Onset T-VER-E50B2 Compact Power and Energy Meter Installation Guide
- June 6, 2024
- Onset
Table of Contents
T-VER-E50B2 Compact Power and Energy Meter
Test Equipment Depot – 800.517.8431 – 99 Washington Street Melrose, MA 02176 – TestEquipmentDepot.com
T-VER-E50B2
Compact Power and Energy Meter
Quick Install Guide Z205881-0D
For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with the environment. Installation category: CAT II or CAT III
Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired.
Additional Resources:
FCC PART 15 INFORMATION Note: This equipment has been tested by the
manufacturer and found
to comply with the limits for a class B digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when this equipment is operated in a residential
environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area may cause harmful interference in which
case the user will be required to correct the interference at his own expense.
Modifications to this product without the express authorization of Veris
Industries nullify this statement.
This symbol indicates an electrical shock hazard exists.
Documentation must be consulted where this symbol is used on this product.
INSTALLATION
Disconnect power prior to installation.
Any covers that may be displaced during the installation must be reinstalled before powering the unit.
Mount the meter in an appropriate electrical enclosure near equipment to be
monitored.
Do not install on the load side of a Variable Frequency Drive (VFD).
The meter can be mounted in two ways: on standard 35 mm DIN rail or screw-
mounted to the back of the enclosure.
A. DIN Rail Mounting 1. Attach mounting clips to the underside of the housing
by sliding them into the slots from the inside. The stopping pegs must face
the housing, and the outside edge of the clip must be flush with the outside
edge of the housing. 2. Snap the clips onto the DIN rail. See diagram of the
underside of the meter. 3. To prevent horizontal shifting across the DIN rail,
use two end stop clips.
B. Screw Mounting 1. Attach the mounting clips to the underside of the housing by sliding them the slots from the outside. The stopping must face the housing, and the screw must be exposed on the outside of the housing. 2. Use three #8 screws (not supplied) to the meter to the back of the enclosure. diagram of the underside of the meter.
into pegs hole
mount See
Page 2
SUPPORTED SYSTEM TYPES
The meter has a number of different possible system wiring configurations (see
Wiring Diagrams, page 9-10). To configure the meter, set the System Type via
the User Interface. The System Type tells the meter which of its current and
voltage inputs are valid, which are to be ignored, and if neutral is
connected. Setting the correct System Type prevents unwanted energy
accumulation on unused inputs, selects the formula to calculate the
Theoretical Maximum System Power, and determines which phase loss algorithm is
to be used. The phase loss algorithm is configured as a percent of the Line-
to-Line System Voltage (except when in System Type 1L + 1n) and also
calculates the expected Line to Neutral voltages for system types that have
Neutral (2L + 1N and 3L + 1n).
Values that are not valid in a particular System Type will display as “—-” on
the User Interface.
No. of wires 2 2 3
3
4
CTs Qty ID
1
A
1
A
2
A,
B
3
A,
B,
C
3
A,
B,
C
Voltage Connections Qty ID Type
2
A, L-N
N
2
A, L-L
B
3
A, L-L with
B, N
N
3
A, Delta
B,
C
4
A, Ground-
B, ed Wye
C,
N
System Type User Interface: SETUP>S SYS 1L + 1n
2L
2L + 1n
3L
3L + 1n
Phase Loss Measurements VLL VLN Balance
AN
AB
AB AN, AN, BN BN
AB,
AB, BC,
BC,
CA
CA
AB, AN, AN, BN,
BC, BN, CN &
CA CN AB, BC,
CA
Wiring Diagram Diagram Number
1 2 3
4
5, 6
Page 5
Page 6
SPECIFICATIONS
Measurement Accuracy: Real Power and Energy
IEC 62053-22 Class 0.5S, ANSI C12.20 0.5%
Input Voltage Characteristics: Measured AC Voltage
Impedance
Minimum 90VL-N (156VL-L) for stated accuracy
UL Maximums: 600VL-L (347VL-N) CE Maximums: 300VL-N (520V L-L)
2.5 M (L-N)/5 M (L-L)
Frequency Range
45 to 65 Hz
Input Current Characteristics: Measurement Input Range
Impedance
0 to 0.333VAC or 0 to 1.0VAC (+20% over-range) 10.6k (1/3 V mode) or 32.1k (1 V mode)
Control Power: AC
DC*
5VA max.; Minimum 90VAC, UL Maximums: 600VL-L (347VL-N), CE Maximums: 300VL-N
(520V L-L)
3W max.; UL and CE: 125 to 300VDC
Ride Through Time
100 msec at 120VAC
Mechanical Characteristics: IP Degree of Protection (IEC 60529)
IP40 front display; IP20 Meter
Terminal Block Screw Torque
0.37 ft·lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) max.
Terminal Block Wire Size
26 to 14 AWG (0.13 to 2.08 mm2)
Rail
T35 (35mm) DIN Rail per EN50022
Environmental Conditions: Operating Temperature
-30° to 70°C
Storage Temperature
-40° to 85°C
Humidity Range
<95% RH (non-condensing)
Altitude of Operation
3 km max.
Metering Category: North America
CAT III; for distribution systems up to 347 V L-N/600VAC L-L
CE
CAT III; for distribution systems up to 300 V L-N
Dielectric Withstand
Per UL 508, EN61010
Conducted and Radiated Emissions
FCC part 15 Class B, EN55011/EN61000 Class B (residential and light industrial)
Conducted and Radiated Immunity
EN61000 Class A (heavy industrial)
Safety: North America (cULus)
UL508 (open type device)/CSA 22.2 No. 14-05
Europe (CE)
EN61010-1:2001
- External DC current limiting is required, see fuse recommendations.
Page 3
To avoid distortion, use parallel wires for control power and voltage inputs. The following symbols are used in the wiring diagrams on the following pages.
Symbol
Description Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No fuses are included with the meter.) Earth ground
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect
circuit breaker. The protection device must be rated for the available short-
circuit current at the connection point.
Page 7
DIMENSIONS
Housing
Bottom View (DIN Mount Configuration)
Bottom View (Screw Mount Configuration)
Page 4
PRODUCT DIAGRAM
Page 8
WIRING DIAGRAMS
Diagram 3: 1-Phase Direct Voltage Connection 2 CT
SYSTEM TYPE 2L + 1n
Diagram 4: 3-Phase 3-Wire System 3 CT no PT
SYSTEM TYPE 3L
CONTROL POWER
Direct Connect Control Power Line to Line (L-L)
Direct Connect Control Power Line to Neutral (L-N)
CTs are not polarity sensitive. No need to observe orientation.
Diagram 1: 1-Phase Line-to-Neutral 2-Wire System 1 CT
SYSTEM TYPE 1L + 1n
Diagram 2: 1-Phase Line-to-Line 2-Wire System 1 CT
SYSTEM TYPE 2L
Diagram 5: 3-Phase 4-Wire Wye Direct Voltage
Input Connection 3 CT
SYSTEM TYPE 3L + 1n
Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT 3 PT
SYSTEM TYPE 3L + 1n
Line to Line from 90VAC to 600VAC (UL) (520VAC for CE). In UL installations,
the lines may be floating (such as a delta). If any lines are tied to an earth
(such as a corner grounded delta), see the Line to Neutral installation
limits. In CE compliant installations, the lines must be neutral (earth)
referenced at less than 300VACL-N
Direct Connect Control Power DC
Line to Neutral from 90VAC to 347 VAC (UL) or 300VAC (CE)
Control PowerTransformers (CPT) Connection
Page 9
DISPLAY SCREEN DIAGRAM
Page 10
SETUP INSTRUCTIONS
These instructions assume the meter is set to factory defaults. If it has been
previously configured, all optional values should be checked.
1. Press or repeatedly until SETUP screen appears.
2. to the PASWD screen.
3. through the digits. Use or to select the password (the default is 00000). Exit the screen to the right.
4. to the S CT (Set Current Transducer) screen.
a. to the CT V screen. Use or to select the voltage mode Current Transducer output voltage.
b. to the CT SZ screen and through the digits. Use or to select the CT size in
amps.
c. back to the S CT screen.
5. to the S SYS (Set System) screen.
a. to the SYSTM screen. Use or wiring diagrams on pages 910).
b. back to the S SYS screen.
to select the System Type (see
6. (Optional) to the S PT (Set Potential Transformer) screen. If PTs are not used, then skip this step.
a. to the RATIO screen and through the digits. Use or to select the Potential
Transformer step down ratio.
b. back to the S PT screen.
DC Control Power from 125VDC to 300VDC (UL and CE The Control Power Transformer may be wired L-N
max.)
or L-L. Output to meet meter input requirements.
Fuse Recommendations:
Keep the fuses close to the power source (obey local and national code
requirements). For selecting fuses and circuit breakers, use the following
criteria: · Current interrupt capacity should be selected based on the
installation category and fault
current capability. · Over-current protection should be selected with a time
delay. · The voltage rating should be sufficient for the input voltage
applied. · Provide overcurrent protection and disconnecting means to protect
the wiring. For DC
installations, the installer must provide external circuit protection
(suggested: 0.5 A time delay fuses).
· The earth connection is required for electromagnetic compatibility (EMC) and
is not a protective earth ground.
Page 11
7. to the S PWR (Set System Power) screen. a. to the MX MW screen, which
displays the calculated Maximum System Power for your reference. b. back to
the S PWR screen.
8. to the S PULS (Set Pulse) screen to set the scaling factors for Wh, VARh,
and mAh.
a. to Wh/P screen. Use or to set the Wh and VARh per pulse (the default is 1).
b. to mAh/P screen. Use or to set the mAh per pulse (the default is 10).
c. to the mS/P screen, which displays the Pulse Duration Time for your
reference (use 10 mS/P for HOBO products).
d. back to the S PULS screen.
9. Use to exit the setup screen and then SETUP. 10. Check that the wrench is
not displayed on the LCD.
a. If the wrench is displayed, use or to find the ALERT screen. b. through the
screens to see which alert is on.
For full setup instructions, see the T-VER-E50B2 Full Installation Guide
available on onsetcomp.com.
CONNECTING TO THE T-VER-E50B2
The T-VER-E50B2 has three outputs. These outputs can be connected to HOBO loggers as shown below.
Terminal block wire range: 12-24 AWG
T-VER-E50B2
Blk
Ah
Wht to input 3
Blk
input 1
Wht
Blk
1
input 2
Wht
2 3
Blk
4
input 3
Wht
Ch 4 not used
Blk
Wh
Wht to input 2
CABLE-2.5-STEREO*
VARh
Blk Wht to input 1 NC
input 1, 2, or 3 Connect to any open pulse port
S-UCC-M00x
input 1, 2, or 3*
Connect to any open Smart Sensor jack
- With ZW, one CABLE-2.5-STEREO is required for each T-VER-E50B2 pulse output channel (VARh, Wh, Ah) to be monitored. With H21, H22, and U30, one S-UCC-M00x is required for each channel.
HOBO UX120-017 Data Logger
HOBO ZW Wireless Data Node
(with pulse input)
HOBO H21, H22, or U30 Series Data Logger (H22-001 shown)
Notes when connecting to non-HOBO® devices:
· The T-VER-E50B2 has solid-state outputs rated for 30VAC/DC nom. · VARh and
Wh are normally open; Ah is normally closed. · Maximum load current is 100mA
at 25°C. Derate 0.56mA per °C above 25°C (e.g.
86mA@50°C). · The over-current protective device must be rated for the short
circuit current at the
connection point. · Pulse outputs are only intended to be connected to non-
hazardous voltage circuits
(SELV or Class 2). Do not connect to hazardous voltages.
Page 12
CHINA ROHS COMPLIANCE INFORMATION (EFUP TABLE)
© 20112013 Veris Industries and Onset Computer Corporation. Veris and the
Veris “V” logo are trademarks or registered trademarks of Veris Industries,
L.L.C. in the USA and/or other countries. Onset and HOBO are registered
trademarks of Onset Computer Corporation.
14708-D MAN-VERIS-E50B2
Page 13
Page 14
Page 15
Page 16
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>