DMP CELLCOMF-LTE-V Universal LTE Fire Alarm Communicator User Guide

June 6, 2024
DMP

DMP logo

DMP CELLCOMF-LTE-V Universal LTE Fire Alarm Communicator User Guide

ECP PASSTHRU OVERVIEW

CellCom and DualCom Universal Communicators enable you to take over and manage ECP panels with connection to the ECP Bus. This feature is called ECP Passthru.

This guide is designed to walk you through ECP passthru installation and setup. For more complete information, refer to the CellCom Installation Guide (LT-1817) or the DualCom Installation Guide (LT-1859).

Procedure

The installation must follow this procedure:
Step 1: Mount the communicator.
Step 2: Wire the communicator.
Step 3: Program Vista keypad device address 20
Step 4: Configure ECP settings (remotely or locally)

Required Materials

The following software and hardware components are required to perform system takeovers:

A Mounting Holes
B Cellular Antenna
C SMA Connector
D Cell Modem
E Tamper
F Programming Connection
G Terminal Block
H Load and Reset Buttons
I Power and Armed LEDs
J Ethernet (DualCom only)

FIG 1 ECP PASSTHRU OVERVIEW

Step 1: MOUNT THE COMMUNICATOR

It is not necessary to remove the PCB from the housing when installing the communicator.

The communicator should be mounted to a wall using the included #6 screws in the mounting holes. Refer to Figure 1 for mounting hole locations.

Mount the communicator in a secure, dry place to protect it from tampering and weather damage. If using a 685 Series Conduit Backbox, refer to the 685 Installation Sheet (LT-1431) for mounting instructions.

Step 2: WIRE THE COMMUNICATOR

The communicator can be connected to the ECP Bus of a VISTA panel. See Table 1 and Figure 2 for the necessary wiring connections.
Caution: Remove all AC and battery power from the panels before wiring.

  1. Attach the antenna to the SMA connector. Refer to Figure 1.

  2. Connect system batteries as needed, then connect the panels to an appropriate power source.

  3. Connect a programming keypad to the communicator.
    a. For 12 VDC applications, connect the keypad to the communicator PROG header with a Model 330 programming harness.
    b. For 24 VDC applications, connect the keypad to the communicator PROG header with a
    Model 330‑24V programming harness with an in-line resistor.

  4. After programming is complete, remove the keypad and replace the housing cover on the mounted base.

Note: Address 1 is reserved by the system for programming keypads.

FIG 2 ECP PASSTHRU OVERVIEW

FIG 3 ECP PASSTHRU OVERVIEW

FIG 4 ECP PASSTHRU OVERVIEW

Figure 2: ECP Wiring

Step 3: PROGRAM THE VISTA KEYPAD

In this step, you will program VISTA Keypad 5 Device Address 20. This enables the VISTA panel to communicate with a CellCom or DualCom. This step must be performed locally at the VISTA panel.

  1. Power down and then power up the VISTA panel.
  2. Within 1 minute of powering up the VISTA panel, simultaneously press and hold the # and * buttons on the keypad.
  3. The keypad displays INSTALLER CODE. Enter the installer code (default is 4112), followed by 8 0 0.
  4. Enter *193, then enter 1 0.
  5. To save and exit programming, enter *99.

Step 4: CONFIGURE ECP SETTINGS

For the communicator to properly process data from the VISTA panel, keypad input must be set to ECP. You can perform this programming remotely with Dealer Admin or locally with a programming keypad.

Remote programming requires communicators with firmware Version 212 or higher. Local configuration requires communicators with firmware Version 202 or higher.

During configuration, refer to “Troubleshooting” for programming messages and troubleshooting steps.

Remotely (Dealer Admin)

Before programming, ensure the ECP panel’s IP address is set as default.

  1. Go to Customers.
  2. Find and select the system name.
  3. Go to Full Programming > System Options.
  4. In Keypad Input, select ECP.
  5. In ECP Partition, enter the number of the partition where you want the communicator to operate.
  6. Press Begin ECP Setup.
  7. If the host panel is a VISTA 128, turn on VISTA 128.
  8. Enter the host panel’s installer code in VISTA Installer Code.
  9. Press Begin.
  10.  After setup is complete, Dealer Admin automatically retrieves zones from the host panel. If you need to retrieve zones again later, open System Options and select Get Zones.

FIG 5 ECP PASSTHRU OVERVIEW

Locally (Keypad)

To advance through the programming menu, press CMD. To go back, press the Back Arrow key. To enter a menu, press any select key or area. To select an option, press the select key or area under that option.
Before programming, ensure the ECP panel’s IP address is set as default.

  1. Power up or reset the communicator.
  2. At the communicator keypad, enter 6653 (PROG) and press CMD.
  3. Advance to SYSTEM OPTIONS, then press any select key or area to enter the menu.
  4. Advance to KYPD INPUT, then press any select key or area.
  5. Select ECP by pressing the third select key or area under that option.
  6.  At ECP PARTN NBR, enter the number of the partition where you want the communicator to operate. Range is 1 – 8. Default is 1.
  7. To save programming, advance to STOP and press any select key or area.
  8. At the communicator keypad, enter 2313 (DIAG) and press CMD.
  9.  Advance to ECP SETUP and press any select key or area.
  10. At ECP SETUP VISTA 128?: If the panel is a VISTA 128, select YES. Otherwise, select NO.
  11.  At INST CODE, enter the ECP panel installer code and press CMD.
  12.  After configuration is finished, the keypad advances to GET ZONES. Press any select key or area.
    As the communicator retrieves zones from the ECP panel, the number of zones is displayed and incremented as ZONE CT (zone count).

Troubleshooting

FIG 6 ECP PASSTHRU OVERVIEW

Step 5: REMOTE PROGRAMMING

Starting with Remote Link™ Version 1.93, you can connect a customer’s Honeywell VISTA® panel with CellCom, DualCom, or iComSL Series communicators using Honeywell’s Compass® software and Remote Link.

Set up Remote Link
The following instructions assume that you already have a basic communicator account added to your Remote Link accounts. To enable ECP Passthru for that account, complete the following steps.

  1. Right-click Remote Link and select Run as administrator.
  2. Double-click the communicator account to open it.
  3. Go to Program > System Options.
  4. To enable communication, go to Keypad input and select ECP. Press OK.
  5. Go to File > Panel Information.
  6. In Connection Information, enter the VISTA account number in Ecp Acct.
  7. Press OK.
  8. Go to ECP Passthru > ECP Start/Stop Server.
  9. Minimize Remote Link.

FIG 7 ECP PASSTHRU OVERVIEW

Add the VISTA Panel in Compass

  1.  Open Compass.
  2. In the lower right corner of the Customers page, select Add. The Customer Detail window opens.
  3. In Subscriber Data, enter a Receiver number and Account number.
  4. In the Panel Data section, select the VISTA panel model and revision number.
  5. In Network Device MAC Addr, enter FFFFFF.
  6. Press OK.

FIG 8 ECP PASSTHRU OVERVIEW

FIG 9 ECP PASSTHRU OVERVIEW

Set Up Communication in Compass

  1. In Customers, double-click the account that you created in the previous section.
  2. The Panel Editor opens. Go to Tools > Communications.
  3. Go to File > Communication Settings.
  4. Select TCPIP Port Settings.
  5. To ensure that Compass uses a TCP/IP connection, select a TCP/IP port.
  6. Press Add.
  7. Back in Communication Settings window, select Apply.
  8. Press OK.

FIG 10 ECP PASSTHRU OVERVIEW

Configure TCP/IP Settings in Compass

  1. In the lower left corner of the Compass Communication window, press Connect.
  2.  A dialog pops up to notify you that communication settings must be configured. Press OK.
  3. Select Enable TCP/IP.
  4. In the TCPIP Port dropdown, select the appropriate TCP/IP port.
  5. Ensure that the Network Device MAC Addr is FFFFFF.
  6. In Connection Mode, select ECP.
  7. Ensure that AlarmNet-i is selected.
  8. Press Connect.

FIG 11 ECP PASSTHRU OVERVIEW

REFERENCE

Virtual Keypad

Virtual Keypad enables users to manage their systems remotely, including arming, disarming, viewing zone status, bypassing zones, view history, manage users, and more.
To use Virtual Keypad for remote management, the configuration must meet the following conditions:

  • ECP Panels must be programmed as Stay/Away for remote arming and disarming (No Partitions).

FIG 12 ECP PASSTHRU OVERVIEW

VISTA Panel Compatibility

FIG 13 ECP PASSTHRU OVERVIEW

Note: Vista 32, 40, 50, 128, 250 are not compatible with ECP Virtual Keypad and eSuite.

DMP logo

Designed, engineered, and manufactured in Springfield, MO using U. S. and global components.
LT-2209 21213

© 2021

I N T R U S I O N • F I R E • A C C E S S • NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP. com

Read More About This Manual & Download PDF:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals