legrand 406432 Isolating Switch DX3 IS 1/2 Module Per Pole Instruction Manual
- June 6, 2024
- Legrand
Table of Contents
Isolating switch DX³-IS
1/2 module per pole, up to 40A
DESCRIPTION – USE
The isolating switch ensures the breaking and the isolation of electrical circuits.
Fully visible breaking indication.
RANGE
Polarity and symbols :
OVERALL DIMENSIONS
PREPARATION – CONNECTION
Mounting :
- On symmetrical EN 60.715 rail or DIN 35 rail.
Operating positions:
Power supply:
- For devices without indicator light: Either from the top or the bottom.
- For devices with indicator light: From the top.
Module maintenance:
- Isolating switches may be replaced in the middle of a row supplied with busbars without disconnecting the other products.
This method is available for the 1-pole, 2-poles, 3-poles, 4-poles.
Connection:
- Terminals protected against direct contact IP20, wired device.
- Cage terminals, with release and captive screws.
- Terminals fitted with shutters preventing a cable from being placed under the terminal, with the terminal partly open or closed.
- Alignment and spacing of the terminals permitting connection with the other products in the range via prong supply busbars.
- Terminal depth: 14 mm.
- Screw head: mixed, slotted, and Pozidriv no. 2.
- Tightening torques:
– Min : 1.2 Nm
– Recommended : 1.6 to 2 Nm
– Max : 2.8 Nm
Conductor type:
- Copper cable or supply busbar.
- Cable cross-section:
| Without ferrule| With ferrule
---|---|---
Rigid cable| 1 conductor 1.5 to 16 mm²
2 conductors 1.5 to 6 mm²|
Flexible cable| 1 conductor 1.5 to 10 mm²
2 conductors 1.5 to 4 mm²| 1 conductor 1.5 to 10 mm²
Recommended tools:
-
For the terminals:
– Screwdriver with 5.5 mm blade.
– Pozidriv no. 2 screwdriver. -
For attaching or removing the DIN rail:
– Screwdriver with 5.5 mm blade.
– Pozidriv no. 2 screwdriver.
Manual actuation of the Isolating switch:
- Ergonomic 2-position handle:
- “O-OFF”: Device open.
- “I-ON”: Device closed.
Contact status display:
- By marking the handle:
– “O-OFF” in white on a green background = contacts open.
– “I-ON” in white on a red background = contacts closed.
Locking:
- Padlocks possible in the open and closed positions with padlock support (Cat. No. 4 063 03) and Ø5 mm padlock (Cat. N°. 4 063 13) or Ø6 mm padlock (Cat. N°. 0 227 97).
Sealing:
- Possible in the open or closed positions.
Labeling:
- Circuit identification by way of a label inserted in the label holder situated on the front of the product.
GENERAL CHARACTERISTICS
Marking on the front side:
- By permanent ink pad printing.
Without indicator light :
*Rated current with X: Devices tested on the fluorescent lamp.
Marking on the upper panel:
- By permanent ink pad printing.
Without indicator light :
Rated operational voltage:
1-pole with or without indicator light and 2 poles with indicator light: We
= 250 V ~
2-poles without indicator light, 3-poles, and 4-poles: We = 400 V ~
Rated frequency:
- 50/60 Hz with standard tolerances.
Short circuit withstands:
- Rated conditional short-circuit current in combination: see coordination table on page 4.
Following IEC/EN 60947-3 :
- Icw = 750 A
- Icm = 1500 A
Following IEC/EN 60669-2-4 :
- Inc =4500 A with a fuse of the same rated current.
Insulation voltage:
- Ui = 500 V
Rated impulse withstand voltage:
- Uimp = 6 kV
Direct current utilization :
- 48V (110V with 2 poles serial cabling).
Utilization category:
- AC22: Mixed load.
- A: Frequent operations.
- AC23: Inductive load. Complies with IEC/EN 60947-3. Characteristic not marked on the product
Degree of pollution:
- 3 in accordance with standard IEC 60664-1.
The power dissipated per pole :
Without indicator light | With indicator light |
---|---|
16 A | 20A |
0,23W | 0,36W |
Indicator light (if equipped):
Technology: the fluorescent lamp.
Shelf life: 50 000 Hours.
Color: Orange.
Degree or class of
protection:
- Terminals protected against direct contact, Class of protection against solid objects and liquids (wired device): IP20 in accordance with standards IEC 529 – EN 60529 and NF 20-010.
- Class II in relation to metallic conductive parts
- Class of protection against mechanical impacts IK04 in accordance with standard EN 62262.
Plastic materials:
- Polyamide, PBT and PC
Enclosure heat and fire resistance:
- Resistance to glow wire tests at 960°C, in accordance with standard IEC 60695-2-10 & 60695-2-11.
- Classification V2, in accordance with standard UL94.
Higher heating potential:
- The heat potential is assessed at:
1-pole and 2-poles| 3-poles and 4-poles
---|---
1.29 MJ| 2.56 MJ
Closing and opening effort via the handle:
Handle force | 1-pole | 2-poles | 3-poles | 4-poles |
---|---|---|---|---|
To switch Off | 4N | 7N | 10N | 14N |
To switch On | 10N | 18N | 29N | 35N |
Mechanical endurance:
- Compliant with standard IEC/EN 60947-3 & IEC/EN 60669-2-4
- 300 000 operations with no load.
Electrical endurance:
- Compliant with standard IEC/EN 60947-3 & IEC/EN 60669-2-4
- 30 000 operations with load AC22A.
- 1 500 operations with load AC23A.
Vibrations and tremors resistance :
- Compliant with appendix Q category F of standard IEC/EN 60947-1.
Ambient temperatures:
- Operation: from – 25 °C to + 70 °C.
- Storage: from – 40 °C to + 70 °C.
Short-circuit behavior in coordination with upstream protection:
- Tests performed according to the protocol of IEC/EN 60669-2-4: The device remains fully functional and meets the switch tests after suffering two short circuits established in coordination with the DPCC of the following table.
– The first short circuit is set at an angle of 45 °.
– The second is provided by the switching on of the isolator switch on the short-circuit.
Rated voltage 400V- | Inc (kA) |
---|---|
Upstream protection | 16A |
MCB | DX3 4500A/6kA |
DX3 6000A/10kA | 4,5 |
DX3 10000A/16 kA | 4,5 |
DX3 25kA | 4,5 |
DX3 36kA | 4,5 |
DX3 50kA | 4,5 |
DPX3 160A 16kA | 4,5 |
DPX3 160A 25kA | 4,5 |
DPX3 160A 36kA | 4,5 |
DPX3 160A 50kA | 4,5 |
DPX3 250A 25kA | 4,5 |
DPX3 250A 36kA | 4,5 |
DPX3 250A 70kA | 4,5 |
Fuse gG / aM | 20A |
25A | 8 |
32A | 8 |
40A | 8 |
63A | 8 |
80A | 8 |
100A | 8 |
125A | 6 |
Rated voltage 250V- | Inc (kA) |
--- | --- |
Upstream protection | 16A |
MCB | DNX3 4500A/4,5kA |
DX3 4500A/6kA | 6 |
DX3 6000A/10kA | 7 |
DX3 10000A/16kA | 7 |
DX3 25kA | 7 |
DX3 36kA | 7 |
DX3 50I<A | 7 |
DPX3 160A 16kA | 7 |
DPX3 160A 25kA | 7 |
DPX3 160A 36kA | 7 |
DPX3 160A 50kA | 7 |
DPX3 250A 25kA | 7 |
DPX3 250A 36kA | 7 |
DPX3 250A 70kA | 7 |
Fuse gG / aM | 20A |
25A | 10 |
32A | 10 |
40A | 10 |
63A | 10 |
80A | 10 |
100A | 10 |
125A | 10 |
Packaged volume:
| Packaging| Volume (dm 3 )
---|---|---
1-pole| Per 10| 1.6
2-poles| Per 10| 1.6
3-poles| Per 5| 1.6
4-poles| Per 5| 1.6
Average unit weight:
1-pole | 65 g |
---|---|
2-poles | 81 g |
3-poles | 145 g |
4-poles | 160 g |
COMPLIANCE AND APPROVALS
In accordance with standards:
- IEC/EN 60947-3.
- IEC/EN 60669-2-4.
Usage in special conditions:
- Compliant with appendix Q category F of standard IEC/EN 60947-1.
Respect for the environment – Compliance with European Union Directives:
-
Compliance with Directive 2002/95/EC of 27/01/03 known as “RoHS” provides for a restriction on the use of dangerous substances such as lead, mercury, cadmium, hexavalent chromium and polybrominated biphenyl (PBB) and polybrominated diphenyl ether (PBDE) brominated flame
retardants from 1st July 2006. -
Compliance with the Directive 91/338/EEC of 18/06/91 and decree 94-647 of 27/07/04.
Plastic materials:
- Halogen-free plastic materials.
- Labeling of parts compliant with ISO 11469 and ISO 1043.
Packaging:
- Design and manufacture of packaging compliant with decree 98-638 of 20/07/98 and Directive 94/62/EC.
approvals obtained:
- See a list of approvals available.
AUXILIARIES AND ACCESSORIES
Wiring accessories:
-
Supply busbar used on 1 pole and 2 poles:
– HX³ 1-pole universal supply busbar (Cat N°: 4 049 26, 4 049 37).
– HX³ 4-poles supply busbar «screw» (Cat N°: 4 052 10).
– HX³ 4-poles supply busbar « head of the group » (Cat N°: 4 052 00, 4 052 01, 4 052 02). -
HX³ connection module plug-in system set (Cat N°: 4 052 23).
-
Connection terminals (Cat N°: 4 049 05, 4 052 08).
-
Sealable screwcover (Cat N°: 4 063 04).
Signaling auxiliaries :
- Auxiliary contact (0.5 module, Cat N°: 4 062 58).
- Double Auxiliary contact (1 module, Cat N°: 4 062 66).
Installation software:
- XL PRO³
Technical data sheet: F01479EN/02
Updated on: 19/06/2020
Created on: 15/11/2012
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>