Honeywell Hand Held Test Tool User Guide

June 7, 2024
Honeywell

Honeywell Hand Held Test Tool -ligo1

QUICK START GUIDE
HANDHELD TEST TOOL
SEARCH ZONE SONIKHoneywell Hand Held Test Tool -
logoHoneywell Hand Held Test Tool -
FigureHoneywell Hand Held Test Tool -
Figure1Honeywell Hand Held Test Tool - Figure-
5

Quick Start Guide

WARNING
Read these user instructions carefully before using this equipment. User instructions must always be available to the user and are not to be removed except by the user  of this equipment. For proper use, see supervisor, user instructions, or contact the manufacturer.

WARNING
Do not mix battery types. Replace the batteries only with the types listed in the Specifications. Use of batteries other than those specified in the Specifications will invalidate the certification.

Waste Electrical and Electronic Equipment (WEEE)
This product complies with the Waste Electrical and Electronic Equipment (WEEE) Directive 2012/19/EU. Components or assemblies bearing this or similar symbols shall not be treated as household or municipal waste. Waste electrical products (end of life) shall be recovered and disposed of at specialist WEEE disposal facilities. Contact your local authority, your distributor, or the manufacturer if you require more information about recycling WEEE.

Box Contents

  • Hand Held Test Tool
  • Set of 10 AAA batteries
  • Hexagon socket key size 6 mm
  • Hand Held Test Tool Quick Start Guide (this document)
  • Certificate

List of Markings
Warning
WEEE mark
UL certification mark
Explosive atmosphere class
European Economic Area certification mark
Environment-Friendly Use Period

Honeywell Hand Held Test Tool -ligo1

Intrinsically Safe – À Sécurité Intrinsèque
Cl. I, Div. 1, Grps. A,B,C,D, T4
Cl. I, Zn. 1, AEx ia IIC T4
Ex ia IIC T4
Ta -20°C to +50°C
IP66
Patent: www.hsmpats.com

HANDHELD UNIT TEST TOOL

Part NO. 2331B1000
Serial NO. XXXXXXXXX
Mod State: 1 2 3 4 5 6 7 8 9 10

WARNING/AVERTISSEMENT
Read and understand manual before installation, operation or servicing. Substitution of components may impair intrinsic safety. Do not open or replace battery when an explosive atmosphere is present.
Use only DURACELL MN2400 AAA batteries or equivalent (refer to Quick Start Guide for allowed battery types).
Honeywell Analytics Ltd., Poole, Dorset, BH17 0RZ Made in UK

Honeywell Hand Held Test Tool -ligo1
HANDHELD UNIT – TEST TOOL
Ex ia IIC T4 Gb Ta -20°C to +50°C
DEMKO20ATEX2247
IECEx UL20.0043
IP66
Patent: www.hsmpats.com

Part NO. 2331B1000
Serial NO. XXXXXXXXX
Mod State: 1 2 3 4 5 6 7 8 9 10

WARNING
Read and understand manual before installation, operation or servicing. Substitution of components may impair intrinsic safety.
Do not open or replace battery when an explosive atmosphere is present.
Use only DURACELL MN2400 AAA batteries or equivalent (refer to Quick Start Guide for allowed battery types)
Honeywell Analytics Ltd., Poole, Dorset, BH17 0RZ Made in UK

Example certification labels

Honeywell Hand Held Test Tool -Example

Example warning label

Instructions

The Hand Held Test Tool is an ultrasound-generating device used for functional verification of the Searchzone Sonik detector. It may be used in combination with the Search zone Sonik App running on a suitable mobile device.

The Hand Held Test Tool generates two different test signals to check detector’s functionality:

  1. First test signal is recognized by the detector as a ‘bump test’ and is used to perform the local test. It is reported through change in detector’s LED ring status indicator, however, the detector’s outputs will NOT be activated. This local test is automatically logged.
  2. The second test signal is used for END-to-END testing. It is reported as Alarm through detector’s LED ring status indicator, relays and through 4-20mA loop.

WARNING
While operating the Hand Held Test Tool, do not under any circumstances aim the tool towards your head, or any other person.
NOTE: When using the Hand Held Test Tool, ensure that it is operated at least 1m from the Searchzone Sonik detector.

Sound pressure levels and usable beam

Honeywell Hand Held Test Tool - Sound pressure levels and usable
beamHoneywell Hand Held Test
Tool - Sound pressure levels and usable beam-

  1. Performing LOCAL Test
    WARNING
    Do not under any circumstances aim the detector at the head or ears of you or anyone else.
    1.1 Local test with Hand Held Test Tool alone
    1. Ensure that Searchzone Sonik is powered and operational.
    2. Aim the Hand Held Test Tool towards the face of Searchzone Sonik detector. Keep the distance between the Searchzone Sonik detector and the Hand Held Test Tool in the range of 1 to 10 m (3.3 to 33 ft.).
    3. Press and hold the Test Button (Figure ). The Hand Held Test Tool will produce audible beeps and show a red LED light to confirm that it is emitting the test signal.
    4. The detector will recognize the test signal and the LED status indicator
    will flash red.
    5. Release the Test Button. The LED status indicator will return to the default state (green). In this mode, the outputs are NOT affected.
    1.2 Local test with Searchzone Sonik App and Hand Held Test Tool
    1. Login to the Searchzone Sonik App.
    2. Connect the Searchzone Sonik App to the detector.
    3. Navigate to the main menu and tap on Detector Overview. Then tap on Proof Test.
    4. Aim the Hand Held Test Tool to the face of the detector. Keep distance between the Searchzone Sonik detector and the Test Tool in the range of 1 to 10 m (3.3 to 33 ft.).
    5. Press the Test Button (Figure ) on the Hand Held Test Tool.
    6. The detector will recognize the test signal and LED status indicator will flash red.
    7. While the Test Button is pressed the Searchzone Sonik App will indicate the test signal as recognized. The test is automatically logged by the Searchzone Sonik App.
    8. Release the Test Button.
    9. The LED status indicator will return to default state (green).
    1.3 END-to-END Test
    NOTE: If you are NOT using the Searchzone Sonik App, begin with Step 4.
    1. Login to the Searchzone Sonik App.
    2. Connect the Searchzone Sonik App to the detector.
    3. Navigate to main menu and tap on Detector Overview. Then tap on Proof Test.
    4. Aim the Hand Held Test Tool to the face of the detector. Keep distance in the range of 1 to 10 m (3.3 to 33 ft.).
    5. Turn and hold the Rotating Collar (Figure 2) to select Test Mode
    2. Holding the collar in this position, press and hold the Test Button (Figure 1).
    6. The detector will recognize the test signal and the visible status indicator will flash red. The alarm relays will change state and the 4-20mA loop will rise to indicate an Alarm condition.
    7. While the Rotating Collar is rotated and Test Button pressed the Searchzone Sonik App will indicate the test signal as recognized. The LED status indicator will flash red.
    8. Release the Test Button and the Rotating Collar on the Hand Held Test Tool.
    9. Detector LED status indicator, relays and 4-20mA loop will return to default state.

Battery replacement **

**

WARNING
Do not mix battery types. Replace the batteries only with the types listed in the Specifications. The use of batteries other than those listed in the Specifications will invalidate the certification.
1. Use a hexagon socket key size 6 mm and rotate it counter-clockwise to loosen the end cap (Figure 3).
2. Slide the battery pack out of the Hand Held Test Tool (Figure 4).
3. Replace batteries in the pack. Refer to the Specifications for acceptable battery types. Position the negative battery terminals against the springs (Figure 5).
4. Slide the battery pack into the Hand Held Test Tool.
5. Gently rotate the battery pack clockwise/anticlockwise until it locates in the guide grooves and slide it fully into position. Incorrect position of the battery pack will not allow the end cap to be mounted back (Figure 6).
6. Replace the end cap and rotate clockwise. Use a hexagon socket key size 6 mm and tighten gently (Figure 7).

Specifications

Environmental -20°C to +50°C (-4°F to +122°F): 0 0/0 to 1000/0 RH condensing
Output Signals Test Signal 1 – 40 kHz , min. 96 dB SPL at 1 m

Test Signal 2 – 40 kHz , min. 96 dB SPL at 1 m
Signal Range| max. 10 m
Storage Temperature Range| +5°C to +30°C (+41°F to +86°F)
Internal Battery Cell| AAA type, primary cells, following types allowed only:

·   Duracell ID2400 IndustrialAAA cell
·   Duracell PC2400 Procell AAA cell
·   Duracell MN2400 Deluxe AAA cell
·   Duracell QU2400 Quantum AAA cell
·   Duracell MX2400 Ultrapower AAA cell
·   Duracell MN2400 Pluspower AAA cell

Battery Life| min. 100 tests per year for 5 years, starting with a new set of AAA primary cells
Weight| 668 g (1.47 lbs)
Dimensions| 100 mm x 150x 50 mm
Ingress Protection| IP 66
Compliance to Standards| EMC Directive RoHS
China RoHS
Safety Approvals| ATEX / IECEx – DEMK020ATEX2247 / IECExUL20.0043
112 G
Ex ia IICT4 Gb
Ta -20 °C to + 50 °C
cULus – E 465385
CI I, Div 1 Grps A, B, C, D T4
Class I Zn. 1 AEx is IIC T4
Ex is IIC T4
Ta -20 °C to + 50 °C

Find out more
www.honeywellanalytics.com
Contact Honeywell Analytics:
Europe, Middle East, Africa, India
Life Safety Distribution GmbH
Javastrasse 2
8604 Hegnau
Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
India Tel: +91 124 4752700
gasdetection@honeywell.com
Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069
USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com
Asia Pacific
Honeywell Analytics Asia Pacific
7F SangAm IT Tower
434 Worldcup Buk-ro,
Mapo-gu, Seoul 03922
Korea
Tel: +82-2-69090300
Fax: +82-2-69090328
analytics.ap@honeywell.com
Technical Services
EMEA: HAexpert@honeywell.com
US: HA.us.service@honeywell.com

Honeywell Hand Held Test Tool -ligo1

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation and you are strongly advised to obtain copies of the most recently issued regulations, standards and guidelines. This publication is not intended to form the basis of a contract.

07/20
2331M1305 Issue 1 ECO A05425
© 2020 Honeywell Analytics

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals