IOTA IIS SERIES 1.5 kW – 16.7 kW Models with Standard Transfer Speed User Manual
- June 9, 2024
- IOTA
Table of Contents
- IIS SERIES 1.5 kW – 16.7 kW Models with Standard Transfer Speed
- CHAPTER1 INTRODUCTION
- HOW TO USE THIS MANUAL
- CHAPTER2 ENVIRONMENT
- CHAPTER3 STARTUP AND SHUTDOWN PROCEDURE
- SHUTDOWN PROCEDURE
- CHAPTER 4 OPERATION
- CHAPTER5 FRONT PANEL DISPLAY
- System Information
- SPECIFICATIONS
- OPTIONS
- MAINTENANCE AND SERVICE
- TROUBLE SHOOTING CHART
- WARRANTY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IIS SERIES 1.5 kW – 16.7 kW Models with Standard
Transfer Speed
User Manual
IIS SERIES 1.5 kW – 16.7 kW Models with Standard Transfer Speed
CAUTION
READ ENTIRE MANUAL AND REVIEW ALL DOCUMENTATION BEFORE ATTEMPTING SYSTEM
INSTALLATION
FOR SERVICE OR INSTALLATION INFORMATION:
TELEPHONE: 610-868-5400 (24 HR.
HOTLINE)
FAX: 610-954-8227
FOR YOUR PROTECTION
PLEASE COMPLETE AND RETURN WARRANTY REGISTRATION CARD IMMEDIATELY.
This unit contains LETHAL VOLTAGES. All repairs and service should be
performed by AUTHORIZED SERVICE PERSONNEL ONLY! There are NO USER SERVICEABLE
PARTS inside this unit.
IMPORTANT SAFEGUARDS
When using electrical equipment, you should always follow basic safety
precautions, including the following:
- READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
- Do not install the system outdoors.
- Do not install near gas or electric heaters or in other high-temperature locations.
- Use caution when servicing batteries. Depending on battery type, batteries contain either acid or alkali and can cause burns to skin and eyes. If battery fluid is spilled on skin or in the eyes, flush with fresh water and contact a physician immediately.
- Equipment should be mounted in locations where unauthorized personnel will not readily subject it to tampering.
- The use of accessory equipment not recommended by Manufacturer may cause an unsafe condition and void the warranty.
- Do not use this equipment for other than its intended use.
- Qualified service personnel must perform all servicing of this equipment.
SAVE THESE INSTRUCTIONS
The installation and use of this product must comply with all national,
federal, state, municipal, or local codes that apply. If you need help, please
call Service.
User’s Guide
An on-site permanent log of the inspection, testing, and maintenance of the
emergency electrical power supply system shall be maintained in accordance
with the Manufacturer’s operating manual. The log shall include:
The date on which the inspection, testing, and maintenance exercise was
carried out.
The name of the person(s) who performed the inspection, testing, and
maintenance.
A note of any unsatisfactory condition observed or discovered, and the steps
taken to correct the condition.
CHAPTER1 INTRODUCTION
Keep this manual and the System Installation Guide in the folder mounted
inside the unit.
This unit is a microprocessor controlled PWM (Pulse Width Modulated) pure sine
wave based DC to AC power inverter utilizing IGBT technology. It integrates a
fully automatic 3rate battery charger, a solid-state transfer system, control
circuitry, self testing and recording digital meter display, and maintenance
free sealed lead calcium type batteries. The system components are carefully
matched to make the unit a completely self-contained, fully automatic standby
power source for operation on fluorescent and incandescent types of lighting
loads. The batteries are sized and tested per UL-924 and Life Safety Code ANSI
/ NFPA 101, providing emergency power for a minimum of 90 minutes.
If the duration of a power failure is greater than the batteries storage
capability, the inverter will automatically shut down when the battery voltage
reaches 85% of the nominal DC voltage. This feature protects the battery from
being permanently damaged from a deep discharge that could cause cell
reversal. This battery protection feature is called “Low Voltage Disconnect”
or L.V.D.
When the AC power is restored after a full discharge, the system will be ready
for another power failure within 24hrs. If another power failure occurs before
the 24-hour recharge time, the run time will be decreased.
The front panel display incorporates a 4 x 20 vacuum fluorescent display and a
4-button keypad. All user interface functions are available from the front
panel assembly.
Utilizing a small footprint, this unit is for use with incandescent and
fluorescent lighting loads.
HOW TO USE THIS MANUAL
This manual tells you how to start, operate, and communicate with your unit
and lets you know how to get more information for special situations.
Please record your unit’s model number, serial number, and part number below.
You can find these numbers on the label on the inside right-hand door.
Model Number
Serial Number
Part Number _____
Service and Support
FOR SERVICE OR INSTALLATION INFORMATION:
TELEPHONE:610-868-5400 (24 HR.
HOTLINE) FAX: 610-954-8227
NOTE: Please have your unit’s Serial and Model numbers available when you
call; this number is located behind the right door.
World Wide Web Site: www.iotaengineering.com
CHAPTER2 ENVIRONMENT
Make sure the environment is a clean, cool, dry place with normal ventilation.
Storage Temperature
Store the batteries (in the system or battery cabinet) at -18 to 40°C (0 to
104°F). Batteries have a longer shelf life if they are stored below 25°C
(77°F). Keep stored batteries fully charged. Recharge the batteries every
90–120 days. The system or battery cabinet without batteries may be stored at
-20 to 70°C (-4 to 158°F).
Ventilation
The air around the unit must be clean, dust-free, and free of corrosive
chemicals or other contaminants. Do not place the system or batteries in a
sealed room or container.
Operating Temperature
System can operate from 20° to 30°C (68° to 86°F) and up to 95% relative
humidity. The batteries’ service life is longer if the operating temperature
stays below 25°C (77°F).
Batteries
The temperature should be near 25°C (77°F) for optimum battery performance.
Batteries are less efficient at temperatures below 18°C (65°F), and high
temperatures reduce battery life.
Typically, at about 35°C (95°F), battery life is half of what it would be at a
normal temperature of 25°C (77°F). At about 45°C (113°F), battery life is one-
fourth of normal.
Make sure that heaters, sunlight, air conditioners, or outside air vents are
not directed toward the batteries. These conditions can make the temperature
within battery strings vary, which can cause differences in the batteries’
voltages. Eventually, these conditions affect battery performance.
If the batteries are not in the system, remember that the batteries should be
installed as close as possible to the unit to reduce DC wiring costs and
improve battery performance.
Do not allow tobacco smoking, sparks, or flames in the system location because
hydrogen is concentrated under the vent cap of each cell of the battery.
Hydrogen is highly explosive, and it is hard to detect because it is
colorless, odorless, and lighter than air.
Every type of battery can produce hydrogen gas, even sealed maintenance-free
batteries.
The gas is vented through the vent caps and into the air, mainly when the unit
is charging the batteries. The batteries produce the most hydrogen when
maximum voltage is present in fully charged batteries; the batteries do not
produce hydrogen during float charging. The amount of current that the charger
supplies to the batteries (not the battery ampere-hour) determines how much
hydrogen is produced.
High Altitude Operation
The maximum operating ambient temperature drops 1°C per 300m (2°F per 1000 ft)
above sea level. Maximum elevation is 3000m (10,000 ft).
CHAPTER3 STARTUP AND SHUTDOWN PROCEDURE
Refer to the Installation Manual to secure the unit and install AC and DC
wiring.
STARTUP PROCEDURE
For the initial startup of the system, follow the instructions in the Startup
and Warranty Validation Form. Failure to do so will void warranty.
CAUTION: HAZARDOUS VOLTAGES – ONLY QUALFIED SERVICE PERSONNEL SHOULD
PERFORM PROCEDURE.
- Verify that the installation switch located on the inverter chassis is in the OFF position. Verify that AC input is disconnected.
- Press and hold the DC Pre-charge switch located on the inverter chassis for approximately five seconds and then install the battery fuse. If a large flash occurs, the batteries are not connected properly. Call service immediately.
- Energize the Mains AC input by turning on the units input circuit breaker and/or the Distribution Panel breaker located upstream from the inverter.
- Turn the installation switch to the on position. The Front Panel display should now be illuminated and a slight hum should be heard from the inverter transformer. The unit is now charging and the output should be energized.
SHUTDOWN PROCEDURE
- Interrupt the AC Mains to the machine by the Distribution Panel Breaker or the machines input circuit breaker. The Inverter should then start.
- Turn the installation switch located on the inverter chassis to the off position. The inverter should stop.
- Disconnect the main battery fuse located on the inverter chassis.
- Locate the DC Discharge Switch (S3) and press it for 10 seconds.
CAUTION:
HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND WITHIN THE
SYSTEM. AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS AND TURN
OFF UTILITY POWER BEFORE SERVICING EQUIPMENT.
WARNING:
DO NOT LEAVE THE SYSTEM SHUTDOWN FOR A PROLONGED LENGTH OF TIME. LEAD BASED
BATTERIES WILL EXPERIENCE PERMANENT DAMAGE FROM LACK OF CHARGING.
CHAPTER 4 OPERATION
The following is a description of the system status located on the front panel
of the Vacuum Fluorescent Display.
AC Present
When the AC Mains is present, the words “LINE PRESENT” will illuminate. If a
power failure was long in duration, or the AC mains was disconnected by some
other means (Circuit breaker open) the “LINE PRESENT” would not be
illuminated. When the control circuit senses that the line has dropped below
an acceptable level (Black Out, Brown Out, or Transient), the inverter will
energize for at least one minute. So, if the power failure was a momentary
glitch, the “LINE PRESENT” would be illuminated but the inverter would be
running.
System Ready
When the system has adequate battery voltage to transfer, the words “SYSTEM
READY” will illuminate.
This feature prevents damage from multiple deep discharges of the battery.
Battery Charging
When the AC Mains is connected to the line and the battery is charging
under normal conditions, the words “BATTERY CHARGING” will illuminate.
Battery Power
When the inverter is producing output power (battery is being discharged), the
words “BATTERY POWER” will be illuminated.
Fault
This is a summary Fault indication. When there is a fault condition present,
the word “FAULT” will illuminate. To view which fault is present, use the
keypad and LCD display feature.
The front panel display will provide the user with a variety of information.
It has a full compliment of Meter functions, Control functions and Program
functions.
CHAPTER5 FRONT PANEL DISPLAY
The Front Panel Display assembly consists of a 4 x 20 vacuum fluorescent
display and a 4-button keypad. The 4 buttons can navigate through all the
menus by using the left and right arrow keys, the ENTER and the ESCAPE.
The default menu will scroll between the status screen and the
Identification/DateTime screen. To view the other menu options from the
default screen, press the ENTER key, and then press the left or the right
arrow key to go to the desired menu.
The Menu’s available are Meter, Test Log, Event Log, Alarm Log, User Setup,
Factory Setup, Status, System Information, and Test Mode. Once the desired
menu has been reached, press the ENTER key to gain access to this menu. Once
into the menu, use the left or right arrow key to scroll to different
functions within the menu. Press the ENTER key again to gain access to the
desire function. To exit, press the ESCAPE key until the desired level has
been reached.
(See figure 5.1)
Control Panel Keypads
Table 5.1 Keypad Functions
Key Name | Description |
---|---|
Enter (Blue) | Pressing this key will view menus. |
Escape (Black) | Pressing this key will exit out of menus and return to the |
Identification/Date-Time screen.
[ ◄ ] (Red)| This key functions as Left scroll key.
[ ◄ ] (Red)| This key functions as Right scroll key.
Meter Functions
To get to the meter functions from the default screen, press the ENTER key,
scroll to the METER menu using the left or the right arrow key, then press the
ENTER key
again. Use left or the right arrow key to view the meter function desired.
Table 5.2 Meter Functions
Function | Description |
---|---|
Voltage Input | Measures the AC Input Voltage to the Inverter. |
Voltage Output | Measures the AC Output Voltage from the Inverter. |
Current Output | Measures the AC Output Current from the Inverter. If there are |
Normally Off loads connected, it will read the sum of Normally On and Normally
Off outputs.
Battery Voltage| Measures DC Battery Voltage.
Battery Current| Measures the DC Battery Current. When in charge mode, the
current will be positive. When in Inverter mode, the current will be negative.
Battery Temperature| Optional feature — measures temperature at the battery.
Internal Temperature| Measures the ambient temperature inside the system.
Inverter Minutes| Indicates the total minutes the system has run on inverter.
System Days| Indicates the total days the system has been on-line.
VA Output| Indicates the AC Volts-Amps of the Inverter output.
Inverter Watts| Indicates the DC Watts (Battery Power) the Inverter is
processing.
Test Log
To get to the Test log menu from the default screen, press the ENTER key,
scroll to the Test log menu using the left or right arrow key, then press the
ENTER key again.
Use the left or right arrow key to view the test desired, and the press the
ENTER key for more information.
The Test log indicates the Date, Time and Duration of the test. It also
indicates if it was a monthly or yearly test, and it records the output
voltage, the output current, the ambient temperature, and if there were any
alarm conditions. The numbers of tests that can be captured in the test log
are 75. The format is first in is first out so; test number one is the most
recent test.
Event Log
To get to the Event log menu from the default screen, press the ENTER key,
scroll to the Event log menu using the left or right arrow key, then press the
ENTER key again. Use the left or right arrow key to view the event desired,
and then press the ENTER key for more information.
The Event log is identical to the test log in parameters it stores. The Event
log captures data every time there is a transfer from utility power to battery
power. The numbers of events that can be captured in the event log are 75. The
format is first in is first out so; event number one is the most recent event.
Alarm Log
To get the Alarm log menu from the default screen, press the ENTER key, scroll
to the alarm log menu using the left or right arrow key, then press the ENTER
key
again. Use the left or right arrow key to view the alarm desired, and then
press the ENTER key for more information.
Any alarm that has occurred is captured in the Alarm log. The numbers of
alarms that can be captured in the alarm log are 75. The format is first in is
first out so;
alarm number one is the most recent alarm.
Alarms
To get to the Alarm menu from the default screen, press the ENTER key, scroll
the Alarm menu using the left or right arrow key, then press the ENTER key
again.
The alarm menu displays all present alarms. If there are no alarms, the
display screen will indicate no alarms.
User Setup
To get to the User Setup menu from the default screen, press the ENTER key,
scroll to the User Setup menu using the left or right arrow key, then press
the ENTER key again. The display will prompt for a password.
**** The password is left arrow, right arrow, left arrow, and right arrow.
Once the password is entered, the user has access to change the following
functions:
Date, Time, Month Test, Year Test, Low VAC, High VAC, Near Low Battery, Low
Battery, High Temp, Load Reduction Current.
Date
The parameters are Day of Week, Month, Day, and Year.
To change any of the parameters, use the left or right arrow key depending if
you want to increase or decrease. Once the parameter is correct, press the
ENTER key and the next parameter can be changed.
Time
The parameters are Hour and Minute. The 24-hour standard is used so 2:00 PM
would be 14 hours. Use the left or right arrow key to change the parameters
and the ENTER key to scroll between parameters.
Month Test, Year Test
The parameters are Date, Time (Hours and Minutes) use the left or right arrow
key to change the parameters and the ENTER key to scroll between parameters.
Low VAC, High VAC, Near Low Battery, Low Battery, High Temperature Parameters
are set in Volts AC, Volts DC, and Degrees Centigrade respectively. Use the
left or right arrow key to turn on or off this alarm. When the alarm is turned
on, a number will appear. To change the number, press the ENTER key and then
use the left or right arrow key. Once the desired number is reached, press the
ENTER key and this will return to the top-level menu.
Table 5.3 Near Low Battery Fault Chart
DC Voltage | Near Low Battery |
---|---|
48VDC | 43VDC |
72VDC | 65VDC |
96VDC | 86VDC |
120VDC | 108VDC |
144VDC | 130VDC |
180VDC | 162VDC |
240VDC | 216VDC |
Load Reduction Current
Parameters are set in Amps AC.
Use the same technique as the above alarms for modification.
Load Reduction Current is a useful diagnostic tool that will automatically
generate a fault when the output current is 10 percent higher or lower than
the set-point number.
Status
Indicates the Status of the machine – Line Present, Battery Charging, Ready,
Battery Power, and if any faults are present.
System Information
Indicates Model Number, Serial Number and Current Software Revision Level of
the system.
Test Mode
To initiate a Test and cause the inverter to run on battery power.
SPECIFICATIONS
General Specifications
IInput| Voltage
Input Power Walk-in Input Frequency Synchronizing Slew Rate Protection
Harmonic Distortion Power Factor| 120 or 277Vac 1-phase 2-wire +10% -15%.
Contact factory for all other voltages. Walk-in limiting inrush current to
less than 125%, 10 times for 1 line cycle 60Hz. +/- 3%, 50Hz Available upon
request 1Hz per second nominal
Input Circuit Breaker < 10% .5 lag/lead
---|---|---
IOutput| Voltage Static Voltage
Dynamic Voltage Harmonic Distortion Overload Output Frequency Load Power
Factor
Inverter Overload Protection| 120 or 277Vac 1-phase 2-wire. Contact factory
for all other voltages. Load current change +1-2%, battery discharge +/-12.5%
+/- 2% for +/-25% load step change, +/-3% for a 50% load step change, recovery
within 3 cycles < 3% THD for linear load Fuse protected 60Hz +/- .05Hz during
emergency mode .5 lag to .5 lead
115% for 10 minutes Optional Distribution Circuit Breakers
IBattery| Type Charger Protection
Disconnect Optional Runtimes| Valve-regulated sealed lead-calcium. Contact
factory for additional battery types. Microprocessor controlled for various
battery types and temperature compensating (recharge per UL924 spec) Automatic
low-battery disconnect; automatic restart upon utility return. Fuse Extended
runtimes available. Consult factory for additional information.
I| Altitude Operating Temperature Storage Temperature Relative Humidity| <
10,000 feet (above sea level) without derating 20 to 30 degree Celsius -20 to
70 degrees Celsius (electronics only) < 95% (non-condensing)
IGeneral| Design Generator Input Control Panel Metering Alarms Communications
Manual Maintenance Bypass
Alarm Contacts Warranty
Factory Start-up 5 Year Service Plan| Stand-by Interruptible PWM inverter type
utilizing IGBT technology with 50mS transfer time. Compatible with generators.
Microprocessor controlled 4 x 20-charactor vacuum fluorescent display with
touch pad ontrols/functions & scrolling system status Input & Output Voltage,
Battery Voltage, Battery & Output Current. Output VA, Temperature. Inverter
Wattage High/Low Battery Charger Fault, Near Low Battery, Low Battery. Load
Reduction Fault, Output Overload. High/Low AC Input Volts, High Ambient
Temperature, Inverter Fault, Output Fault. Optional Circuit Breaker Trip
RS-232 port (DB9). Optional E-mail/fax modem.
Optional Internal or optional external without internal distribution breakers.
Optional Summary Form “C” Contacts 1 year standard warranty includes all
parts, labor, & travel expenses within 48 contiguous states. Up to 10 years
prorated warranty on batteries. Extended warranties, preventative maintenance
and customized service plans are available. Purchase factory start-up &
receive 1 additional year of warranty. Purchase 5 year service plan & receive
free factory start-up.
IPhysical| Cabinet Cooling Cable Entry
Access| Freestanding NEMA Type 1 Forced Air, during emergency mode. Top or
Side Front
OPTIONS
MAINTENANCE BYPASS PROCEDURE
CAUTION:
HAZARDOUS VOLTAGES – ONLY QUALFIED SERVICE PERSONNEL SHOULD PERFORM PROCEDURE.
System Into Bypass Mode
- Open System doors. Locate Maintenance Bypass Switch behind left-hand door on chassis.
- Turn Maintenance Bypass Switch handle from normal mode (UPS) (12 O’clock position) to bypass mode (BYPASS) (3 O’clock position).
- Locate Installation Switch behind right-hand door on chassis. Turn the Installation Switch to the (OFF) position.
- Locate Input Circuit Breaker (CB1) behind left-hand door on chassis. Turn the Input circuit Breaker to the (OFF) position.
- Locate Main Battery Fuse behind right-hand door on chassis. Remove Main Battery fuse.
CAUTION:
HAZARDOUS VOLTAGES STILL EXIST AT THE BATTERY TERMINAL BLOCK AND WITHIN THE
SYSTEM. AUTHORIZED SERVICE TECHNICIANS MUST DISCHARGE DC CAPACITORS BEFORE
SERVICING EQUIPMENT. LOCATE DISCHARGE SWITCH ON INVERTER CHASSIS. PRESS IT FOR
10 SECONDS.
WARNING:
DO NOT LEAVE THE SYSTEM SHUTDOWN FOR A PROLONGED LENGTH OF TIME. LEAD BASED
BATTERIES WILL EXPERIENCE PERMANENT DAMAGE FROM LACK OF CHARGING.
Remove all Battery String Fuses from Fuse Holders (10KVA – 16.7KVA Systems).
System On Line From Bypass Mode
-
Verify that the Installation Switch located on inverter chassis is in the (OFF) position.
-
Install all Battery String Fuses. (10KVA – 16.7KVA Systems)
-
Press and hold DC Pre-charge switch located on the inverter chassis for approximately five seconds and then install the Main Battery Fuse on the inverter chassis. If a large flash occurs, the batteries are not connected properly. Call service immediately.
-
Turn the Input Circuit Breaker (CB1) to the (ON) position.
-
Turn the Installation Switch on the inverter chassis to the (ON) position. The Front Panel
Display will now be illuminated and a slight hum should be heard from the inverter transformer. The unit is now charging the batteries. -
Turn the Maintenance Bypass Switch handle from bypass mode (BYPASS) (3 O’clock position) to normal mode (UPS) (12 O’clock position). The emergency equipment is now protected by the inverter system.
MAINTENANCE AND SERVICE
The Self-testing feature of the inverter ensures that the system is tested at
least once per month for 5 minutes and once per year for 90 minutes. If there
are any problems with the self-tests, the fault log shall indicate which
faults occurred. Please see the fault descriptions and troubleshooting guide.
A few simple maintenance operations performed periodically will help ensure
many years of trouble free operation. Battery terminals should be checked for
tightness and corrosion. If severe corrosion is evident, maintenance is
required to correct this situation.
Since the unit depends on unrestricted airflow for cooling of power handling
components, it is important to keep the air vents free of any obstruction. If
the environment tends to be extremely dusty, occasionally blow away any
accumulation of dust on components. Please follow the shutdown procedure
before cleaning.
CAUTION: Follow the shutdown procedure (See Chapter 3) before cleaning.
An authorized technician only should perform Service!
Table 8.1 Preventive Maintenance Schedule
SERVICE TO PERFORM: | PERFORM SERVICE EVERY: |
---|---|
3 MONTHS | 6 MONTHS |
1.TEST UNIT:
NOTE: Perform manual test only when critical load is connected but not
required. Output voltage should be present. Confirm operations of front
panel indicators.| X| |
| |
| |
| |
| |
| |
| |
| |
2.INSPECT BATTERIES:
All connections are tight. Connections have no corrosion. (Clean if
necessary).| | X|
| |
| |
| |
| |
| |
| |
| |
CLEAN UNIT: NOTE : Unit must be shut down during this service.
Inspect air vents and clean if necessary. Clean excessive dust from inside
cabinet. Clean excessive dust from fan(s).| | | X
| |
| |
| |
| |
| |
| |
| |
“X” Indicates when to perform service. Lines below the “X” are for the date of service.
TROUBLE SHOOTING CHART
WARRANTY
For warranty information on IOTA IIS Central Inverters and battery components,
visit www.iotaengineering.com or call IOTA
Customer Service.
OUT OF WARRANTY REPAIR CHARGES AND LABOR
Contact Field service for current parts and labor rates. A minimum rate will be assessed. The manufacturer will not proceed with repairs of an out of warranty unit until authorization in the form of a purchase order is received from the customer. The unit for repair must be returned prepaid with an RMA number on the carton. For travel to the job site, a quote “Not to Exceed” estimate will be given. A purchase order to cover that amount is required before a trip to the job site is made.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>