IOTA IIS3P SERIES Three Phase Central Inverters User Manual
- June 9, 2024
- IOTA
Table of Contents
- IIS3P SERIES Three Phase Central Inverters
- IMPORTANT SAFEGUARDS
- CHAPTER1 INTRODUCTION
- CHAPTER2 ENVIRONMENT
- CHAPTER3 STARTUP AND SHUTDOWN PROCEDURE
- MAINTENANCE BYPASS PROCEDURE
- CHAPTER4 OPERATION
- CHAPTER5 FRONT PANEL DISPLAY
- Meter Functions
- Control Functions
- Program Functions
- CHAPTER 6 SPECIFICATIONS
- CHAPTER7 MAINTENANCE AND SERVICE
- TROUBLE SHOOTING CHART
- WARRANTY
- OUT OF WARRANTY REPAIR CHARGES AND LABOR
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IIS3P SERIES Three Phase Central Inverters
User Manual
IIS3P SERIES THREE PHASE
24kW 50 kW and 16.7 (2-hour) User’s Manual
113784C System
Users Manual
IIS3P SERIES Three Phase Central Inverters
CAUTION
READ ENTIRE MANUAL AND REVIEW ALL DOCUMENTATION BEFORE ATTEMPTING SYSTEM
INSTALLATION
FOR SERVICE OR INSTALLATION INFORMATION:
TELEPHONE: 610-868-5400 (24 HR.
HOTLINE)
FAX: 610-954-8227
FOR YOUR PROTECTION PLEASE COMPLETE AND RETURN WARRANTY REGISTRATION CARD
IMMEDIATELY.
This unit contains LETHAL VOLTAGES. All repairs and service should be
performed by AUTHORIZED SERVICE PERSONNEL ONLY! There are NO USER SERVICEABLE
PARTS inside this unit.
IMPORTANT SAFEGUARDS
When using electrical equipment, you should always follow basic safety precautions, including the following:
- READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Do not install the system outdoors.
- Do not install near gas or electric heaters or in other high-temperature locations.
- Use caution when servicing batteries. Depending on battery type, batteries contain either acid or alkali and can cause burns to skin and eyes. If battery fluid is spilled on skin or in the eyes, flush with fresh water and contact a physician immediately.
- Equipment should be mounted in locations where unauthorized personnel will not readily subject it to tampering.
- The use of accessory equipment not recommended by Manufacturer may cause an unsafe condition and void the warranty.
- Do not use this equipment for other than its intended use.
- Qualified service personnel must perform all servicing of this equipment.
SAVE THESE INSTRUCTIONS
The installation and use of this product must comply with all national,
federal, state, municipal, or local codes that apply. If you need help, please
call Service.
User’s Guide
An on-site permanent log of the inspection, testing, and maintenance of the
emergency electrical power supply system shall be maintained in accordance
with the Manufacturer’s operating manual. The log shall include:
The date on which the inspection, testing, and maintenance exercise was
carried out
The name of the person(s) who performed the inspection, testing, and
maintenance.
A note of any unsatisfactory condition observed or discovered, and the steps
taken to correct the condition
CHAPTER1 INTRODUCTION
Keep this manual and the System Installation Guide in the folder mounted
inside the unit.
This unit is a microprocessor controlled PWM (Pulse Width Modulated) pure sine
wave based DC to AC power inverter utilizing IGBT technology. It integrates a
fully automatic 3rate battery charger, a solid-state transfer system, control
circuitry, self testing and recording digital meter display, and maintenance
free sealed lead calcium type batteries. The system components are carefully
matched to make the unit a completely self-contained, fully automatic standby
power source for operation on all types of lighting loads. The batteries are
sized and tested per UL-924 and Life Safety Code ANSI / NFPA 101, providing
emergency power for a minimum of 90 minutes.
If the duration of a power failure is greater than the batteries storage
capability, the inverter will automatically shut down when the battery voltage
reaches 85% of the nominal DC voltage. This feature protects the battery from
being permanently damaged from a deep discharge that could cause cell
reversal. This battery protection feature is called “Low Voltage Disconnect”
or L.V.D.
When the AC power is restored after a full discharge, the system will be ready
for another power failure within 24hrs. If another power failure occurs before
the 24-hour recharge time, the run time will be decreased.
The front panel display incorporates an alphanumeric 2×20 LCD character
display, LED status indicators and a 4 x 4 keypad. All user interface
functions are available from the front panel assembly.
Utilizing a small footprint, this unit is for use with any lighting load
including quartz, HID, incandescent, fluorescent and halogen.
HOW TO USE THIS MANUAL This manual tells you how to start, operate, and
communicate with your unit and lets you know how to get more information for
special situations. Please record your unit’s model number, serial number, and
part number below. You can find these numbers on the labels on the inside
panel.
Model Number __
Serial Number __
Part Number ___
Service and Support
We are committed to outstanding customer service. A service technician is
available 24 hours a day, 365 days a year. Service is also available 24 hours
a day to give you access to technical notes and product information. You can
also visit our web site.
NOTE: Please have your unit’s Serial and Model numbers available when you
call; this number is located behind the right door.
Contact SERVICE one of the following ways:
Service Number: 610-868-5400
Service Fax: 610-954-8227
CHAPTER2 ENVIRONMENT
Make sure the environment is a clean, cool, dry place with normal ventilation.
Storage Temperature
Store the batteries (in the system or battery cabinet) at -18 to 40°C (0 to
104°F). Batteries have a longer shelf life if they are stored below 25°C
(77°F). Keep stored batteries fully charged. Recharge the batteries every
90120 days. The system or battery cabinet without batteries may be stored at
-20 to 70°C (-4 to 158°F).
Ventilation
The air around the unit must be clean, dust-free, and free of corrosive
chemicals or other contaminants. Do not place the system or batteries in a
sealed room or container.
Operating Temperature
System can operate from 20° to 30°C (68° to 86°F) and up to 95% relative
humidity. The batteries’ service life is longer if the operating temperature
stays below 25°C (77°F).
Batteries
The temperature should be near 25°C (77°F) for optimum battery performance.
Batteries are less efficient at temperatures below 18°C (65°F), and high
temperatures reduce battery life. Typically, at about 35°C (95°F), battery
life is half of what it would be at a normal temperature of 25°C (77°F). At
about 45°C (113°F), battery life is one-fourth of normal.
Make sure that heaters, sunlight, air conditioners, or outside air vents are
not directed toward the batteries. These conditions can make the temperature
within battery strings vary, which can cause differences in the batteries’
voltages. Eventually, these conditions affect battery performance. If the
batteries are not in the system, remember that the batteries should be
installed as close as possible to the unit to reduce DC wiring costs and
improve battery performance. Do not allow tobacco smoking, sparks, or flames
in the system location because hydrogen is concentrated under the vent cap of
each cell of the battery. Hydrogen is highly explosive, and it is hard to
detect because it is colorless, odorless, and lighter than air. Every type of
battery can produce hydrogen gas, even sealed maintenance-free batteries. The
gas is vented through the vent caps and into the air, mainly when the unit is
charging the batteries. The batteries produce the most hydrogen when maximum
voltage is present in fully charged batteries; the batteries do not produce
hydrogen during float charging. The amount of current that the charger
supplies to the batteries (not the battery ampere-hour) determines how much
hydrogen is produced.
High Altitude Operation
The maximum operating ambient temperature drops 1°C per 300m (2°F per 1000
ft) above sea level. Maximum elevation is 3000m (10,000 ft).
CHAPTER3 STARTUP AND SHUTDOWN PROCEDURE
Refer to the Installation Manual to secure the unit and install AC and DC
wiring.
STARTUP PROCEDURE
For the initial startup of the system, follow the instructions in the Startup
and Warranty Validation Form. Failure to do so will void warranty.
CAUTION: HAZARDOUS VOLTAGES ONLY QUALFIED SERVICE PERSONNEL SHOULD
PERFORM PROCEDURE.
- Verify that the installation switch located on the inverter chassis is in the OFF position. Verify that AC input is disconnected.
- Press and hold the DC Pre-charge switch located on the inverter chassis for approximately five seconds and then turn on the battery breaker.
- Energize the Mains AC input by turning on the units input circuit breaker and/or the Distribution Panel breaker located upstream from the inverter.
- Turn the installation switch to the On position. The Front Panel display should now be illuminated and a slight hum should be heard from the inverter transformer. The unit is now charging and the output should be energized.
SHUTDOWN PROCEDURE
- Interrupt the AC Mains to the machine by the Distribution Panel Breaker or the machines input circuit breaker. The Inverter should then start.
- Turn the installation switch located on the inverter chassis to the off position. The inverter should stop.
- Disconnect the main battery breaker.
CAUTION: HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND
WITHIN THE SYSTEM. AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS
AND TURN OFF
UTILITY POWER BEFORE SERVICING EQUIPMENT.
CAUTION: DO NOT LEAVE THE SYSTEM SHUTDOWN FOR A PROLONGED LENGTH OF TIME. LEAD
BASED BATTERIES WILL EXPERIENCE PERMANENT DAMAGE FROM LACK OF CHARGING AFTER A
FEW MONTHS.
MAINTENANCE BYPASS PROCEDURE
CAUTION:
HAZARDOUS VOLTAGES ONLY QUALFIED SERVICE PERSONNEL SHOULD PERFORM PROCEDURE.
MAINTENANCE BYPASS SHOULD NOT BE PERFORMED WHEN SYSTEM IS IN BATTERY EMERGENCY
MODE.
System Into Bypass Mode
- Open left-hand door. Locate Maintenance Bypass Switch.
- Turn Maintenance Bypass Switch from normal mode (UPS) to bypass mode (BYPASS).
- Locate Installation Switch behind left-hand door on right-hand wall. Turn the Installation Switch to the (OFF) position.
- Locate Input Circuit Breaker (CB1) behind left-hand door. Turn the Input Circuit Breaker to the (OFF) position.
- Remove screws to open the right-hand doors. Locate the Main Battery Circuit Breaker on lower left-hand wall. Turn Main Battery Circuit Breaker to the (OFF) position.
CAUTION: HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND
WITHIN THE SYSTEM. AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS
BEFORE SERVICING EQUIPMENT.
WARNING: DO NOT LEAVE THE SYSTEM SHUTDOWN FOR A PROLONGED LENGTH OF TIME. LEAD
BASED BATTERIES WILL EXPERIENCE PERMANENT DAMAGE FROM LACK OF CHARGING.
Remove all Battery Fuses from all Battery Cabinets.
System On Line From Bypass Mode
- Verify that the Installation Switch is in the (OFF) position.
- Install all Battery Fuses in all Battery Cabinets.
- Press and hold DC Pre-charge switch located behind right-hand door for approximately five seconds and then turn the Main Battery Circuit Breaker to the (ON) position. If the circuit breaker trips, the batteries are not connected properly. Call service immediately.
- Turn the Input Circuit Breaker (CB1) to the (ON) position.
- Turn the Installation Switch behind the left-hand door on the right-hand wall to the (ON) position. The Front Panel Display will now be illuminated and a slight hum should be heard from the inverter transformer. The unit is now charging the batteries.
- Turn the Maintenance Bypass Switch from bypass mode (BYPASS) to normal mode (UPS). The emergency equipment is now protected by the inverter system.
CHAPTER4 OPERATION
The following is a description of the status LED’s located on the front panel.
AC Present
When the AC Mains is present, the LED will illuminate. If a power failure was
long in duration, or the AC mains was disconnected by some other means
(Circuit breaker open) the AC Present LED would not be illuminated. When the
control circuit senses that the line has dropped below an acceptable level
(Black Out, Brown Out, or Transient), the inverter will energize for at least
one minute. So, if the power failure was a momentary glitch, the AC present
LED would be illuminated but the inverter would be running.
System Ready
When the system has adequate battery voltage to transfer, the System Ready LED
will illuminate. This feature prevents damage from multiple deep discharges of
the battery.
Battery Charging
When the AC Mains is connected to the line and the battery is charging under
normal conditions, the Battery Charging LED will illuminate.
Battery Power
When the inverter is producing output power (battery is being discharged), the
Battery Power LED will be illuminated.
Fault
This is a summary Fault indication. When there is a fault condition present,
the Fault LED will illuminate. To view which fault is present, use the keypad
and LCD display feature.
The front panel display will provide the user with a variety of information.
It has a full compliment of Meter functions, Control functions and Program
functions.
CHAPTER5 FRONT PANEL DISPLAY
The Front panel consists of a 2 x 20 alphanumeric LCD display with LED Back
lighting, 5 Status LED indicators and a 4 x 4 keypad for user interface.
Figure 5.1 Front Panel Display
Control Panel Keypads
Table 5.1 Keypad Functions
Key Name | Description |
---|---|
Meter (Blue) | Pressing this key will activate Meter Functions |
Control (Red) | Pressing this key will activate Control Functions |
Program (Black) | Using this key, you can enter passwords or change parameter |
values. To enter passwords, press [PROGRAM], enter the password, and press
[ENTER]. NOTE: A password must be entered to change parameters.
Enter (Grey)| This key records or enters a task you perform using the control
panel keys.
◄| This key functions as Left scroll key
►| This key functions as Right scroll key
0| This key works as a number key; it is also used to display active alarms
when in CONTROL Mode.
[ 1 ] through [ 9 ]| These keys work as number keys.
Meter Functions
Meter functions are available by pressing the METER keypad to get to the Meter
Menu and then pressing the desired function keypad. (See figure 5.1)
Table 5.2 Meter Functions
Function | Description | Keypad Text |
---|---|---|
Voltage Input | Measures the AC Input Voltage to the Inverter | V IN |
Voltage Output | Measures the AC Output Voltage from the Inverter | V OUT |
Current Output | Measures the AC Output Current from the Inverter. If optional |
Normally Off loads is connected, it will read the sum of Normally On and
Normally Off outputs.| I OUT
Battery Voltage| Measures Battery Voltage| V BATT
Battery Current| Measures the Battery Current. When in charge mode, the
current will be positive. When in Inverter mode, the current will be
negative.| I BATT
VA Output| Multiplication of the output voltage and output current| VA OUT
Inverter Watts| Multiplication of the battery voltage and the battery current|
INV. WATTS
Inverter Minutes| Total minutes the system has run on inverter| INV. MIN
Temperature| Measures the ambient temperature of the electronics enclosure.|
TEMP
System Days| Total days the system has been in service.| SYS. DAYS
Control Functions
Control functions are available by pressing “CONTROL” to get to the Control
Menu and then pressing the desired function.
Table 5.3 Control Functions
Function | Keypad Text |
---|---|
Test Log | TEST LOG |
Event Log | EVENT LOG |
Initiate Test | TEST |
Alarm Log | ALARM |
Buzzer Silence | BUZZER |
-
TEST LOG – View the Test Log of the last 75 monthly or Yearly Tests. View the Date, Time,
Duration, Output Voltage, Output Current, Temperature and Fault Status.
Use the left and right scroll key to change event number.
Use the ENTER key to select desired event number.
Use the left and right scroll key to view event information about the event.
Use the TEST LOG key to return to the event number. -
EVENT LOG – Identical to the TEST LOG except this log records the past 75 events.
-
TEST – Pressing the TEST key will initiate a 1-minute test. This test will be recorded in the
Event log since it is not part of the scheduled monthly or yearly test. -
ALARM – View the Alarm log of the last 50 alarms. View the Date, Time and Alarm.
Use the left and right scroll key to change alarm number.
Use the enter key to select alarm number.
Use the left and right scroll key to view information about the alarm.
Use the ALARM key to return to event number. -
BUZZER – Pressing this key silences the audible buzzer from a fault condition or an intermittent beep when the inverter is under battery power. If a fault caused the buzzer to alarm and the alarm is silenced, the buzzer will return after 24 hours or after the fault is cleared.
Program Functions
User Program Functions
All program functions are password protected. The password for user level is
1234. When the PROGRAM keypad is pressed, the display will prompt the user for
the password. After the password is entered (1234 + ENTER key), the user can
change the Date, Time, Month Test Date, Month Test Time, Yearly Test Date and
Yearly Test Time, Load Reduction Fault, Low VAC Alarm, High VAC Alarm, Ambient
Temp Alarm and Near Low Battery settings. Time is always in the 24 hour
standard. Example 4:00 PM is 16:00.
Table 5.4 Program Functions
Parameter | Format | Factory Default |
---|---|---|
Date | MM/DD/YY (Month, Date, Year) | Current Date |
Time | HH/MM (Hours, Minutes) | Eastern Stand Time |
Monthly Test Date | DD (Date) | 15th of the Month |
Monthly Test Time | HH/MM (Hours, Minutes) | 5:00 |
Yearly Test Date | MM (Month) | 1 |
Yearly Test Time | HH/MM (Hours, Minutes) | 8:00 |
Load Reduction | AAAA(Amps) | 0.0A |
Low VAC Alarm | VVVV(Volts) | 1.0V |
High VAC Alarm | VVVV(Volts) | 999.9V |
Ambient Temp Alarm | DDD(Degrees Centigrade) | 70°C |
Near Low Battery | VVVV(Volts) | See Table 5.5 |
- Near Low Battery Voltage is in VVVV (Volts). The last digit entered is after the decimal place.
- I.E. (430 + ENTER) will register 43.0VDC. Please refer to table 5.5.
- Load Reduction Fault is in AAAA (Amps). The last digit entered is after the decimal place.
- I.E. (480 + ENTER) will register 48.0 Amps. If the output current under battery power is 10 percent below this number, the alarm will be set.
- Low AC Voltage Alarm is in VVVV (Volts). The last digit entered is after the decimal place.
- I.E. (1200 + ENTER) will register 120.0 Volts. If the Input AC Voltage goes below this number the alarm will be set.
- High AC Voltage Alarm is similar to Low AC Voltage Alarm.
- Ambient Temperature Alarm is in DDD (Degrees Centigrade). I.E. (75 + ENTER) will register 75 deg. C. When the ambient temperature internal to the inverter enclosure goes above the set point the alarm will be set.
Table 5.5 Near Low Battery Voltage
DC Voltage | Near Low Battery |
---|---|
240VDC | 216VDC |
CHAPTER 6 SPECIFICATIONS
IIS3P Series | Three Phase |
---|
Phone: 610-868-3500; Fax:
610-868-8686| General Specifications
effective 7/01/02
Input
Voltage
Input Power Walk-in Input Frequency Synchronizing Slew Rate
Protection
Harmonic Distortion Power Factor| 120/208 or 277/480Vac 3-phase 4-wire +10%
-15%.
Limiting inrush current to less than 125%, 10 times for 1 line cycle
60Hz, +/- 3%, 50Hz Available upon request
1Hz per second nominal
Input Circuit Breaker
< 10%
.5 lag/lead
Output
Voltage
Static Voltage
Dynamic Voltage
Harmonic Distortion Output Frequency Load Power Factor Inverter Overload
Protection| 120/208 or 277/480Vac 3-phase 4-wire.
Load current change +/-4%, battery discharge +/-4%
+/- 3% for +/-25% load step change, +/-6% for a 50% load step change, recovery
within 3 cycles
< 3% THD for linear load
60Hz +/- .05Hz during emergency mode
.5 lag to .5 lead
115% for 5 minutes
Output Cicuit Breaker
Battery
Type
Charger
Protection
Disconnect
Optional Runtimes| Valve-regulated sealed lead-calcium. Contact factory for
additional battery types.
Microprocessor controlled for various battery types and temperature
compensating (recharge per UL924 spec)
Automatic low-battery disconnect; automatic restart upon utility return.
Fuse- and-Fuse/ Circuit Breaker above 24KVA
Extended runtimes available. Consult factory for additional information.
Environmental
Altitude
Operating Temperature Storage Temperature Relative Humidity| < 10,000 feet
(above sea level) without derating
20 to 30 degree Celsius
-20 to 70 degrees Celsius (electronics only)
< 95% (non-condensing)
General
Design
Generator Input Control Panel Metering Alarms Communications Manual
Maintenance Bypass Alarm Contacts Warranty
Factory Start-up
5 Year Service Plan| Stand-By UPS. PWM inverter type utilizing IGBT technology
with 2mS transfer time.
Compatible with generators.
Microprocessor controlled 2 x 20-charactor Display with touch pad controls &
functions
5 LED indicators & alarm with ring-back feature
Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA,
Temperature, Inverter Wattage
High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction
Fault, Output Overload,
High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output
Fault, Optional Circuit Breaker Trip
RS-232 port (DB9)
Standard
Optional Summary Form “C” Contacts
1 year standard warranty includes all parts, labor, & travel expenses within
48 contiguous states. Up to 10 years
prorated warranty on batteries. Extended warranties, preventative maintenance
and customized service plans are available.
Purchase factory start-up & receive 1 additional year of warranty.
Purchase 5 year service plan & receive free factory start-up.
Physical
Cabinet Cooling
Cable Entry
Access| Freestanding NEMA Type 1
Forced Air, during emergency mode.
Top or Side
Front
CHAPTER7 MAINTENANCE AND SERVICE
The Self-testing feature of the inverter ensures that the system is tested at
least once per month for 5 minutes and once per year for 90 minutes. If there
are any problems with the self-tests, the fault log shall indicate which
faults occurred. Please see the fault descriptions and troubleshooting guide.
A few simple maintenance operations performed periodically will help ensure
many years of trouble free operation. Battery terminals should be checked for
tightness and corrosion. If severe corrosion is evident, maintenance is
required to correct this situation.
Since the unit depends on unrestricted airflow for cooling of power handling
components, it is important to keep the air vents free of any obstruction. If
the environment tends to be extremely dusty, occasionally blow away any
accumulation of dust on components. Please follow the shutdown procedure
before cleaning.
CAUTION: Follow the shutdown procedure (See Chapter 3) before cleaning.
An authorized technician only should perform Service!
Table 7.1 Preventive Maintenance Schedule
SERVICE TO PERFORM: | PERFORM SERVICE EVERY: |
---|---|
3 MONTHS | 6 MONTHS |
1.TEST UNIT:
NOTE: Perform manual test only when critical load is connected but not
required.
Output voltage should be present.
Confirm operations of front panel indicators.| X| |
| |
| |
| |
| |
| |
| |
| |
2.INSPECT BATTERIES:
All connections are tight.
Connections have no corrosion. (Clean if necessary).| | X|
| |
| |
| |
| |
| |
| |
| |
CLEAN UNIT: NOTE: Unit must be shut down during this service.
Inspect air vents and clean if necessary.
Clean excessive dust from inside cabinet(s).
Clean excessive dust from fan(s).| | | X
| |
| |
| |
| |
| |
| |
| |
“X” Indicates when to perform service. Lines below the “X” are for the date of service.
TROUBLE SHOOTING CHART
WARRANTY
For warranty information on IOTA IIS Central Inverters and battery components, visit www.iotaengineering.com or call IOTA Customer Service, the RMA number must appear on shipping labels, packing slips, and bills of lading.
OUT OF WARRANTY REPAIR CHARGES AND LABOR
Contact Field service for current parts and labor rates. A minimum rate will be assessed. The manufacturer will not proceed with repairs of an out of warranty unit until authorization in the form of a purchase order is received from the customer. The unit for repair must be returned prepaid with an RMA number on the carton. For travel to the job site, a quote “Not to Exceed” estimate will be given. A purchase order to cover that amount is required before a trip to the job site is made.