87 87                           Fax :+ 33 (0)5 55 06 88 88

V7

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>