AKO 1569x PROPlus 3PH BASIC Electronic Panel User Guide

June 13, 2024
AKO

AKO 1569x PROPlus 3PH BASIC Electronic Panel

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel

Product Information

  • Product Name: AKO-1569x AKO-1569x-EVC PROPlus 3PH BASIC Electronic Panel
  • User Manual: 1569H042 Ed.04

Index

  • 1.- Presentation
  • 1.1.- Maintenance
  • 1.2.- Precautions
  • 2.- Versions and references
  • 3.- Installation

Presentation

The PROPlus 3PH is a global electronic solution designed to manage positive and negative cold room stores. It can be used with standard condensing units, streamlined condensing units, or as a service panel in decentralized systems. The panel offers a high degree of IP65 protection, making it suitable for installation in damp environments. It features a new connection strip that simplifies the installation process.

Maintenance

To clean the surface of the unit, use a soft cloth, water, and detergent. Avoid using abrasive detergents, petrol, white spirits, or solvents.

Precautions

It is important to note the following precautions:

  • The AUX 1, AUX 2, and AUX 3 relays are programmable and their operation depends on the configuration. Refer to page 25 for more information.
  • The function of the digital inputs also depends on the configuration. See page 26 for details.
  • The recommended currents and powers mentioned are the maximum working currents and powers.

Versions and References

Condensing unit| Condenser fans| Evaporator fan| Defrost resistances| Light Power supply
---|---|---|---|---
AKO-15690| 2.5 – 4 A| –| –| 7,000 W
AKO-15691| 4 – 6.3 A| –| –| 10,200 W
AKO-15692| 6.3 – 10 A| –| –| 20,000 W
AKO-15693| 10 – 16 A| –| –| –
AKO-15697| –| –| –| 5 A (I+N)
AKO-15699| –| 3 A| 4 A (I+N)| –
AKO-15699-1| –| 1.6 – 2.5 A (III+N)| –| –
AKO-15690-EVC| 2.5 – 4 A| –| –| 7,000 W
AKO-15691-EVC| 4 – 6.3 A| –| –| 10,200 W
AKO-15692-EVC| 6.3 – 10 A| –| –| 20,000 W
AKO-15693-EVC| 10 – 16 A| –| –| –
AKO-15697-EVC| –| –| –| 5 A (I+N)
AKO-15699-EVC| –| 3 A| 4 A (I+N)| –
 |

Condensing unit

|

Condenser fans

|

Evaporator fan

|

Defrost resistances

|

Light

|

Power supply

---|---|---|---|---|---|---
AKO-15690| 2,5 – 4 A|

3 A (I+N)

|

4 A (I+N)

| 7.000 W|

1 A (230 W)

|

400 V / III

50/60 Hz

AKO-15691| 4 – 6,3 A
AKO-15692| 6,3 – 10 A|

10.200 W

AKO-15693| 10 – 16 A
AKO-15697| –| –| 5 A (I+N)
AKO-15699| 1.6 – 2.5 A (III+N)
AKO-15699-1| –| –| 6.3 – 10 A (I+N)| 20.000 W
AKO-15690-EVC| 2,5 – 4 A|

3 A (I+N)

|

4 A (I+N)

| 7.000 W
AKO-15691-EVC| 4 – 6,3 A
AKO-15692-EVC| 6,3 – 10 A|

10.200 W

AKO-15693-EVC| 10 – 16 A
AKO-15697-EVC| –| –| 5 A (I+N)
AKO-15699-EVC| 1.6 – 2.5 A (III+N)

Installation

A.- Open and remove the cover.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(1\)
B.- Use the included template to make four holes in the wall. Fasten the unit to the wall using the supplied screws. Create a hole in the bottom of the box to pass the cables through, and use a suitable gland to maintain the IP65 degree of protection.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(2\)
C.- Put on the cover and arrange the wiring according to the enclosed diagrams. Connect the control hose (1), adjust the motor guard (Q1/Q3), and close the cover (2).

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(3\)
Note: Refer to the user manual for specific instructions on motor guard adjustment for different models.

AKO Electromecànica thanks you and congratulates you on the purchase of our product, the development and manufacture of which involved the most innovative technologies, as well as rigorous production and quality control processes. Our commitment to achieving customer satisfaction and our continuous efforts to improve day by day are confirmed by the various quality certificates obtained. This is a high-performance, technologically advanced product. Its operation and the final performance achieved will depend, to a great extent, on correct planning, installation, configuration, and commissioning. Please read this manual carefully before proceeding to install it and respect the instructions in the manual at all times.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(4\)

Only qualified personnel may install the product or carry out technical support. This product has been developed for use in the applications described in the manual. AKO Electromecànica does not guarantee its operation in any use not foreseen in this document and accepts no liability in the case of damage of any type that may result from incorrect use, configuration, installation or commissioning. Complying with and enforcing the regulations applying to installations where our products are destined to be used is the responsibility of the installer and the customer. AKO Electromecànica accepts no liability for damage that may occur due to failure to comply with these regulations. Rigorously follow the instructions described in this manual. In order to extend the lifetime of our products to the maximum, the following points must be observed.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(6\)

Do not expose electronic equipment to dust, dirt, water, rain, moisture, high temperatures, chemical agents or corrosive substances of any type. Do not subject equipment to knocks or vibrations or attempt to handle them in any way differently to that indicated in the manual. Do not under any circumstances exceed the specifications and limitations indicated in the manual. Respect the indicated environmental conditions for operation and storage at all times. During installation and on completion of this, avoid the presence of loose, broken or unprotected cables or cables in poor condition. These may constitute a risk for the equipment and its users.AKO Electromecànica reserves the right to make any modification to the documentation and the product without prior notification.

Presentation

PROPlus 3PH is the global electronic solution to manage positive and negative cold room stores, in combination with

  • Standard condensing units
  • Streamlined condensing units
  • Or as a service panel in decentralized systems.

It offers a high degree of IP65 protection for installation in damp environments. It is easy to install thanks to its new connection strip.

Maintenance
Clean the surface of the unit with a soft cloth, water and detergent. Do not use abrasive detergents, petrol, white spirits or solvents.

Precautions
Using the equipment without following the manufacturer’s instructions may affect the device’s safety requirements. To ensure that the device operates correctly, only probes supplied by AKO should be used.
Between -40 ºC and +20 ºC, if the NTC probe is extended up to 1,000 m with minimum 0.5 mm² wire, the maximum deviation will be 0.25 ºC (Wire for probe extension ref. AKO-15586)

IMPORTANT

  • The AUX 1, AUX 2, and AUX 3 relays are programmable, and their operation depends on the configuration (see page 25).
  • The function of the digital inputs depends on the configuration (See page 26).
  • The recommended currents and powers are the maximum working currents and powers.

Installation

  • A.- Open and remove the cover.
  • B.- Using the included template, make 4 holes in the wall and fasten the unit to the wall using the supplied screws.
  • Make a hole in the bottom of the box to pass the cables through, and a suitable gland should be used to maintain the IP65 degree of protection.
  • C.- Put on the cover, and arrange the wiring according to the diagrams enclosed. Connect the control hose (1), adjust the motor guard (Q1/Q3) and close the cover (2).

AKO-15690/1/2/3, AKO-15690/1/2/3-EVC
Motor guard adjustment (Q1): Put an ammeter clamp into one of the compressor’s conductors. Start the compressor and check its consumption. Set the motor guard (Q1) according to the obtained value. The set value should never be higher than the consumption indicated by the manufacturer.

Motor guard adjustment (Q3)
Put an ammeter clamp into one of the fan’s conductors. Start the fan and check its consumption. Set the motor guard (Q3) according to the obtained value.The set value should never be higher than the consumption indicated by the manufacturer. Remove the front trims (A) and screw the cover on using the included screws (B). Then install the trims again.

Recommendations
Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to current standards and should be carried out by authorized staff. Only carry out the wiring foreseen in the wiring diagrams. Using the electrical panel not observing the manufacturer’s instructions may alter the appliance’s safety requirements. A tool is needed to remove any fixed part.

Panel installation

  • It is advisable to leave a clean safety space without obstacles around the panel.
  • Do not knock or make sudden movements on the panel.
  • Carry out the wiring according to the installation manual.
  • The probes and their cables should NEVER be installed in a conduit together with power, control or feeder cables.
  • The earth terminals that the panels contain are installed to guarantee the continuity of earthing, however, earthing is not carried out by the terminal and should be carried out outside the panel.
  • The neutral ratings are of the TT type. The IT rating should not be used.
  • Circuit breakers (protective switches) are of the phase/s + neutral, curve C type, guaranteeing switching and protection against overcurrents.
  • Close the panel when you are not working on it.
  • Residual current protection outside the electrical panel according to low voltage electrotechnical regulations.
  • The panels meet European standards EN 61439-1 / EN 61439-2.
  • Terminals for copper external conductors.

Checks before starting the panel up

  • Power supply voltages and frequencies will be the ones that figure in the “Technical specifications” section.
  • Check that there are no loose parts or foreign bodies on connections or switchgear.
  • Check that there is no dust or damp inside the panel.
  • Check the correct fastening of the switchgear and components.
  • Check the correct tightening of the screws and power connections.
  • Check the correct connection of the power conductors.
  • Check the correct insulation of the outer lines and that they do not mechanically force the inner connections of the panel.
  • Check that the maximum current of the Q1 and Q3 current breaker (according to model) has been set correctly. Before starting the installation up, we recommend preheating the compressor’s housing.

Checks during the panel start-up

  • Check that no electric arcs occur.
  • Check that the relays or contactors do not produce ratios.
  • Check that there is no overheating in cables, controllers, and the rest of the switchgear.

Checks after the first 24 hours of operation

  • Check that no overheating occurs.
  • Retighten screws and power connections.
  • Periodical preventive maintenance:
  • The panel should remain closed using its lock.
  • Retighten the power connections once a year.
  • Check the wear of the switchgear once a year.
  • Clean the outer surface of the panel with a soft cloth, water and detergent. Do not use abrasive detergents, petrol, white spirits or solvents.

Technical data

  • Working ambient temperature: –5 ºC to 40 ºC
  • Rated isolation voltage Ui = 440 V~
  • Electrical panels with degree of protection: IP 65
  • CEM B environment
  • Terminals for copper conductors
  • Resistance to short-circuits Icc=6 kA
  • Rated pulse voltage (Vimp) 2,5 KV
  • Cable isolation voltage:
  • Operation: 500V (Halogen free)
  • Power: 750V (Halogen free)

Description

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(7\)

If the pump down is active, it indicates the operation of the compressor. If the pump down is active, it indicates that the solenoid is open, otherwise, it indicates that the compressor is in operation.

Quick access to functions

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(8\)

Messages

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(9\)AKO-1569x-PROPlus-3PH-BASIC-Electronic-
Panel-fig- \(10\)

Message6.- Component location

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(11\)

ATTENTION: Make sure to turn of the equipment’s power supply before handling it, as different areas may be energized.
IMPORTANT: The availability of the elements described depends on the panel model.

Identification

  • F1: Defrost circuit breaker
  • FM: Operation circuit breaker
  • Q1: Compressor motor guard
  • Q3: Evaporator fan motor guard K1M: Compressor contactor K2M: Defrost contactor
  • K4M: Evaporator fan contactor T2: EVC Transformer
  • EVC1: Controller for expansion valve

Pressure switch wiring options

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(12\)

  • Combine high-low pressure controller (AKO-15690/1/2/3 – AKO-15690/1/2/3-EVC)
  • Separate Low-pressure controller per AC input (AKO-15690/1/2/3 – AKO-15690/1/2/3-EVC)

Pressure controller equivalence

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(13\)

Basic configuration

The basic configuration menu allows the equipment to be configured for the most common applications. Press the SET key for 5 seconds to access it. If the access code is activated, a 2-digit code is requested (See page 19), if the code entered is not correct the unit will not enter programming. If a more specific configuration is required use the advanced configuration menu (see page 22) After 20 seconds without touching any key, the unit returns to the previous level without saving changes or it will exit programming.

Function of the keys in programming

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(14\)

SP: Set point
It defines the temperature that should be inside the cold storage room (See page 13):

  • Minimum: –45.0 *
  • Maximum: 99 *

(Depends on the bottom/top locking of the set point). d0: Defrost frequency
The time that must elapse between the start of each defrost (see page 15)
d1: Maximum defrost duration

The defrost will end after this time has elapsed since it started.
F3: Fan status during defrost

It defines the status of the fans during defrosting. 0= OFF 1= ON
A1: Maximum alarm probe 1

Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.

  • Minimum: –45.0 *
  • Maximum: 99 *

(Depends on the bottom/top locking of the set point).
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.

  • Minimum: –45.0 *
  • Maximum: 99 *

Depends on the bottom/top locking of the set point).

Operation

Compressor control

NORMAL OPERATION

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(15\)

CONTINUOUS CYCLE MODE
Use this function to cool the cold rooms before loading products. It is activated by pressing the O key for 5 seconds, the display shows the % icon while this mode is active.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(16\)

CHANGE OF SET POINT” FUNCTION
Modifies the set point value in the low-use periods of the refrigeration device. If this variation is positive (increases the value), the display will show the ECO icon.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(17\)

It can be activated after a certain time has elapsed (defined in parameter C11) without activity in the cold room door, to do this one of the digital inputs such as “door contact” (P10 or P11 = 1) must be configured. Optionally, you can activate and deactivate this mode at will, using an external pushbutton (1 press to activate/deactivate), configuring one of the digital inputs as “Change set point” (P10 or P11 = 4).
If we set parameter C11 to 0, it can only be activated by an external pushbutton.

COMPRESSOR PROTECTION DELAY
There are three types of delay, selectable by parameter C4, to protect the compressor. These delays prevent continuous compressor starts and stops due to sudden changes in temperature.
OFF-ON (C4=0): Minimum compressor OFF time before each start-up.
OFF-ON / ON-OFF (C4=1): Minimum time during which the compressor will remain ON and OFF in every cycle. The delay time is defined by parameter C5.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(18\)

OPERATION IN CASE OF PROBE 1 FAILURE
In the event of probe 1 failure (fault, disconnection, etc.) compressor performance will depend on C6 settings. Users may choose between 3 options:

  • C6=0: The compressor will be stopped until probe 1 is working again.
  • C6=1: The compressor will be operational until probe 1 is working again.
  • C6=2: The compressor will operate according to the average performance of the last 24 hours, taking into account the number of starts and stops and the average time in each state (stop-start).
  • C6=3: The compressor will run as scheduled in C7 (ON) and C8 (OFF).

SET POINT LOCKING
Using the C2 and C3 parameters, it is possible to set an upper and a lower limit for the Setpoint (SP), which precludes configuring a set point that is too low or too high that could damage the installation or the stored product.

STOP FANS AND COMPRESSOR WHEN THE DOOR IS OPENED
Parameter P23 defines whether the compressor stops when the cold room door is opened. To do so one of the digital inputs must be configured as “door contact” (P10 or P11=1) (See page 26).
If the door stays open longer than the value programmed in parameter P24, the compressor will return to its normal operation.

Defrost control

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(20\)
Defrost start-up Defrost is initiated if:

  • The time scheduled in parameter d0 has passed since the beginning of the last defrost.
  • The N key is pressed for 5 seconds.

Defrost type
By resistors: The defrost resistors start-up and the compressor stops; defrost is the result of heat from the resistors. Fans will be running or not depending on parameter F3.

Drip time
Parameter d9 sets drip time and the time added at the end of the defrost cycle to allow for drainage of the remaining water in the evaporator. During this time the compressor and fans will not be running (unless defrost is by air). Defrost termination

The defrost will terminate

  • The temperature programmed in parameter d4 has been reached in probe 2 Probe 2 must be activated (P4).
  • In the event of probe 2 failure, defrosting will be complete once the maximum time has elapsed (d1)
  • The time set in parameter d1 has passed (maximum duration of defrost).
  • The H key is pressed for 5 seconds.

Message displayed during defrost
Set by parameter d2, with the choice of showing the actual temperature detected by probe 1 (d2=0), displaying the temperature detected by probe 1 at the start of defrost (d2=1) or displaying the DEF message (d2=2). The d3 parameter defines the time during which the message is displayed, once the drip time (d9) and the fan stop time (F4) is over.

Other parameters
Parameter d5 allows users to specify if the unit will (d5=1) or will not (d5=0) defrost when powered up (initial start-up or after a power failure). In case of choosing option YES (d5=1), the defrost will start after the delay time specified in d6. Using parameter d8, users define the computation of time in d0, choosing between total time elapsed (d8=0) or the total compressor running time (d8=1).NOTE: If parameter d1 is set to 0, no defrost will be performed. Remote defrost This function allows activating the defrost of the unit using an external button, connecting it to one of the digital inputs that must be configured as “remote defrost”(P10 ó P11=6) .

Fan control

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(21\)

  • Fans are controlled with probe 2 (evaporator) and parameters F0 (shutdown temperature) and F1 (Probe differential).
  • Even if probe 2 is not connected or an error is detected in the probe (E2), the fans will always run regardless of parameters F0 and F1, but taking into account parameters F2 to F5.
  • Parameter F2 defines the status of the fans during compressor stops.
  • Parameter F3 defines the status of fans during defrost.
  • Parameter F4 defines the fan start-up delay after defrosting (see section 9.2)

Light control
Auxiliary relay 3 must be configured as “Light” (P63=1).
Switching the lights on or off is controlled using:

  • The ? pushbutton: One press switches the lights on or off.

  • The cold room door: When the door is opened, the lights stay on for the time
    defined by parameter P22. If the value is 0, when the door closes the lights go out. (One of the digital inputs must be configured as door contact (P10 or P11=1).

  • The control even occurs with the equipment in Stand-by.

Pump down function
This function prevents compressor problems caused by the movement of the refrigerant, using a stop/start technique of the unit controlled by liquid solenoid, the low-pressure switch and the compressor.
For this feature to be active, the auxiliary relay must be set as “Pump down” (P6=1).

SHUTOFF

  • When temperature probe 1 reaches the set point value (SP), the AUX 1 relay is deactivated by closing the liquid solenoid.
  • Since the compressor is still running the evaporator pressure drops suddenly. When it reaches a specific point, the low-pressure switch is activated, changing the state of digital input 1, and the controller stops the compressor. This maneuver isolates the refrigerant from the compressor crankcase, preventing serious damage on start-up. In case of a low-pressure switch failure, the controller stops the compressor after the safety time set at P15, showing the message “Pd”, but it will continue to function normally. (informative message, does not affect the equipment operation).
  • If time P15 is 0 (default value), the compressor will not stop until the low press start is activated, but it will display the “Pd” message after 15 minutes.
  • DOES NOT activate the alarm relay or the sound alarm, it is only shown on the display.

STARTUP
When temperature probe 1 reaches the set point value plus the differential (SP+C1), the AUX 1 relay is activated (ON), opening the liquid solenoid. This causes the pressure in the evaporator to increase, disabling the low-pressure switch. The controller detects this change and starts the compressor. If a period of time has elapsed (determined by P14) after the liquid solenoid is opened (AUX 1 relay set to ON), the low press start will not be deactivated, the controller will once again close the solenoid (AUX 1 relay set to OFF) and the “LP” message will be displayed. This maneuver will be repeated every 2 minutes indefinitely until the press start is deactivated and the installation reverts to its normal operation. If time P14 is 0 (default value), the solenoid will stay open until the low press start is deactivated, but it will display the “LP” message after 3 minutes. DOES NOT activate the alarm relay or the sound alarm, it is only shown on the display.

STAND-BY
If the pump-down function is active, some time may elapse from the time the stand-by function starts until the controller stops. This is because certain control phases of the system cannot be stopped.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(23\)

Alarms
The unit warns the user with a message on the screen of the activation of a relay or the activation of an acoustic signal in certain circumstances, according to the programming of the following parameters.

Max/Min Temperature Alarm

Shows the AH or AL message when the temperature in probe 1 reaches the value set in
the A1 (maximum temperature) or A2 (low temperature) parameters.

This value can be
Absolute (A0=1): A1/A2 should indicate the temperature at which the alarm should be activated.

Relative to SP (A0=0): A1/A2 should indicate the number of degrees above or below the set point at which the alarm is activated. This option allows users to adjust the set point without having to modify the high and low alarm settings. Parameter A10 sets the differentials for both parameters (hysteresis). Activates alarm relay (if P62=1) and sound alarm.

Example
In a controller, we configure the following parameters: SP=2, A1=10, A10=2

  • If A0=0 (relative to SP), the maximum temperature alarm goes off when probe 1 reaches 12 degrees and is disabled when it reaches 10 degrees.
  • If A0=1 (absolute), the maximum temperature alarm goes off when probe 1 reaches 10 degrees and is disabled when it reaches 8 degrees.

External alarm/severe external alarm

Displays the message AE (external alarm) or AES (severe external alarm), when the digital input configured as an external alarm or severe external alarm is activated. The severe external alarm also deactivates all the charges, therefore, the temperature regulation is stopped. When this alarm disappears the device returns to its normal operation. At least one of the digital inputs must be configured as an external alarm (P10 or P11=2) or severe external alarm (P10 or P11=3). Activates alarm relay (if P62=1) and sound alarm.

Defrost alarm completed by time
Shows the Adt alarm message when a defrost terminates by time-out, if parameter A8=1. DOES NOT activate the alarm relay or the sound alarm, it is only shown on the display.

Door open alarm
Displays the PAb message when the door stays open for a time greater than that set with parameter A12. (One of the digital inputs must be configured as door contact (P10 or P11=1). Activates alarm relay (if P62=1) and sound alarm.

Pump down malfunction error (Stop)

Displays the Pd message if a malfunction is detected when the installation is stopped using the pump down maneuver. (See page 17). DOES NOT activate the alarm relay or the sound alarm, it is only shown on the display.

Pump down malfunction error (Startup)

Displays the LP message if a malfunction is detected when the installation is started up using the pump down maneuver. (See page 17). DOES NOT activate the alarm relay or the sound alarm, it is only shown on the display. Compressor safety chain alarm The ASC message is displayed if any component in the compressor’s safety chain is triggered (compressor motor guard, thermistors or high-pressure controller). Regulation is stopped until protection has been restored.

Alarm delay
These delays prevent the display of specific alarms while allowing the unit to recover normal operation after certain events.

  • Start-up delays (A3): Delays activation of temperature alarms on power-up (start-up or after a power failure). This allows for avoiding continuous alarms upon start-up
  • Delay after defrost (A4): Delays activation of temperature alarms post-defrost.
  • Delay of max/min temperature alarm (A5): Delays activation of maximum (A1) and minimum (A2) temperature alarms from the moment temperature probe 1 reaches the set value.
  • Delay of external alarm activation (A6): Delays the activation of the external alarm from the moment the digital input becomes active.
  • Delay of external alarm deactivation (A7): Delays the deactivation of the external alarm from the moment the digital input becomes inactive.
  • Door opening alarm relay (A12): Delays activation of the open door opening detection alarm.

Alarm relay configuration

  • If the auxiliary relay 2 is configured as an alarm relay (P62=1), parameter A9 allows defining the status of the relay when an alarm is triggered.
  • A9=0 relay active (ON) in case of alarm (no alarm OFF)
  • A9=1 Inactive relay (OFF) in case of alarm (no alarm ON)

Access code (password)
It allows protection the configuration of the unit using a 2-digit code (from 01 to 99). If it is active a code is requested when you try to access the programming menu. This menu cannot be accessed if a wrong value is entered. The code is defined using the L5 parameter. Parameter P2 defines the operation of this code.

Parameter transfer

This function allows transferring the programmed parameters from one device to another, using the AKO-D14918 programming key. This will save a lot of time when configuring similar devices.
Requires the use of the AKO-80018 power supply for the programming key.AKO-
1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig- \(28\)
Transfer parameters from the equipment to the key

  • Disconnect the unit power supply.
  • Connect the programming key in the parameter server connector.
  • Connect the power supply for the programming key.
  • Press the READ key on the programming key.
  • Disconnect the device programming key.

Transfer parameters from the key to the equipment

  • Disconnect the unit power supply.
  • Connect the programming key in the parameter server connector.
  • Connect the power supply for the programming key.
  • Press the RECORD key for the programming key.
  • Disconnect the device programming key.

Connectivity

The unit has a port for RS485 data connection (MODBUS), which can be managed using a PC. Up to 127 units can be connected to a PC with AKONet (AKO-5010), or to the AKO-5011 web server. Each of these units should have a different MODBUS address, that is defined using the P5. Using the AKONet software it is possible to display and capture the data of any connected unit, and configure its parameters.
AKONet: Management software for AKO units with RS485 (MODBUS) communication. If it is installed in a server the software can be accessed from any PC in the network or even from the Internet (it requires the server to have a connection to the Internet and a fixed IP).
AKO-5011: Web server that includes the AKONet software. It can carry out the same functions as the PC, with the advantage of having a server dedicated to communication with the units.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(29\)

Advanced configuration
Using the advanced configuration menu, you can set ALL the equipment’s parameters. The parameters are grouped into 6 sections depending on their function. Press the N + Q keys for 10 seconds to access it. If the access code is activated, a 2 digit code is requested (See page 19), if the code entered is incorrect the unit will not enter programming mode. To see the complete parameters list, refer to page 23. After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.

AKO-1569x-PROPlus-3PH-BASIC-Electronic-Panel-fig-
\(30\)

Advanced configuration

Return to initial parameters
This function configures all the unit’s parameters to its default values, i.e., as it leaves the factory. in order to return the computer to its initial settings, go to the programming menu and set parameter P3 to 1. The computer will now restart with its factory settings.WARNING: Any change made in the unit’s configuration will be lost.

Program version
The PU and PR settings allow the version and review of the firmware installed in the equipment to be displayed. Use this information if you have to ask for advice from the technical assistance service.

Parameters
The parameters are grouped into 6 sections depending on their function. Press the N + Q keys for 10 seconds to access it. The Def. column shows factory-set default parameters. Temperature values are expressed in ºC. (Equivalent temperature in ºF)

Level 1.- REGULATION AND CONTROL

  Description Units Min Def Max.
SP Temperature Adjustment (Set Point) (Pág. 13) (ºC/ºF) -45 0.0 99
C0 Calibrating probe 1 (Offset) (Pág. 13) (ºC/ºF) -20.0 0.0 20.0
C1 Probe 1 differential (Histeresis) (Histéresis) (Pág. 14) (ºC/ºF)
0.1 2.0 20.0
C2 Upper blocking of the set point (Page 14) (cannot be set above this
value) (ºC/ºF) C3 99 99
C3 Lower blocking of the set point (Page 14) (cannot be set below this
value) (ºC/ºF) -45 -45 C2

C4

| Type of delay for protection of the compressor (Page 14)

0 =OFF/ON (since the last disconnection);

1 =OFF-ON/ON-OFF (since the last shut-down /start-up)

|  | ****

0

| ****

0

| ****

1


C5

| Protection                       delay                         time (value of the option selected in parameter C4) (Page14)| ****

(min.)

| ****

0

| ****

0

| ****

120


C6

| Status  of  COMP.  relay  with   probe   fault   (Page   14): 0 =OFF; 1 =ON; 2 =Average based on last 24 hours prior to probe fault; 3 =ON-OFF as prog. C7 and C8|  | ****

0

| ****

2

| ****

3

C7| Time relay ON  in  case  of  faulty  probe  (Page  14): (If C7=0 and C8¹0, the relay will always be OFF deenergised)| (min.)| 0| 10| 120
C8| Time relay OFF in case of fault of probe 1 (Page 14): (If C8=0 y C7¹0, the relay will always be ON energised)| (min.)| 0| 5| 120
C9| Maximum duration of the continuous cycle mode. ( 0 =disabled) (Page. 14)| (h.)| 0| 0| 48


C10

| Variation of the set point (SP) in continuous cycle mode, when it reaches this point (SP+C10), it reverts to the normal mode.  (Page  13)  (SP+C10  ³ C3) ( 0 =OFF) The value of this parameter is always negative, except if it is 0| ****

(ºC/ºF)

| ****

0

| ****

-50

| ****

C3-SP

C11| Idle time of the digital input for the change Set Point function to be activated (Only if P10 or P11 =1) ( 0 =OFF) (Page 13)| (h.)| 0| 0| 24
C12| Variation of the set point (SP) when the change set point function is active. (SP+C12 £ C2) ( 0 = disabled) (Page 13)| (ºC/ºF)| C3-SP| 0,0| C2-SP
EP| Exit to Level 1|  |  |  |

Level 1.- DEFROST CONTROL

Description Units Min Def Max

  • d0 Defrost frequency (Time between two starts) (Page 15) (h.) 0 6 96
  • d1 Maximum defrost duration (0=defrost deactivated) (Page 15) (min.) 0 15 255
  • d2 Type of message during defrost: (Page 15)
  • 0=Current temperature; 1=Temperature at start of defrost; 2=Display dEF message
  • 0 2 2d3 Maximum duration of message
  • (Time added at the end of the defrost process) (Page15) (min.)
  • 0 5 255d4 Defrost end temperature (probe 2) (If P4 ¹ 1) (Page. 15) (ºC/ºF) -45 8.0 99,0
  • d5Defrost on equipment start-up (Page16):
  • 0=NO, First defrost as per d0
  • 1=YES, First defrost as per d6
  • 0 0 1d6 Defrost start delay on equipment start-up (Page 16) (min.) 0 0 255
  • d8 Calculated time between defrost period (Page 16):
  • 0=Total actual time; 1 =Sum of times the compressor is on 0 0 1d9
  • Drip time at end of defrost (Page 15) (compressor and fans off) (if P4 ¹ 1) (min.) 0 1 255
  • EP Exit Level 1

Level 1.- FAN CONTROL

  Description Units Min Def Max.
F0 Fan shut-down temperature as per probe 2 (if P4 ¹ 1) (Page 16)
(ºC/ºF) -45 45 99,0
F1 Probe 2 differential (If P4 ¹ 1) (Page16) (ºC/ºF) 0,1 2,0 20,0
F2 Stop fans when stopping compressor 0 =No, 1 =Yes (Page 16)
0 1 1
F3 Fan status during defrost: (Page 16)

0 =Off; 1 =On

|  | 0| 0| 1
F4| Starting delay after defrost (if F3=0) (Page 16) Will only operate if it is higher than d9| (min.)| 0| 3| 99
EP| Exit Level 1

Level 1.- ALARM CONTROL

Description Units Min Def Max.

  • A0 Configuration of temperature alarms (Page 18): 0=Relative to SP 1=Absolute 0 1 1
  • A1 Maximum alarm probe 1 (must be greater than SP) (Page 18) (ºC/ºF) A2 99,0 99,0
  • A2 Minimum alarm probe 1 (must be greater than SP) (Page 18) (min.) -45 -45 A1
  • A3 Temperature alarm delay during start-up (Page 19) (min.) 0 0 120
  • A4 Temperature alarm delay after completion of a defrost (Page 19) (min.) 0 0 99
  • A5 Temperature alarm delay after reaching the value of A1 or A2 (Page 19) (min.) 0 30 99
  • A6 External alarm delay when receiving a digital input signal (P10 or P11=2 or 3) (Page 19) (min.) 0 0 120
  • A7 Deactivation delay of the external alarm when the signal of the digital input disappears (P10 or P11=2 or 3) (Page 19) (min.) 0 0 120
  • A8 Show warning if defrost is terminated by time-out 0=No, 1=Yes (Page 18) 0 0 1
  • A9 Alarm relay polarity 0= Relay ON in alarm (OFF no alarm);
  • (Page 19) 1= Relay OFF on alarm (ON with no alarm) 0 0 1
  • A10 Temperature Alarm Differential (A1 and A2) (Page 18) (ºC/ºF) 0,1 1,0 20,0
  • A12 Door open alarm delay (if P10 or P11=1) (Page 19) (min.) 0 10 120
  • EP Exit Level 1

Level 1.- GENERAL STATUS

  Description Units Min Def Max.
P1 Delay of all functions on receiving electrical power (min.) 0 0

255
P2| Función del código de acceso (password)

0 = Inactivo; 1 = Bloqueo acceso a parámetros; 2 = Bloqueo del teclado

|  | 0| 0| 2
P3| Configures the default factory settings

0 = No changes 1 =Return to default settings

|  | 0| 0| 1
P4| Selection of type of inputs         1 =1 probe 2 =2 probes| | 1| 2| 2
P5| MODBUS address (Page 21)|  | 1| 1| 225
P6| AUX 1 relay configuration                               0 =Deactivated 1 =Pump down                 2 = Same compressor status| | 0| | 2
P62| AUX 2 relay configuration                              0 =Deactivated                   1 =Alarm     2 = Same compressor status 3 =Same unit status            4 =Pump down|  | 0|
| 4
P63| AUX 3 relay configuration                              0 =Deactivated                   1 =Light 2** =Same unit status|  | 0| 1| 2


P7

| Temperature display mode

0 =Integers in ºC      1 =One decimal in ºC 2 =Integers in ºF 3 =One decimal in ºF

|  | ****

0

| ****

1

| ****

3

P8| Probe to be displayed (as per parameter P4)

0 =visualization of all the probes in sequence;          1 =Probe 1 2 =Probe 2

|  | 0| 1| 2

See table page 26.

The options available in each setting can vary depending on the model.Description Units Min Def Max.

  • P1 Delay of all functions on receiving electrical power (min.) 0 0 255
  • P2 Función del código de acceso (password)
  • 0= Inactivo; 1= Bloqueo acceso a parámetros; 2= Bloqueo del teclado 0 0 2 P3
  • Configures the default factory settings
  • 0= No changes 1=Return to default settings 0 0 1
  • P4 Selection of type of inputs 1=1 probe 2=2 probes 1 2 2
  • P5 MODBUS address (Page 21) 1 1 225
  • P6 AUX 1 relay configuration** 0=Deactivated
  • 1=Pump down 2= Same compressor status 0 * 2
  • P62 AUX 2 relay configuration** 0=Deactivated 1=Alarm
  • 2= Same compressor status 3=Same unit status 4=Pump down 0 * 4
  • P63 AUX 3 relay configuration** 0=Deactivated 1=Light 2=Same unit status 0 1 2 P7
  • Temperature display mode
  • 0=Integers in ºC 1=One decimal in ºC
  • 2=Integers in ºF 3=One decimal in ºF 0 1 3
  • P8 Probe to be displayed (as per parameter P4)
  • 0=visualization of all the probes in sequence; 1=Probe 1 2=Probe 2

Nivel 1.- ACCESS CONTROL AND INFORMATION (tid)

Lev Description Units Min Def Max.
L5 Access code (Password) (Pág 19)   0 0 99
PU Program version (Information)    
Pr Program revision (Information)    
EP Exit Level 1

Default parameters according to models

  Parameter
  P11
AKO-15690/1/2/3 0 =Deactivated
AKO-15697 0 =Deactivated

=Alarm
AKO-15699/699-1| 2 = External alarm| 2 = Same compressor status| 1 =Alarm
AKO-15690/1/2/3-EVC| 0 =Deactivated| 0 =Deactivated| 4 =Pump down
AKO-15697-EVC| 0 =Deactivated| 0 =Deactivated| 2 = Same compressor status
AKO-15699-EVC| 2 = External alarm| 0 =Deactivated| 2 = Same compressor status

Technical specifications

  • Rated voltage Un…………………………………………………………………………………………400 V~ ±10 % 50/60 Hz ±5 %
  • Rated voltage Ue…………………………………………………………………………………………230 V~ ±10 % 50/60 Hz ±5 %
  • ALARM relay …………………………………………………………………………………………………………… 8A at 250V, cosj=1
  • Probe temperature range……………………………………………………………………………………………..–45.0 ºC to 99.9 ºC
  • Resolution, setting, and differential ………………………………………………………………………………………………….0.1 ºC
  • Thermometric precision…………………………………………………………………………………………………………………± 1 ºC
  • Precision of the NTC probe at 25 ºC ……………………………………………………………………………………………….± 0.4 ºC
  • Input for NTC probe ……………………………………………………………………………………………………………..AKO-14901
  • Maximum input power in the operation …………………………………………………………………………………………….30 VA
  • Working ambient temperature………………………………………………………………………………………………-5 ºC to 40 ºC
  • Storage ambient temperature …………………………………………………………………………………………….–30 ºC to 70 ºC
  • Overvoltage category…………………………………………………………………………………….II s/ EN 61439-1 / EN 61439-2
  • Degree of pollution ……………………………………………………………………………………….II s/ EN 61439-1 / EN 61439-2
  • Degree of protection ………………………………………………………………………………………………………………………IP65
  • Dimensions ……………………………………………………………………………………………….400(An) x 300(Al) x 135(P) mm
  • Double isolation between the power supply, secondary circuit, and relay output.
  • Type of assembly………………………………………………………………………………………………………………..Fixed internal
  • Internal buzzer
  • Encapsulated assembly

AKO ELECTROMECÁNICA , S.A.L.
Avda. Roquetes, 30-38
08812 Sant Pere de Ribes.
Barcelona Spain.
www.ako.com

We reserve the right to supply materials that might vary slightly from those described in our Technical Sheets. Updated information is available on our website.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals