MITSUBISHI ELECTRIC 12000 BTU/H Wall Mounted Heat Pump System User Guide

June 7, 2024
Mitsubishi Electric

logo

MITSUBISHI ELECTRIC 12000 BTU/H Wall Mounted Heat Pump System

product

Indoor Unit: MSZ-GL12NAimage 1

Outdoor Unit:

  • MUZ-GL12NA-U1
  • MUZ-GL12NA-U2image 2

Wireless Remote Controllerimage 3

GENERAL FEATURES

  • Slim wall-mounted indoor units provide zone comfort control
  • The outdoor unit powers the indoor unit, and should a power outage occur, the system is automatically restarted when power returns
  • INVERTER-driven compressor and LEV provide high efficiency and comfort while using only the energy needed to maintain maximum performance
  • Multiple fan speed options: Quiet, Low, Medium, High, Super-high, Auto
  • Multiple control options available:
    • Hand-held Remote Controller (provided with unit)
    • kumo cloud® smart device app for remote access
    • Third-party interface options
    • Wired or wireless controllers
  • Quiet operation
  • Smart Set: recalls a preferred preset temperature setting at the touch of a button
  • Blue Fin anti-corrosion treatment applied to the outdoor unit heat exchanger for increased coil protection and longer life.

SPECIFICATIONS: MSZ-GL12NA & MUZ-GL12NA

Cooling1

| Maximum Capacity| BTU/H| 13,600
---|---|---|---
Rated Capacity| BTU/H| 12,000
Minimum Capacity| BTU/H| 1,500
Maximum Power Input| W| 1,300
Rated Power Input| W| 920
Moisture Removal| Pints/h| 2.5
Sensible Heat Factor| 0.77
Power Factor| %| 95 / 95

Heating at 47°F2

| Maximum Capacity| BTU/H| 18,100
Rated Capacity| BTU/H| 14,400
Minimum Capacity| BTU/H| 2,000
Maximum Power Input| W| 1,620
Rated Power Input| W| 1,100
Power Factor| %| 96 / 96

Heating at 17°F3

| Maximum Capacity| BTU/H| 12,000
Rated Capacity| BTU/H| 9,200
Maximum Power Input| W| 1,240
Rated Power Input| W| 870

Heating at 5°F4

| Maximum Capacity| BTU/H| 9,790
Maximum Power Input| W| 1,020
Heating at -4°F5| Maximum Capacity| BTU/H| 7,920

Efficiency

| SEER| 23.1
EER1| 13.0
HSPF (IV)| 12.5
COP at 47°F2| 3.84
COP at 17°F in Maximum Capacity3| 2.84
COP at 5°F in Maximum Capacity4| 2.81
ENERGY STAR® certified units (ENERGY STAR products are third-party certified by an EPA-recognized Certification Body.)| YES

Electrical

| Voltage, Phase, Frequency| 208/230V, 1 phase, 60Hz
Guaranteed Voltage Range| V AC| 187 – 253
Voltage: Indoor – Outdoor, S1-S2| V AC| 208 / 230
Voltage: Indoor – Outdoor, S2-S3| V DC| 24
Short-circuit Current Rating (SCCR)| kA| 5
Recommended Fuse/Breaker Size (Outdoor)| A| 15
Recommended Wire Size (Indoor – Outdoor)| AWG| 14

Indoor Unit

| MCA| A| 1
MOCP| A| 15
Blower Motor Full Load Amperage| A| 0.76
Blower Motor Output| W| 30
Airflow Rate at Cooling, Dry| CFM| 399-321-237-170-145

SPECIFICATIONS: MSZ-GL12NA & MUZ-GL12NA
  Airflow Rate at Cooling, Wet CFM 364-286-201-134-109
Airflow Rate at Heating, Dry CFM 406-321-237-170-145
Sound Pressure Level (Cooling) dB(A) 45-37-30-22-19
Sound Pressure Level (Heating) dB(A) 43-37-30-22-19
Drain Pipe Size In. (mm) 5/8 (15.88)
Heat Exchanger Type Plate fin coil
External Finish Color Munsell 1.0Y 9.2/0.2

Unit Dimensions

| W: In. (mm)| 31-7/16 (798)
D: In. (mm)| 9-1/8 (232)
H: In. (mm)| 11-5/8 (295)

Package Dimensions

| W: In. (mm)| 33-1/2 (850)
D: In. (mm)| 12 (300)
H: In. (mm)| 14 (350)
Unit Weight| Lbs. (kg)| 22 (10)
Package Weight| Lbs. (kg)| 26 (11.5)
Indoor Unit Operating Temperature Range| Cooling Intake Air Temp (Maximum / Minimum)*| °F| 90 DB, 73 WB / 67 DB, 57 WB
Heating Intake Air Temp (Maximum / Minimum)| °F| 80 DB / 70 DB

Outdoor Unit

| MCA| A| 9
MOCP| A| 15
Fan Motor Full Load Amperage| A| 0.5
Fan Motor Output| W| 55
Airflow Rate| CFM| 1,229 / 1,172
Refrigerant Control| LEV
Defrost Method| Reverse cycle
Heat Exchanger Type| Plate fin coil
Sound Pressure Level, Cooling1| dB(A)| 49
Sound Pressure Level, Heating2| dB(A)| 51
Compressor Type| DC INVERTER-driven
Compressor Model| SNB092FQAMT
Compressor Rated Load Amps| A| 6.6
Compressor Locked Rotor Amps| A| 8.2
Compressor Oil Type // Charge| oz.| FV50S // 11.8
External Finish Color| Munsell 3Y 7.8/1/1
Base Pan Heater| Optional

Unit Dimensions

| W: In. (mm)| 31-1/3 (800)
D: In. (mm)| 11-1/5 (285)
H: In. (mm)| 21-5/9 (550)

Package Dimensions

| W: In. (mm)| 37 (940)
D: In. (mm)| 14-15/16 (380)
H: In. (mm)| 24-13/16 (630)
Unit Weight| Lbs. (kg)| 81 (37)

SPECIFICATIONS: MSZ-GL12NA & MUZ-GL12NA
  Package Weight Lbs. (kg) 89 (40)

Outdoor Unit Operating Temperature Range

| Cooling Air Temp (Maximum / Minimum)*| °F| 115 / 14
Cooling Thermal Lock-out / Re-start Temperatures| °F| -1 / 3
Heating Air Temp (Maximum / Minimum)| °F| 75 / -4
Heating Thermal Lock-out / Re-start Temperatures
| °F| -9 / -4

Refrigerant

| Type| R410A
Charge| Lbs, oz| 2, 9

Piping

| Gas Pipe Size O.D. (Flared)| In. (mm)| 3/8 (9.52)
Liquid Pipe Size O.D. (Flared)| In. (mm)| 1/4 (6.35)
Maximum Piping Length| Ft. (m)| 65 (20)
Maximum Height Difference| Ft. (m)| 40 (12)
Maximum Number of Bends| 10

Notes

AHRI Rated Conditions (Rated data is determined at a fixed compressor speed)| 1Cooling (Indoor // Outdoor)| °F| 80 DB, 67 WB // 95 DB, 75 WB
---|---|---|---
2Heating at 47°F (Indoor // Outdoor)| °F| 70 DB, 60 WB // 47 DB, 43 WB
3Heating at 17°F (Indoor // Outdoor)| °F| 70 DB, 60 WB // 17 DB, 15 WB

Conditions

| 4Heating at 5°F (Indoor // Outdoor)| °F| 70 DB, 60 WB // 5 DB, 4 WB
5Heating at -4°F (Indoor // Outdoor)| °F| 70 DB, 60 WB // -4 DB, -5 WB
*Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.

**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.

ACCESSORIES: MSZ-GL12NA

Anti-allergy Enzyme Filter □ MAC-408FT-E
kumo touch™ RedLINK™ Wireless Controller □ MHK2
Deluxe MA Remote Controller1 □ PAR-40MAAU
Simple MA Controller1 □ PAC-YT53CRAU-J
Touch MA Controller1 □ PAR-CT01MAU-SB
Wired Remote Sensor □ M21-EAA-307
Wireless Temperature and Humidity Sensor □ PAC-USWHS003-TH-1
System Control Interface2 □ MAC-334IF-E
Wireless Interface 2 □ PAC-USWHS002-WF-2
Thermostat Interface □ PAC-US444CN-1
kumo station® □ PAC-WHS01HC-E
USNAP Interface □ PAC-WHS01UP-E
IT Extender □ PAC-WHS01IE-E
BACnet® and MODBUS® Interface □ PAC-UKPRC001-CN-1
Lockdown Bracket for Hand-held Remote Controllers □ RCMKP1CB
Blue Diamond Sensor Extension Cable — 15 Ft. □ C13-103
Blue Diamond Alarm Extension Cable — 6.5 Ft. □ C13-192
Blue Diamond MultiTank — collection tank for use with multiple pumps

C21-014
Blue Diamond Rubber Foot Pads| □ F10-010
Mini Condensate Pump — 230 volt application| □ SI30-230
MegaBlue Advanced Blue Diamond Condensate Pump w/ Reservoir & Sensor| □ X87-835 – 110 to 250V
MaxiBlue Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (110V) up to 48,000 BTU/ H[recommended]| □ X87-711 – 110V
Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended]| □ X87-721 – 208/230V
MicroBlue Blue Diamond Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H| □ X85-003
Fascia Kit for MicroBlue Pump – mounts the MicroBlue and sensor directly beneath the indoor unit| □ T18-016
Drain Pan Level Sensor| □ SS610E
(30A/600V/UL) [fits 2″ X 4″ utility box] – Black| □ TAZ-MS303
(30A/600V/UL) [fits 2″ X 4″ utility box] – White| □ TAZ-MS303W

ACCESSORIES: MUZ-GL12NA

Air Outlet Guide □ MAC-881SG
Drain Socket □ MAC-860DS
Optional Defrost Heater □ MAC-640BH-U
Hail Guard □ HG-B4
Outdoor Unit 3-1/4 inch Mounting Base (Pair) – Plastic □ DSD-400P
Condensing Unit Mounting Pad 16″ x 36″ x 3″ □ ULTRILITE1
Outdoor Unit Stand — 12″ High □ QSMS1201M
Outdoor Unit Stand — 18″ High □ QSMS1801M
Outdoor Unit Stand — 24″ High □ QSMS2401M
Heavy Duty Wall Mounting Bracket— Coated Steel □ QSWB2000M-1
Heavy Duty Wall Mounting Bracket — 316 Series Stainless Steel □ QSWBSS
15′ x 1/4″ x 15′ / 3/8″ Lineset (Twin-Tube Insulation) □ MLS143812T-15
30′ x 1/4″ x 30′ / 3/8″ Lineset (Twin-Tube Insulation) □ MLS143812T-30
50′ x 1/4″ x 50′ / 3/8″ Lineset (Twin-Tube Insulation) □ MLS143812T-50
65′ x 1/4″ x 65′ / 3/8″ Lineset (Twin-Tube Insulation) □ MLS143812T-65

DIMENSIONS: MSZ-GL12NAimage 4

DIMENSIONS: MUZ-GL12NAimage 5 image
6

FORM# MSZ-GL12NA / MUZ-GL12NA – 202003
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
1340 Satellite Boulevard, Suwanee, GA 30024
Toll Free: 800-433-4822 www.mehvac.comlogo