Metering Module of Basic local monitored PDU
Manual
DN-95622
Safety and Grounding:
Read the following information before installing or operating your DIGITUS Power Distribution Unit:
-
This PDU is intended for indoor use only.
-
This PDU must not be operated one behind the other!
-
Operation only in dry and closed rooms.
-
This PDU may not be operated covered. Always ensure free accessibility.
-
The maximum power stated on the rating plate must not be exceeded.
-
Plug this PDU into a three-wire, grounded power outlet only.
The power outlet must be connected to the appropriate branch circuit/ mains protection (fuse or circuit breaker). Connection to any other type of power outlet may result in a shock hazard. -
Use only the supplied brackets of mounting.
-
Check that the power cord, plug, and socket are in good condition.
-
Voltage is free only when the power plug is unplugged.
-
Disconnect the PUD from the power outlet before you install or connect equipment to reduce the risk of electric shock when you can not verify grounding.
Reconnect the PDU to the power outlet only after you make all connections. -
Operation under unfavorable environmental conditions must be avoided. (Humidity over 80% relative, wet, ambient temperatures above 50 ° C, solvents, flammable gases, dust, vapors).
-
If external damage to this PDU is detected, do not operate this PDU.
Take this PDU immediately out of service if external damage is detected. -
Do not pour liquids over the power strip. There is a high risk of fire or life-threatening electric shock.
-
When opening the power strip, live parts can be exposed.
There is a risk of electric shock. The power strip may only be opened by a specialist. When opening the power strip, live parts can be exposed.
There is a risk of electric shock. The power strip may only be opened by a specialist.
Overview
Basic Metered PDU is a data center power distribution device with a local monitoring function. It can accurately monitor voltage, current, power, and electrical energy with an accuracy of ±1%, providing customers with safe and stable power distribution services.
Hardware Introduction
-
Product sketch
Basic Metered PDU is equipped with a hot-swappable monitoring module, which can be replaced without power interruption of the devices when necessary.
1. Screen: LCD screen
2. RUN: A run indicator (flashes at intervals of 1 second during normal operation)
3. BUTTON: Button key (switch display content)
4. RESET: Restart the module -
Interactive display
2.1 Single-phase two way monitoring module (AC)
Press the “BUTTON” key to turn the pages, the first to sixth screens will display the current (00.00A), voltage (225.5V), active power (00.00kW), and electrical energy (00007.7kWh) of L, C1 circuit, and C2 circuit in sequence, and the seventh screen displays version number (VEr1.5.9), as shown below.
Technical Specification
Input | Single-phase | Rated voltage | 100-240VAC 50–60Hz |
---|---|---|---|
Maximum total load current | 16A/ 32A | ||
Three-phase | Rated voltage | 200-400VAC 50–60Hz | |
Maximum total load current | 3x1GA, 3x32A | ||
Direct current | Rated voltage | 240VDC/ 336VDC | |
Maximum total load current | 40A/ 60A | ||
Overload protection | Circuit breaker (optional) |
Input current detection and
display| Detection accuracy: ±1%; Display accuracy: 0.01A
Display mode: liquid crystal display;
Display direction: vertical/horizontal;
Input voltage detection and display| Detection accuracy: ±1%; Display
accuracy: 0.1V
Display mode: liquid crystal display;
Display direction: vertical/horizontal;
Output| Single-phase| Rated voltage| 100-240VAC 50–60Hz
Maximum total load current| 16A/ 32A
Three-phase| Rated voltage| 100-240VAC 50–60Hz
Maximum total load current| 3x16A, 3x32A
| Direct current| Rated voltage| 240VDC/ 336VDC
Maximum total load current| 40A/ 60A
Output socket system| See “Socket Standard and Output Unit Configuration
Table” for details.
Output unit specification| Accept customized production
Monitoring function (Local)| Voltage (V), Current (A), Active Power(kW),
Energy (kWh)
Alarm| Alarm condition| When total load current/voltage-current exceeds
the rated value
Alarm method| Buzzer alarm
Physical characteristics| Product dimensions| Depending on the actual
model
Properties of shell material| ABS & PC
Case color| Black
Mounting Style| Side brackets mounting/ Rear button mounting
Environment| Working temperature| 0°C–45°C
Relative humidity| 3090%
Storage temperature| -20°C — +70°C
This is a Class A product. In-home environment, this product may cause radio
interference.
In this case, the user may be required to take appropriate measures.
Hereby Assmann Electronic GmbH declares that the Declaration of Conformity is
part of the shipping content. If the Declaration of Conformity is missing, you
can request it by post under the below-mentioned manufacturer address.
www.assmann.com
Assmann Electronic GmbH
Auf dem Schüffel 3
58513 Lüdenscheid
Germany
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>