IOTA IIS Single Phase Central Inverters User Guide

June 3, 2024
IOTA

Table of Contents

IOTA IIS Single Phase Central Inverters User Guide
IOTA IIS Single Phase Central Inverters

Explore the available options for IIS Central Inverters to design the perfect emergency lighting inverter solution for your unique application.
Note: not all options are available for each model. See Table 1 on page 13 to quickly determine option availability per model, or consult individual specification sheets..

5YR – Five Year Extended Warranty

Provides additional warranty coverage up to a total of five years on electronic components. See iotaengineering.com for full warranty details. Batteries are covered under a separate pro-rated warranty. Available in the continental U.S. only. Requires factory startup (see FSREG#) to be ordered.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, and IIS3P EXT models

BACIP – BACnet IP Interface

Equips the IIS Inverter System with an RJ-45 Ethernet port for remote communications to a Building Management System (BMS) via the BACnet IP protocol. The BACnet IP interface supports standard IP network settings (DHCP or static IP address, subnet mask, default gateway and programmable port number) and has a programmable system-wide Device Instance number. This BACnet IP interface provides read-only access to the following telemetry about the IIS Inverter System:

  • Input Voltage(s)
  • Output Voltage(s)
  • Output Current(s)
  • Total Output Power
  • Ambient Temperature
  • Battery Voltage
  • Battery Current
  • Total Time on Battery (in Emergency Mode)
  • Days of Operation
  • Results of the Inverter’s last automatic monthly self-test
  • Results of the inverter’s last automatic yearly self-test
  • Alarm states including no utility, on battery, battery low, input voltage high/low, inverter failure detected, inverter overloaded and overload shutdown, ‘load reduction’ activated, ambient temperature high, and battery charger fault.

BACnet IP Interface

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

BACNET – BACnet MS/TP Interface

Equips the IIS Inverter System with an RS-485 serial port for remote communications to a Building Management System (BMS) via the BACnet MS/TP protocol. The BACnet interface supports standard baud rates (9600, 19200, 38400, 57600, 115200) and MAC addressing (0-127), and has a programmable system-wide Device Instance number. The BACnet interface supports standard BACnet discovery and provides read-only access to the following telemetry about the IIS Inverter System:

  •  Input Voltage(s)
  • Output Voltage(s)
  • Output Current(s)
  • Total Output Power
  • Ambient Temperature
  • Battery Voltage
  • Battery Current
  • Total Time on Battery (in Emergency Mode)
  • Days of Operation
  • Results of the Inverter’s last automatic monthly self-test
  • Results of the inverter’s last automatic yearly self-test
  • Alarm states including no utility, on battery, battery low, input voltage high/low, inverter failure detected, inverter overloaded and overload shutdown, ‘load reduction’ activated, ambient temperature high, and battery charger fault
  • Event logs, alarm logs, and test logs as text files downloadable via BACnet file transfer

BACnet MS/TP Interface

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models

BATINST – Battery Installation by Factory Certified Technician

Provides expert battery installation done by a certified IIS Inverter Technician. The IIS Technician will come to the job site to conduct final installation of your IIS Inverter System’s batteries and test their operation. The IIS Inverter must already be physically installed in its final operating location before the technician arrives and all conduit/wiring must be extended to the IIS Inverter System. See iotaengineering.com for more details on how to order/schedule battery installation. Available in the continental U.S. only. Requires factory startup (see FSREG#) to be ordered.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, and IIS3P EXT models.

BFAN – Battery Cabinet Fan

The IIS Inverter battery cabinet(s) are equipped with a fan (one per battery cabinet) for additional airflow and ventilation.
Available on IIS3P and IISCN3P models.

BLOCK(#) – Output Breaker Locks

Provides lock tabs on the output circuit breakers to prevent unauthorized personnel from tampering with the breaker positions. The breaker locks can either be configured to “lock on” (ie: the lock must be removed to open the breaker and  remove power to the emergency circuit) or “lock off” (ie: the lock must be removed to  close the breaker which is useful to prevent the breakers from accidentally being closed, and thus energizing the circuit, during maintenance).

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P and IIS3P EXT models.

BTM – Battery Temperature Monitor

Includes a Battery Temperature Monitor with Shunt Trip DC breaker(s) (1 breaker per battery string). The BTM monitors  the batteries for over- temperature or thermal runaway conditions and trips the batterystring DC breaker if over-temperature/thermal runaway conditions exist. Includes a Form C Dry Contact to connect to a Fire Alarm Panel for remote alarm signaling. Additionally, the IIS Inverter is outfitted with an external Exhaust Fan Monitoring System that can interface with a “state of health” dry contact input on an external exhaust fan. The IIS Inverter will monitor the “state of health” dry contact input and, if the exhaust fan is in an alarm condition and the normally open contact is closed, a signal is sent to the IIS Emergency Inverter to stop charging the batteries.

Requires factory startup (see FSREG#, FSCAN, FSMEX) to be ordered. This option is required in California when the IIS Inverter System has more than 50 gallons of electrolytes or more (applies to 16.7VA through 50000VA single and three phase models).

Available on IIS Single Phase, IIS3P, and IISCN3P models

BYPASSBBM – Internal Maintenance Bypass (Break Before Make)

Includes a Maintenance Bypass Switch that is mounted inside the IIS Inverter System. This device allows maintenance personnel to route power from the AC utility directly to the output circuit breakers, bypassing the inverter electronics. The switch isolates the system to perform routine maintenance or servicing while allowing the lighting load to remain in normal operation. The “break before make” switch disconnects the power inside the inverter immediately before it makes the direct electrical connection from the AC utility to the output circuit breakers. Requires output circuit breakers. If output circuit breakers are not desired, an External Maintenance Bypass may be available (see EXTPASS).
BYPASS

Available on IIS Single Phase and IISC models. This feature is standard with IIS3P and IISCN3P models.

BYPASSBBM – Internal Maintenance Bypass (Break Before Make)

Includes a Maintenance Bypass Switch that is mounted inside the IIS Inverter System. This device allows maintenance personnel to route power from the AC utility directly to the output circuit breakers, bypassing the inverter electronics. The switch isolates the system to perform routine maintenance or servicing while allowing the lighting load to remain in normal operation. The “break before make” switch disconnects the power inside the inverter immediately before it makes the direct electrical connection from the AC utility to the output circuit breakers. Requires output circuit breakers. If output circuit breakers are not desired, an External Maintenance Bypass may be available (see EXTPASS). Available on IIS Single Phase, IISC, IIS3P, and IISCN3P models.

DR – Dimming Relay

Allows a 0-10V dimming signal to reach interfacing emergency luminaires during normal power conditions and will interrupt the 0-10V dimming signal if a power loss is detected. This will cause the emergency luminaires to operate at full light output in power loss conditions regardless of the position of a 0-10V dimming control. Note: the usefulness of on-board dimming relays is limited in large applications with multiple circuit breakers since this only allows for a single dimming control to be employed for each output circuit. Consider using an ALCR device such as the IOTA ETS DR in these scenarios.

Available on IIS 1100 and IISCN models.

DRIP – NEMA 2 Drip Top

Provides a NEMA 2 drip top shield to protect the electronics and batteries from falling or splashing water. Typically one NEMA 2 Drip Top is required per electronics and battery cabinet. Note: this option is NOT intended for use outdoors and will NOT allow indoor rated inverters to be suitable for outdoor applications.

Available on IIS 1100, IIS Single Phase, IISC, IIS3P, IISCN and IISCN3P models.

EMD – Enhanced Metering and Programming Display

Outfits IISCN models with a meter panel and keypad display that enables additional metering and programming functions. This option allows users to view data on system and alarm status as well as the results of automatic life safety tests. The EMD option also allows users to program the date, time, and duration of automatic monthly and annual tests as well as configure set-points for summary alarm contacts. Available on IISCN models.

EXTPASS – External Maintenance Bypass (Make Before Break)

Equips the Emergency Inverter with a maintenance bypass switch mounted exterior to the unit in a NEMA 1 enclosurewith a hinged door measuring 20” high x 16” wide x 9” deep. This device allows maintenance personnel to route power from the AC utility directly to the lighting load, bypassing the inverter electronics. The switch isolates the system to perform routine maintenance or servicing while allowing the lighting load to remain in normal operation. The “make before break” switch shorts the direct electrical connection from the AC utility to the lighting load immediately before power is disconnected inside the inverter. This option cannot be used in conjunction with more than one output circuit breaker and, if a single output circuit breaker is used, it must be sized for the total system current.

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, and IISCN3P models.

FASTCHG – Fast Charge, Battery Charger Upgrade

Upgrades the battery charger on the IIS Inverter System to decrease the time it  takes to recharge a fully discharged battery bank to full capacity from the standard 24-hour period to a 12-hour period.

Available on IIS 1100, IIS Single Phase, IIS EXT (excluding 1750), IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

FLOOR – Floor Mount Bracket

Provides a bracket for securing the IIS Inverter System to the floor. This option will add anywhere from 2.7” to 5” to the total system height depending on model (see individual specification sheets for more details).

FLOOR

Available on IIS 1100, IISC, and IISCN models.

FLRMOUNT – Floor Mount Base

Provides a base that is factory-installed to the bottom of the IIS EXT 1750 for mounting to the floor.

Available on IIS EXT 1750 models.

FLRMOUNT – Floor Mount Base

Provides a base that is factory-installed to the bottom of the IIS EXT 1750 for mounting to the floor.

Available on IIS EXT 1750 models.

FLRSTRP – Floor Mount Bracket and Battery Strapping

Includes options “FLOOR” and “STRAP.” Provides a floor mount bracket to secure the IIS Inverter System to the floor and battery strapping to contain the batteries within the system.

Available on IIS 1100 and IISCN models

FSREG(#), FSCAN, FSMEX – Factory Startup

Factory startup provides the confidence and reliability of expert installation on IIS Inverter Systems. A qualified IIS technician will visit the job site to oversee the startup and initial testing of the IIS Inverter to ensure it performs to factory specifications. Should any problems be detected, the IIS Technician will take corrective action to repair the affected components. See iotaengineering.com for more information about what is included in Factory Startup.

Must be scheduled with the factory at least two weeks out from when the unit has been received at the job site. The IIS Inverter must already be physically installed in its final operating location before the technician arrives and all conduit/wiring must be extended to the IIS Inverter System. Note: system should not be energized before the IIS Inverter technician arrives.

Purchasing IIS Inverter Factory startup provides an additional year of Warranty coverage on all electronic components, provided Factory Startup occurs within 180 days of ship date. Note: the additional warranty provided by Factory Startup does not apply to Canada (FSCAN), Mexico (FSMEX), Hawaii and Alaska (FSREG13), or anywhere outside the continental USA.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

FT – Fast Transfer

IIS Single Phase FT (Fast Transfer) models will transfer to battery power (emergency mode) when AC utility power is interrupted for less than 2ms. This allows IIS Single Phase FT models to be compatible with any lighting type including LED, Fluorescent, Incandescent, Quartz and HID lamps in addition to motor loads. IIS Single Phase FT models feature a line interactive design to eliminate excessive transfers to battery power, and are considered “uninterruptable.”

Available on IIS Single Phase models.

IDC – Inverter On, On Utility, On Battery Dry Form C Contact

Provides Dry Form C Contacts that will change state when the IIS Inverter System transfers from AC utility to battery power (emergency mode). These Form C Contacts are rated at 5 amps maximum at 250VAC/30VDC. These contacts can be used to provide a continuity path to an external monitoring device (not provided), such as a Building ManagementSystem (BMS) or Indicator Panel for remote monitoring of the IIS Inverter’s operating mode.

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, and IISCN3P models.

IRTEST – Infrared Remote Test

Provides a method to manually trigger an Inverter self-test via a laser remote (remote included).

Available on IIS 1100 and IISCN models

KEYPAD – Keypad and Display Panel (IIS EXT 1750 only)

Includes with the IIS EXT 1750 a 4 x 20 vacuum fluorescent display and a 4-button keypad that allows users to view alarm, test, and operating data about the IIS EXT 1750 and set test and alarm parameters. The KEYPAD option is used for system setup and status and is recommended to order one KEYPAD per site. The KEYPAD option allows users to view the following telemetry about the IIS Inverter System.

  • Input Voltage
  • Output Voltage
  • Output Current
  • Battery Voltage
  • Battery Current
  • Battery Temperature
  • Ambient (Internal) Temperature
  • Total Time on Battery (in Emergency Mode)
  • Days of Operation
  • VA Output
  • Battery DC Watts (total battery wattage the inverter is processing)
  • Results of the Inverter’s last automatic monthly self-test
  • Results of the inverter’s last automatic yearly self-test
  • Alarm states including High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction Fault, Output Overload, High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output Fault
    KEYPAD

Available on IIS EXT 1750 models

LBT – Load Bank Test

As part of the Factory Startup and Testing Process an IIS Inverter technician will perform a full-load test IIS Inverter System to ensure that it is ready for emergency operation. This option is useful in situations where the total emergency lighting load isn’t present at time of Inverter Startup, but a full- load test is desired. Available in the continental U.S. only. Requires factory startup (see FSREG#) to be ordered.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, and IIS3P EXT models

LCR – Load Control Relay

Equips the IIS Inverter with a relay used to bypass an ON/OFF control (such as a wall switch or occupancy sensor). Note: the usefulness of the on-board load control relay is limited in large applications with multiple circuit breakers since this only allows for a single ON/OFF control to be employed for each output circuit. Consider using an ALCR device such as the IOTA ETS DR in these scenarios. Requires at least one output  circuitbreaker.

Available on IIS Single Phase, IISC, and IIS3P models.

LFILTER – TVSS Line Filter

Protects the emergency inverter against short duration, excessive voltage spikes (such as lightening strikes) on the utility line. The filter module is a two-stage protection unit utilizing a Low-Q Pi Filter as well as secondary MOV protection. The module provides filtering of line harmonics and high frequency noise.

Available on IIS 1100 models.

LFILTER Ratings

Noise Rejection: -10db @ 1kHz and -50db @ 1Mhz at full load
Initial Clamp Voltage: 560 VAC, L-N, L-G, N-G
Maximum Clamp Voltage: 1060 VAC, 100A
Primary Protection L-N: 320J
Primary Protection L-G, N-G: 320J
Thermal fusing on all MOV’s

MDC – Status Monitoring Dry Form C Contacts

Equips the IIS Inverter System with a series of Dry Form “C” contacts that are pre-configured to various indicators on Inverter status. These contacts will change state when their associated Inverter state is triggered. For example, if the IIS Inverter System detects a high temperature fault, the high temperature Status Monitoring Contact will change state. These contacts can be connected to an external panel (see “MDCP” option) or indicator (not provided) for external monitoring of the IIS Inverter’s alarm status.

**IIS 1100*** All Other Models
A.C. Utility Present A.C. Utility Present
Test Failure On Bypass**
System Overload High Temperature Alarm
Near Low Battery Summary Fault
Inverter On (Emergency Mode) Inverter On (Emergency Mode)
Blown Fuse Indicator Inverter Off

Available on IIS 1100, IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

MDCP – Status Monitoring Dry Form C Contacts with Remote Status Panel

Includes the MDC option (see MDC section for more details) and an additional remote status panel and alarm silence switch that will display alarms based on the state of the Status Monitoring Dry Form C Contacts. This allows users to remotely monitor Inverter status and silence alarms.

Available on IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, and IISCN3P models.

MODBUSIP – MODBUS TCP Interface

Equips the IIS Inverter System with an RJ-45 Ethernet port for remote communications to a Building Management System (BMS) via the MODBUS TCP protocol. The MODBUS TCP interface supports standard IP network settings (DHCP or static IP address, subnet mask, default gateway, and programmable port number). The MODBUS TCP interface provides read-only access to the following telemetry about the IIS Inverter System:

  • Input Voltage(s)
  • Output Voltage(s)
  • Output Current(s)
  • Total Output Power
  • Ambient Temperature
  • Battery Voltage
  • Battery Current
  • Total Time on Battery (in Emergency Mode)
  • Days of Operation
  • Results of the Inverter’s last automatic monthly self-test
  • Results of the inverter’s last automatic yearly self-test
  • Alarm states including no utility, on battery, battery low, input voltage high/low, inverter failure detected, inverter overloaded and overload shutdown, ‘load reduction’ activated, ambient temperature high, and battery charger fault
    MODBUSIP

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models

MODBUSRTU – MODBUS Serial (RTU or ASCII) Interface

Equips the IIS Inverter System with an RS-485 serial port for remote communications to a Building Management System (BMS) via the MODBUS RTU or MODBUS ASCII protocol (selectable). The MODBUS Serial interface supports standard baud rates (9600, 19200, 38400, 115200), parity (no parity or even parity) and device addressing (1-247). The MODBUS Serialinterface supports setting a custom Device/User ID string (via Function Code 0x15) and retrieving it (via Function Code 0x11 – Report Server ID – or Function Codes 0x2B/0x0E – Encapsulated Interface Transport ‘Read Device Identification’). The MODBUS Serial interface provides read-only access to the following telemetry about the IIS Inverter System (via MODBUS Function Codes 0x01 through 0x04, and 0x14 for retrieving log files):

  • Input Voltage(s)
  • Output Voltage(s)
  • Output Current(s)
  • Total Output Power
  • Ambient Temperature
  • Battery Voltage
  • Battery Current
  • Total Time on Battery (in Emergency Mode)
  • Days of Operation
  • Results of the Inverter’s last automatic monthly self-test
  • Results of the inverter’s last automatic yearly self-test
  • Alarm states including no utility, on battery, battery low, input voltage high/low, inverter failure detected, inverter overloaded and overload shutdown, ‘load reduction’ activated, ambient temperature high, and battery charger fault
  • Event logs, Alarm logs and Test logs, as text files downloadable via MODBUS Read File Record function code 0x14
    MODBUSRTU

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

OBSHUNT – Main Output Breaker with Shunt Trip

Outfits the IIS Inverter System with a main output circuit breaker (63A, 1-pole, Normally On @ 120VAC) that includes a shunt trip that can be used to temporarily disable the inverter output. The shunt trip requires input from a momentary, normally-open switch (such as those found in a Fire Lock Box) to activate. When activated, the inverter output is disabled, but the system is still energized. It is recommended that this option is only used in cases where access to the shunt trip feature is controlled by the Fire Department. Consult local codes before ordering.

Available on IIS Single Phase, IISC, and IIS3P models.

OTA – Output Breaker Trip Alarm

Equips optional output distribution circuit breakers on the IIS Inverter System with an audible and visual alarm that activates with the circuit breaker is open or has tripped. If the system includes a display panel, the output circuit breaker trip alarms will also cause an alarm-state notification to appear on the display panel when a circuit breaker has tripped. Thisoption is especially useful with normally-off breakers since normally-off breakers don’t provide a visual indication that they have been tripped.

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, and IISCN3P models

OTDELAY – Output Transfer Delay to Emergency

This option causes the IIS Inverter System to delay the transfer from normal operation (AC utility power) to emergency operation (battery power) and vice versa. When power is lost, the IIS Inverter System will take 3 seconds (factory default) to apply battery-supplied power to the emergency circuit. This is useful in some fixture applications where sensing controls need to detect the loss in utility power to default to full light output in emergency mode. The transfer delay is factory set at 3 seconds but may be field adjusted by an IIS Inverter Technician to 1-8 seconds.

Available on IIS Single Phase, IISC, IIS3P, and IISCN3P models

PM(A or B)REG(#) – Five-Year Preventative Maintenance Plan

Ensure your IIS Inverter System operates at peak performance through its operating lifespan with regular preventative maintenance performed by a qualified IIS Inverter Technician. IOTA’s network of factory serviced technicians and factory trained and authorized service centers will travel to the job site to perform critical maintenance tasks on your IIS Inverter System on an annual (option PMA5REG#) or bi-annual (option PMB5REG#) basis. See iotaengineering.com for more details on what is included in the IIS Central Inverter preventative maintenance plan. Available in the continental U.S. only. Requires factory startup (see FSREG#) to be ordered.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P and IIS3P EXT models.

RAP – Remote Summary Alarm Panel

Provides a box (4″ x 4″ x 2 ¼”) containing a red alarm light and an audible alarm with a silence switch that will activate on any alarm condition. See individual  product user manuals for alarm details. The Remote Summary Alarm Panel may be installed up to 1000 feet from the Inverter.

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, and IISCN3P models.

RMP – Remote Meter Panel

Outfits the IIS Inverter System with an additional detached panel and keypad that provides greater flexibility in monitoring and programming the system from a remote location (up to 150 feet away from the inverter). This option allows users to remotely view status, alarm, and test data about the IIS Inverter System and remotely program system and test parameters. Standard Remote Meter Panel mounting distance is 100 feet but it may be extended up to 150 feet from the IIS Inverter. The Remote Meter Panel is an addition to the standard display panel attached to the Inverter cabinet. BACnet (BACIP, BACNET) and MODBUS (MODBUSIP, MODBUSRTU) options are not available with the Remote Meter Panel.

Available on IIS Single Phase, IIS3P, and IISCN3P models.

RTS – Remote Test Switch and Indicator

Provides a remote test switch, alarm, and indicator that can be used to remotely trigger a life safety test. Alarm conditions and failure modes will be communicated via the accompanying audible alarm and visual indicator.

Available on IIS 1100 and IISCN models.

SDC – Summary Dry Contacts

Provides Dry Form “C” Contacts (rated at 5 amps maximum at 250VAC/30VDC) that change state when any system alarm activates. These contacts can be used to provide a continuity path to an external monitoring device (not provided), such as a Building Management System (BMS) or Indicator Panel for remote monitoring of the IIS Inverter’s alarm status. The Summary Dry Form C Contacts will change states with the following alarms (if available): high battery charger fault, near low battery, low battery, load reduction fault, output overload, high/low AC  input volts, high ambient temperature,inverter fault, and system test fault. The Summary Dry Contacts can also be configured to change state when optional circuit breaker trip alarms are triggered (see OTA option).

Available on IIS Single Phase, IISC, IIS3P, and IISCN3P models.

SNMP – Serial to Ethernet Network Adapter

Equips the IIS Inverter System with an RJ-45 Ethernet port for remote communications to a Building Management System (BMS) or Network Manager via SNMP protocol. The SNMP interface supports standard IP network settings including DHCP or static IP address, subnet mask, and default gateway. The SNMP interface supports SNMP v1 and v2c, and supports the programming of SNMP traps when user defined alarm conditions are met. The SNMP interface supports standard “SNMP Get,” as well as standard SNMP MIB walking via “SNMP Get Next,” and provides read-only objects (OIDs) for the following telemetry about the IIS Inverter System:

  • Input Voltage(s)

  • Output Voltage(s)

  • Output Current(s)

  • Total Output Power

  • Ambient Temperature

  • Battery Voltage

  • Battery Current
    Total Time on Battery (in Emergency Mode)

  • Days of Operation

  • Results of the Inverter’s last automatic monthly self-test

  • Results of the inverter’s last automatic yearly self-test

  • Alarm states including no utility, on battery, battery low, input voltage high/low, inverter failure detected, inverter overloaded and overload shutdown, ‘load reduction’ activated, ambient temperature high, and battery charger fault
    SNMP

Available on IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, and IISCN3P models.

SPAREF – Spare Fuses

Provides spare fuses for the IIS Inverter System.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

SPARES – Spare Fuses and Circuit Boards

Provides spare fuses and circuit boards for the IIS Inverter System.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

ST – Standard Transfer

Single Phase ST (Standard Transfer) models will transfer to battery power (emergency mode) when AC utility power is interrupted for more than one line cycle (50ms). This allows IIS Single Phase FT models to be compatible with most lighting types including LED, Fluorescent, Incandescent, and Quartz lamps. IIS Single Phase ST models are considered “interruptible.”

Available on IIS Single Phase models.

STAINLESS – Stainless Steel Enclosure

Outfits IIS EXT Outdoor Inverter Systems with a stainless steel enclosure toprotect against corrosion from exposure tosalt water or environments where corrosive gas or moisture is present.

Available on IIS EXT (excluding 1750) and IIS3P EXT models.

STRAP – Battery Strapping

Provides battery strapping to secure the batteries in the enclosure.

Available on IIS 1100, IISC, and IISCN models.

STRAPW – Battery Strapping and Wall Mount Bracket

Includes options STRAP and WALL. Provides a wall mount bracket to mount the IIS Inverter to the wall and battery strapping to secure the batteries in the enclosure.

Available on IISC models.

SZ – Seismic Rating with Shaker Table Testing for OSHPD

IIS SZ and IIS3P SZ models are designed and built to meet Seismic Zone 4 (the highest seismic zone rating) conditions and undergo thorough withstand testing to meet OSHPD certification requirements. These models undergo shaker table withstand testing to an SDS level of 2.5g in accordance with ICC-ES-AC-156 procedures. If OSHPD certification is not needed, many IIS models offer Seismic Zone Mounting (see SZM option) for increased durability and safety in seismic zone installations.

Available on IIS Single Phase and IIS3P Models.

SZM – Seismic Zone Mounting

Provides an additional base and battery strapping (on certain models) for seismic mounting to the floor. Note: this option does not include shaker testing to meet OSHPD/ICC requirements. IIS SZ or IIS3P SZ models must be purchased for seismic applications where shaker testing is required.

Available on IIS Single Phase, IISC, IIS3P and IISCN3P models. Standard offering on IIS EXT and IIS3P EXT models.

TREG(#), TCAN, TMEX – Extended On-Site Training

Empower facility staff to confidently maintain the IIS Central Inverter System with Extended On Site Training. An addition to the IIS Factory Startup program, Extended On Site Training is conducted at the job site by a qualified IIS Inverter technician for the benefit of any on-site personnel. The training features a deep dive into the system operation, safety procedures, and maintenance of the IIS Central Inverter. The agenda may be customized at the time of service by the IIS Inverter technician to accommodate the needs of the attendees. See iotaengineering.com for more details on what Extended On Site Training entails. Requires factory startup (see FSREG#, FSCAN, FSMEX) to be ordered.

Available on IIS 1100, IIS Single Phase, IIS EXT, IISC, IIS3P, IIS3P EXT, IISCN, and IISCN3P models.

VRLA10 – 10-Year Long Life VRLA Batteries

Note: IIS EXT 1750 models automatically come with 10-year long-life VRLA batteries as standard. This option equips the IIS EXT and IIS3P EXT Inverter System with 10-year long-life VRLA batteries for extended battery operation. Standard batteries in IIS EXT and IIS3P EXT systems have an operating lifespan of 5 years. This option extends the battery lifespan to up to 10 years of normal operation.

Available on IIS EXT (excluding 1750) and IIS3P EXT models.

VRLA20 – 20-Year Long Life VRLA Batteries

This option equips the IIS and IIS3P Inverter System with 20-year long-life VRLA batteries for extended battery operation. Standard batteries in IIS Single Phase and IIS3P systems have an operating   lifespan of 10 years. This option extends thebattery lifespan to up to 20 years of normal operation.

Available on IIS Single Phase and IIS3P models

WALL – Wall Mount Bracket

Provides a wall mount bracket for securing the IIS Inverter System to a building wall.

Available on IISC and models.

ZM(#) – Zone Monitoring

Allows the IIS Inverter System to monitor the presence of AC power in a specific zone (ex: area circuit or distribution panel). Upon loss of normal power in the zone(s), the inverter will switch to emergency mode and power any connected emergency equipment via its internal battery. Any normally-off loads will turn on and normally-on loads will remain on. Once AC power is restored to the zone(s), the inverter will return to normal  mode. Any normally-off loads will turn off and normally-on loads will continue operating via AC utility power.

Available on IIS Single Phase, IIS EXT (excluding 1750), IISC, IIS3P, IIS3P EXT, and IISCN3P models.

If you would like further information on IOTA IIS Central Inverter Systems, or have additional questions on IIS Inverter Options, please visit us online at www.iotaengineering.com or call us at 1-800-866-4682

Table 1: Option Availability per Model

Option is available

Option is not available

Option| Description| IIS 1100| IIS Single Phase| IIS EXT| IIS EXT 1750| IISC| IIS3P| IIS3P EXT| IISCN| IISCN3P
---|---|---|---|---|---|---|---|---|---|---
5YR| Five Year Extended Warranty|  |  |  |  |  |  |  |  |
BACIP| BACnet IP Interface|  |  |  |  |  |  |  |  |
BACNET| BACnet MS/TP Interface|  |  |  |  |  |  |  |  |
BATINST| Battery Installation|  |  |  |  |  |  |  |  |
BFAN| Battery Cabinet Fans|  |  |  |  |  |  |  |  |
BLOCK(#)| Output Breaker Locks|  |  |  |  |  |  |  |  |
BTM| Battery Temperature Monitor|  |  |  |  |  |  |  |  |
BYPASS| Internal Maintenance Bypass (MBB)|  |  |  |  |  |  |  |  |
BYPASSBBM| Internal Maintenance Bypass (BBM)|  |  |  |  |  |  |  |  |
DR| Dimming Relay|  |  |  |  |  |  |  |  |
DRIP| NEMA 2 Drip Top|  | | | | |  |  |  |
EMD| Enhanced Metering and Programming Display| | | | |  |  |  |  |
EO| Emergency Override|  |  |  |  |  |  |  |  |
EXTPASS| External Maintenance Bypass|  | |  |  |  |  |  |  |
FASTCHG| Fast Charge|  | | |  |  |  |  |  |
FLOOR| Floor Mount Bracket|  |  |  |  |  |  |  |  |
FLRMOUNT| Floor Mount Base|  | |  |  |  |  |  |  |
FLRSTRP| Floor Mount and Battery Strapping|  | | |  |  |  |  |  |
Option| Description| IIS 1100| IIS Single Phase| IIS EXT| IIS EXT 1750| IISC| IIS3P| IIS3P EXT| IISCN| IISCN3P
FSREG(#), FSCAN, FSMEX| Factory Startup|  |  |  |  |  |  |  |  |
FT| Fast Transfer|  |  |  |  |  |  |  |  |
IDC| Inverter On Dry Form C Contact|  |  |  |  |  |  |  |  |
IRTEST| Infrared Remote Test|  |  |  |  |  |  |  |  |
KEYPAD| Keypad and Display Panel|  |  |  |  |  |  |  |  |
LBT| Load Bank Test|  |  |  |  |  |  |  |  |
LCR| Load Control Relay|  |  |  |  |  |  |  |  |
LFILTER| TVSS Line Filter|  |  |  |  |  |  |  |  |
MDC| Status Monitoring Dry Form C Contacts|  |  |  |  |  |  |  |  |
MDCP| Status Monitoring Contacts w/ Panel|  |  |  |  |  |  |  |  |
MODBUSIP| MODBUS TCP Interface|  |  |  |  |  |  |  |  |
MODBUSRTU| MODBUS Serial (RTU or ACII) Interface|  |  |  |  |  |  |  | |
OBSHUNT| Main Output Breaker w/ Shunt Trip|  |  |  |  |  |  |  |  |
OTA| Output Breaker Trip Alarm|  |  |  |  |  |  |  |  |
OTDELAY| Output Transfer Delay to Emergency|  |  |  |  |  |  |  |  |
PM(A or B)5REG| Five-Year Preventative Maintenance Plan|  | |  |  |  | |  |  |
RAP| Remote Summary Alarm Panel|  |  |  |  |  |  |  |  |
Option| Description| IIS 1100| IIS Single Phase| IIS EXT| IIS EXT 1750| IISC| IIS3P| IIS3P EXT| IISCN| IISCN3P
RMP| Remote Meter Panel|  |  |  |  |  |  |  |  |
RTS| Remote Test Switch and Indicator|  |  |  |  |  |  |  |  |
SDC| Summary Dry Contacts|  |  |  |  |  |  |  |  |
SNMP| Serial to Ethernet Network Adapter|  |  |  |  |  |  |  |  |
SPAREF| Spare Fuses|  |  |  |  |  |  |  |  |
SPARES| Spare Fuses and Circuit Boards|  |  |  |  |  |  |  |  |
ST| Standard Transfer|  |  |  |  |  |  |  |  |
STAINLESS| Stainless Steel Enclosure|  |  |  |  |  |  |  |  |
STRAP| Battery Strapping|  |  |  |  |  |  |  |  |
STRAPW| Battery Strapping and Wall Bracket|  |  |  |  |  |  |  |  |
SZ| Seismic Rating for OSHPD|  |  |  |  |  |  |  |  |
SZM| Seismic Zone Mounting|  |  |  |  |  |  |  |  |
TREG(#), TCAN, TMEX| Extended On-Site Training|  |  |  |  |  |  |  |  |
VRLA10| 10-Year Long Life VRLA Batteries|  |  |  |  |  |  |  |  |
VRLA20| 20-Year Long Life VRLA Batteries|  |  |  | |  |  |  |  |
WALL| Wall Mount Bracket|  | |  | |  |  |  |  |
ZM(#)| Zone Monitoring|  |  | | |  |  |  |  |

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals