Milesight EM300 Series Temperature and Humidity Sensor User Guide

June 6, 2024
Milesight

Milesight Logo

Milesight EM300 Series Temperature and Humidity Sensor

Milesight EM300 Series Temperature and Humidity Sensor

Applicability

This guide is applicable to EM300 series sensors shown as follows, except where otherwise indicated.

Model

|

Description

---|---

EM300-TH

| Temperature and Humidity Sensor

EM300-MCS

| Magnet Switch Sensor

EM300-SLD

| Spot Leak Detection Sensor

EM300-ZLD

| Zone Leak Detection Sensor

Safety Precautions

Milesight will not shoulder responsibility for any loss or damage resulting from not following the instructions of this operating guide.

  • The device must not be remodeled in any way.
  • The device is not intended to be used as a reference sensor, and Milesight will not should responsibility for any damage which may result from inaccurate readings.
  • Do not place the device close to objects with naked flames.
  • Do not place the device where the temperature is below/above the operating range.
  • Make sure electronic components do not drop out of the enclosure while opening.
  • When installing the battery, please install it accurately, and do not install the reverse or wrong model.
  • Make sure both batteries are newest when install, or battery life will be reduced.
  • The device must never be subjected to shocks or impacts.
Declaration of Conformity

EM300 series is in conformity with the essential requirements and other relevant provisions of the CE, FCC, and RoHS.

© 2011-2021 Xiamen Milesight IoT Co., Ltd.
All rights reserved.
All information in this guide is protected by copyright law. Whereby, no organization or individual shall copy or reproduce the whole or part of this user guide by any means without written authorization from Xiamen Milesight IoT Co., Ltd.

For assistance, please contact Milesight technical support:
Email: iot.support@milesight.com
Tel: 86-592-5085280
Fax: 86-592-5023065

Revision History

Date

| Doc Version|

Description

---|---|---

October 14, 2020

|

V 1.0

| Initial version

October 21, 2020

|

V 1.1

| Model name change and pictures replace

November 19, 2020

|

V 2.0

| Layout replace

Product Introduction

Overview

EM300 series is a sensor mainly used for outdoor environment through wireless LoRa network. EM300 device is battery powered and designed for multiple mounting ways. It is equipped with NFC (Near Field Communication) and can easily be configured by a smartphone or a PC software.
Sensor data are transmitted in real-time using standard LoRaWAN® protocol. LoRaWAN® enables encrypted radio transmissions over long distance while consuming very little power. The user can obtain sensor data and view the trend of data change through Milesight IoT Cloud or through the user’s own Network Server.

Features
  • Up to 11km communication range
  • Easy configuration via NFC
  • Standard LoRaWAN® support
  • Milesight IoT Cloud compliant
  • Low power consumption with 4000mAh replaceable battery

Hardware Introduction

Packing List
  • 1 × EM300 Sensor
    EM300 Sensor

  • Wall Mounting Kits
    Wall Mounting Kits

  • 1 × Warranty Card
    Warranty Card

  • 1 × Quick Guide
    Quick Guide

  • Double Sided Tape (for SLD or MCS sensor)
    Double Sided Tape

  • Mounting Screws (for SLD or MCS sensor)
    Screws

  • 1 × NFC Reader (Optional)
    NFC Reader

If any of the above items is missing or damaged, please contact your sales representative.

Product Overview
  • Front View:
    ① NFC Area
    Front View

  • Bottom View:
    ② Vent
    ③ Waterproof Connectors
    (For water leakage and magnet switch sensor)
    Bottom View

  • Internal View:
    ④ LED
    ⑤ Power Button
    ⑥ USB Type-C
    ⑦ Expandable Battery Slot
    ⑧ Battery
    Internal View

Dimensions (mm)

Dimensions

Power Button

Note: The LED indicator and power button are inside the device. EM300 can also be turned on/off and reset via Mobile APP or Toolbox.

Function

| Action|

LED Indication

---|---|---

Turn On

| Press and hold the button for more than 3 seconds.|

Off → Static Green

Turn Off

| Press and hold the button for more than 3 seconds.|

Static Green -> Off

Reset

| Press and hold the button for more than 10 seconds.
Note: EM300 will automatically power on after reset.|

Blink 3 times.

Check On/Off Status

| Quickly press the power button.|

Light On: Device is on.

Light Off: Device is off.

Basic Configuration

EM300 sensor can be monitored and configured via one of the following methods:

  • Mobile APP (NFC);
  • Windows software (NFC or Type-C port).

In order to protect the security of sensor, password validation is required when configuring via unused phone . Default password is 123456.

Configuration via Smartphone APP

Preparation:

  • Smartphone (NFC supported)
  • Toolbox APP: download and install from Google Play or Apple Store.

Read/Write Configuration via NFC

  1. Enable NFC on the smartphone and open “Toolbox” APP.

  2. Attach the smartphone with NFC area to the device to read basic information.
    Note: Ensure your smartphone NFC area and it is recommended to take off phone case before using NFC.
    Read or Write Configuration via NFC 01
    Read or Write Configuration via NFC 02

  3. Change the on/off status or parameters, then attach the smartphone with NFC area to the device until the APP shows a successful prompt.
    Read or Write Configuration via NFC 03

  4. Go to “Device > Status” to tap “Read” and attach the smartphone with NFC area to the device to read real-time data of sensor.
    Read or Write Configuration via NFC 04

Template Configuration

Template settings only work for easy and quick device configuration in bulk.
Note: Template function is allowed only for sensors with the same model and LoRa frequency band.

  1. Go to “Template” page on the APP and save current settings as a template.
    Read or Write Configuration via NFC 05

  2. Attach the smartphone with NFC area to another device.

  3. Select the template file from Toolbox APP and tap “Write”, keep the two devices close until the APP shows a successful prompt.
    Read or Write Configuration via NFC 06

  4. Slide the template item to the left to edit or delete the template.
    Read or Write Configuration via NFC 07

Configuration via PC

Preparation:

Log in the Toolbox
Make sure “Toolbox” is downloaded on your computer. Select one of the following methods to log in Toolbox.

Type-C Connection

  1. Open the case of EM300 and connect the EM300 to computer via type-C port.
    Type-C Connection

  2. Select type as “General” and click password to log in Toolbox. (Default password: 123456)
    General Setting

NFC Connection

  1. Connect the NFC reader to computer, then attach the EM300 to NFC area of the reader.
    NFC Connection 01

  2. Select type as “NFC” and serial port as NFC reader port on Toolbox.
    NFC Connection 02

Basic Configuration

  1. Click “Read” to read current data of the sensor.
    Add a Milesight Gateway 01

  2. When you perform one of the following operations, enter the password and wait a few seconds until toolbox shows a successful prompt. (Password is not need if you connect it via type-C port)

    • Turn on/off the sensor
    • Reset the sensor
    • Click “Write” to change settings
    • Upgrade
      NFC Connection 04

Template Settings
Note: Template function is allowed only for sensors with the same model and LoRa frequency band.

  1. Go to “Maintenance -> Template and Reset” page in Toolbox.
  2. Click “Export” to save the current settings as a template.
  3. Click “Browse” to select the correct template from computer.
  4. Click “Import” to import the template to the device.

NFC Connection 05

Upgrade

  1. Download firmware on your computer.
  2. Go to “Maintenance -> Upgrade” page in Toolbox.
  3. Click “Browse” and select the firmware from computer.
  4. Click “Upgrade” to upgrade the device.
    Note: If NFC connection is selected, please keep the two devices close and don’t move them in order to get the best connectivity as possible when upgrading.

NFC Connection 06

Configuration Examples

LoRa Channel Settings
The configuration of LoRaWAN® channel of EM300 must match the gateway’s. Refer to Appendix to check default channel settings of EM300.

Mobile APP Configuration:
Open Toolbox APP and go to “Device ->Setting -> LoRaWAN Settings” to change the frequency and channels.

Software Configuration:
Log in Toolbox and go to “LoRaWAN Settings -> Channel” to change frequency and channels.
Note: If frequency is one of CN470/AU915/US915, you can enter the index of the channel that you want to enable in the input box, making them separated by commas.
Examples:
1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60 All: Enabling all channels
Null: Indicates that all channels are disabled

NFC Connection 07

Alarm Settings
When water leakage sensor or magnet switch sensor is triggered, it will send alarm message once by default. Toolbox allows users to change the alarm reporting interval and reporting times.

Mobile APP Configuration:
Open Toolbox APP and go to “Device -> Setting -> Threshold Settings” to enable the threshold settings and input the threshold.

Alarm Setting 01

Software Configuration:
Log in Toolbox and go to “Device Settings -> Basic -> Threshold Settings” to enable the calibration and input the calibration value.

Alarm Setting 02

Installation

  1. Attach EM300 to the wall and mark the two holes on the wall. The connecting line of two holes must be a horizontal line.

  2. Drill the holes according to the marks and screw the wall plugs into the wall.

  3. Mount the EM300 to the wall via mounting screws.

  4. Cover the mounting screws with screw caps.
    Installation 01

  5. For leak detection senor, install the probe/cable to the place where liquid may leak. For magnet switch sensor, install the magnet beside the door/window.

Note: For SLD sensor, please ensure the metal pins of the probe are flat on the floor; for ZLD sensor, the cable can’t be twined or accumulated together. The probe or cable of water leakage sensor should be placed in an area of concern where water from a leak would likely accumulate.

Installation 02

Milesight IoT Cloud Management

EM300 sensors can be managed by Milesight IoT Cloud platform. Milesight IoT cloud is a comprehensive platform that provides multiple services including device remote management and data visualization with the easiest operation procedures. Please register a Milesight IoT Cloud account before operating following steps.
Milesight IoT Cloud URL: cloud.milesight-iot.com

Add a Milesight Gateway
  1. Enable “Milesight” type network server and “Milesight IoT Cloud” mode in gateway web GUI.
    Note: Ensure gateway has accessed the Internet.
    Add a Milesight Gateway 01

  2. Go to “My Devices” page and click “+New Devices” to add gateway to Milesight IoT Cloud via SN. Gateway will be added under “Gateways” menu.
    Add a Milesight Gateway 02

  3. Check if gateway is online in Milesight IoT Cloud.
    Add a Milesight Gateway 03

Add EM300 to Milesight IoT Cloud
  1. Go to “My Devices” page and click “+New Devices”. Fill in the SN of EM300 and select associated gateway.
    Add a Milesight Gateway 04

  2. After EM300 is connected to Milesight IoT Cloud, you could check the device information and data and create dashboard for it.
    Add a Milesight Gateway 05

Sensor Payload

All data are based on following format:

Channel 1

| Type 1| Data 1| Channel 2| Type 2| Data 2| Channel 3| …
---|---|---|---|---|---|---|---
1 Byte| 1 Byte| N Bytes| 1 Byte| 1 Byte| M Bytes| 1 Byte|

Uplink Packet(HEX)

Channel

| Type| Data Example|

Description

---|---|---|---

01

|

75(Battery Level)

|

64

|

64=>100
Battery level =100%

03

|

67 (Temperature)

|

10 01

|

10 01 => 01 10 = 272
Temp=272*0.1=27.2°C

04

|

**** 68 (Humidity)

|

71

|

71=>113
Hum=113*0.5=56.5%

05

|

00

|

00

|

Not water leakage

01

|

Water leakage

06

|

00

|

00

|

Magnet switch closed

01

|

Magnet switch open

ff

|

01 (Milesight Protocol Version)

|

01

|

V1

08 (Device SN)

|

64 10 90 82 43 75 00 01

|

Device SN is 6410908243750001

09 (Hardware Version)

|

01 40

|

V1.4

0a(Software Version)

|

01 14

|

V1.14

0f(Device Type)

|

00

|

Class A

Downlink Packet (HEX)

Channel

| Type| Data Example|

Description

---|---|---|---

ff

| 03(Set Reporting Interval)| b0 04|

b0 04 => 04 b0 = 1200s

Appendix

Default LoRaWAN Parameters

DevEUI

|

24E124 + 2nd to 11th digits of SN e.g. SN = 61 26 A1 01 84 96 00 41
Then Device EUI = 24E124126A101849

---|---

AppEUI

|

24E124C0002A0001

Appport

|

0x55

NetID

|

0x010203

DevAddr

|

The 5th to 12th digits of SN
e.g. SN = 61 26 A1 01 84 96 00 41
Then DevAddr = A1018496

AppKey

|

5572404C696E6B4C6F52613230313823

NwkSKey

|

5572404C696E6B4C6F52613230313823

AppSKey

|

5572404C696E6B4C6F52613230313823

Default Uplink Channels

Model

| Channel Plan|

Channel Settings/MHz

---|---|---

EM300-470M

| CN470|

470.3~489.3(All 95 channels)



EM300-868M

| EU868| 868.1, 868.3, 868.5
RU864|

868.9, 869.1

IN865

|

865.0625, 865.4025, 865.6025

EM300-915M

|

AU915

| 915.2~927.1 (All 72 channels)
US915|

902.3~914.2 (All 72 channels)

KR920

|

922.1, 922.3, 922.5

AS923|

923.2, 923.4

References