Aprilaire Dehumidifier E080 & E100 Instruction Manual
- June 6, 2024
- Aprilaire
Table of Contents
Dehumidifier E080 & E100
Model E080 & E100 Dehumidifier
Installation Instructions
SAFETY INSTRUCTIONS WARNING
1. 120 Volts may cause serious injury from electric shock. Disconnect
electrical power before starting installation or servicing. Leave power
disconnected until installation/service is completed.
2. Sharp edges may cause serious injury from cuts. Use care when cutting
plenum openings and handling duct work. 3. Dropping may cause personal injury
or equipment damage. Handle with care and follow installation instructions.
CAUTION
1. Read all instructions before beginning installation. 2. Improper
installation may cause property damage or injury. Installation, service, and
maintenance must be performed by a qualified service
technician. 3. Do not use in pool applications. Pool chemicals can damage the
dehumidifier. 4. Do not use solvents or cleaners on or near the circuit board.
Chemicals can damage circuit board components. 5. Wait 24 hours before running
the unit if it was not shipped or stored in the upright position 6. Do not use
dehumidification to prevent window condensation in the winter. To address
window condensation, use ventilation to lower
indoor humidity in the winter. 7. This appliance is not intended for use by
persons (including children) with reduced physical, sensory or mental
capabilities, or lack of
experience and knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person responsible for their
safety. 8. Children should be supervised to ensure that they do not play with
the appliance. 9. If the supply cord is damaged, it must be replaced by a
special cord or assembly available from the manufacturer or its service agent.
PLEASE READ AND LEAVE THIS MANUAL WITH THE HOMEOWNER
1
SAFETY INSTRUCTIONS
SAFETY INSTRUCTIONS 1 SPECIFICATIONS 3 SET UP DEHUMIDIFIER FOR INSTALLATION 3
Duct Collars 4 Control Location 5 HARD WIRING E080H & E100H 6 Electrical
Specifications for Hard Wiring 6 Wiring Instructions 7 LOCATION CONSIDERATIONS
8 DRAIN INSTALLATION 8 Leveling 9 Condensate Pan, Condensate Pump and Float
Switch 9 DUCTING TO HVAC SYSTEM BASEMENT AND ATTIC INSTALLATIONS 10 DUCTING
TO HVAC SYSTEM CLOSET INSTALLATIONS 11 DUCTING FOR STAND ALONE INSTALLATIONS
OR NON-DUCTED INSTALLATIONS 11 DUCTING FOR TWO ZONE INSTALLATIONS 12 MODEL 76
EXTERNAL CONTROL OR CRAWL SPACE/SEALED ATTIC CONTROL AND WIRING 13 WIRING
THE DEHUMIDIFIER TO THE HVAC SYSTEM AND ZONE DAMPERS 14 SYSTEM SET-UP AND
CHECKOUT 15 Installer Test Mode 17 START UP AND SEQUENCE OF OPERATION 18
Single Zone Whole House or Stand Alone Using the Dehumidifier Control 18
Single Zone Whole House or Stand Alone Using Model 76 External Control 18
Crawl Space or Sealed Attic (Remote) Control Using Model 76 18 Two Zone
Primary and Secondary 18 VENTILATION 19 Installation and Wiring 19 Vent Auto &
Vent-Timed 20 Outdoor Temperature Sensor Installation 20 Determine Ventilation
Requirements 21 Installer Settings 22 Sequence of Operation 23 TROUBLESHOOTING
24 Table 4 Diagnostic Codes 24 Table 5 Troubleshooting Guide 26 SERVICE
PARTS 27
2
SPECIFICATIONS
Unit Weight Shipping Weight Capacity 80°F, 60% RH Conditions Power 115 VAC,
Single Phase, 60Hz Dehumidifier Inlet Air Conditions Filter
Airflow
MODEL E080 63 lbs 81 lbs
80 pints per day @ 185 CFM
MODEL E100 64 lbs 82 lbs
100 pints per day @ 280 CFM
51A operating current
69A operating current
Dehumidification: 50°F 104°F, 40°F dew point minimum Ventilation: 40°F 140°F, 0%RH 99%RH (non-condensing)
MERV 8, washable
External Static Pressure (“w.c.)
Airflow (CFM)
External Static Pressure (“w.c.)
00
185
00
02
135
02
04*
85
04
06*
Airflow (CFM) 280 245 210 175
NOTE: Rated capacity and current draw measured at 80°F/60% RH inlet conditions at 0.0 external static pressure. *Maximum design external static pressure.
SET UP DEHUMIDIFIER FOR INSTALLATION
IMPORTANT: Cut the strap securing the compressor
shipping support bracket and remove the strap and shipping bracket See FIGURE
1
FIGURE 1 REMOVE SHIPPING BRACKET REMOVE SHIPPING BRACKET
CLIP OFF PLASTIC STRAP
90-1908
3
DUCT COLLARS
STANDARD BASEMENT AND ATTIC INSTALLATIONS (FULLY DUCTED)
· Use the screws in the parts bag to attach the duct collars to the inlet and
outlet of the dehumidifier The outlet collar has a backflow damper
· The outlet duct collar may be attached to the top or end of the unit Move
the outlet cover to the location not being used See FIGURE 2
· Make sure there are no bends in the ductwork coming off the outlet for a
minimum of 4″ This will ensure that the ductwork will not interfere with the
backflow damper function
CLOSET INSTALLATIONS
Use the screws provided in the parts bag to attach the duct collars if desired
or required based on recommendations below:
· Where inlet space is restricted, the inlet duct collar is optional
· When the dehumidifier is installed below the HVAC equipment and requires a
vertical discharge, move the top access panel to the end of the unit The
outlet duct collar with backflow damper is not required See FIGURE 3
· When the dehumidifier requires a ducted vertical discharge, remove the top
access panel and remount on the outlet of the unit Install the outlet duct
collar with backflow damper on top of the unit See FIGURE 3
CRAWL SPACE, SEALED ATTICS OR BASEMENT INSTALLATIONS
If dehumidifying the space in which the dehumidifier is installed, the duct
collars do not need to be installed Leave the outlet cover on top of the unit
See FIGURE 4
FIGURE 2 FULLY DUCTED INSTALLATIONS
INLET DUCT COLLAR
OUTLET COVER
OUTLET DUCT COLLAR W/BACK DRAFT DAMPER
INLET DUCT COLLAR
END DISCHARGE
MOVE OUTLET COVER AND INSTALL OUTLET DUCT COLLAR TO TOP DISCHARGE LOCATION
TOP DISCHARGE
90-1909
FIGURE 3 CLOSET INSTALLATIONS
UNDUCTED INLET
UNDUCTED OUTLET
OUTLET COVER
FIGURE 4 NON-DUCTED INSTALLATIONS OUTLET COVER
UNDUCTED INLET
OUTLET DUCT COLLAR W/BACK DRAFT DAMPER
OUTLET COVER
90-1910
90-1911
4
CONTROL LOCATION
The on-board control can be located on the top of the dehumidifier or can be
relocated to the front of the dehumidifier if the control cannot be
seen/accessed in the top orientation It may also be rotated 180 degrees in
either orientation as shown in FIGURE 6
TO MOVE THE CONTROL
1. Remove the front control panel cover
FIGURE 5 CONTROL LOCATION
CONTROL
CONTROL PANEL COVER
CONTROL PANEL COVER
CONTROL
2. Remove the filter access door and filter
3. Detach the on-board control by removing the four (4) screws around the control NOTE: Use one hand to support the bottom of the on-board control when removing
4. Keep the control in the unit and relocate to the front access hole
5. Secure the control with the same four screws used to attach the control to
the top of the unit
FILTER ACCESS DOOR
90-1884
6. Secure the control panel cover to the top of the unit
NOTE: E100V UI can be rotated but not relocated
FIGURE 6 CONTROL ROTATED 180 DEGREES
90-2525
5
HARD WIRING E080H & E100H
WARNING
ELECTRICAL SHOCK HAZARD: 115-volts may cause serious injury or death from
electrical shock. Disconnect and tag electrical service before starting
installation or field-service. Leave electrical service disconnected until
installation or field-service is complete. ELECTRICAL SHOCK HAZARD: An
interrupted or broken ground may cause property damage, serious injury or
death should an electrical fault occur. The cabinet must be grounded in
accordance with NEC ANSI/NFPA 70-2011 or local codes. In Canada, refer to
Canadian Electrical Code CSA C22.1. FIRE HAZARD: Use of improper wire may
cause serious injury, property damage or death due to fire. Do not use
aluminum wire for electrical service to the dehumidifier. Use only copper
wire.
CAUTION
Use of an undersized circuit breaker may cause property damage and/or the need
for mold remediation service. See SPECIFICATIONS for wire and circuit breaker
sizing.
The Model E080H and the Model E100H must be hard wired An electrical
disconnect switch can be installed as needed to comply with appropriate codes
or ordinances The ON/OFF switch on the dehumidifier interrupts the 115 VAC
service to the internal components of the dehumidifier, but does not
disconnect the power supply at the 115 VAC terminals on the dehumidifier
United States Installations: Make all electrical connections in accordance
with the current edition of the NEC ANSI/NFPA 70 and any local codes or
ordinances that may apply Canada Installations: Make all electrical
connections in accordance with the current edition of the Canadian Electrical
Code CSA C221 and any local codes or ordinances that may apply
ELECTRICAL SPECIFICATIONS FOR HARD WIRING
Voltage Minimum Circuit Ampacity (MCA) Maximum Fuse or Circuit Breaker Amps (MOP) Minimum Wire Size AWG
MODEL E080H 110-120 VAC, 60 Hz, 1 phase
9A 16A 14
MODEL E100H 110-120 VAC, 60 Hz, 1 phase
12A 20A 14
6
WIRING INSTRUCTIONS
1. Disconnect electrical service at the main fuse or circuit breaker box
2. Install any code required disconnects to the line service within eyesight
of the appliance
3. Remove the side panel and electrical service panel from the dehumidifier
See FIGURE 7
4. Route the service cable through the 7/8″ diameter hole where the power
cord was removed USE ONLY COPPER SUPPLY WIRES
5. Secure the cable/conduit to the dehumidifier using fittings/ connectors
approved for the type of cable/conduit used
6. Connect the ground wire of the service cable to the ground lug in the
electrical service box See FIGURE 8
7. Connect the line voltage wires of the service cable to the LINE BLK and
NTRL WHT terminals See FIGURE 8
8. Reattach the electrical service panel and side panel
9. Restore electrical service at the main fuse or circuit breaker box
FIGURE 7 ELECTRICAL SERVICE BOX LOCATION SIDE PANEL
ELECTRICAL SERVICE BOX
90-2609
FIGURE 8 HARD WIRE TO 115 VAC SERVICE
ELECTRICAL SERVICE BOX
115V AC WIRING TERMINALS
GROUND LUG LINE SERVICE CABLE/CONDUIT
NEUTRAL LINE VOLTAGE
FITTING AS REQUIRED
GROUND
90-2609
7
LOCATION CONSIDERATIONS
· Allow sufficient clearance for filter removal and to prevent airflow
obstruction
· Electrical service access will require the removal of the side panel shown
Allow sufficient space for service on this side of the unit
· If locating the unit in an attic or crawl space, a Model 76 Control mounted
in the living space is recommended
· For attic installations, it is recommended that the dehumidifier be
suspended
· Always install the dehumidifier in a condensate pan when locating in or over
a finished space
FIGURE 9 FILTER ACCESS CLEARANCE
ELECTRICAL SERVICE ACCESS THIS SIDE
6 FT. POWER CORD
FILTER
TOP VIEW
6″ MINIMUM CLEARANCE FOR PROPER AIR FLOW
15″ MINIMUM CLEARANCE FOR FILTER (EITHER SIDE)
90-1840
DRAIN INSTALLATION
The drain outlet on the dehumidifier can be hard piped using a 3/4″ PVC Slip x
3/4″ MNPT fitting and 3/4″ nominal drain tubing or the provided 3/4″ MNPT x
3/4″ hose barb fitting 3/4″ clear PVC tubing can be used to drain the
dehumidifier Always maintain a constant downward slope from the dehumidifier
to the drain and do not allow soft tubing to curl up which may result in air
lock NOTE: PTFE thread seal tape is recommended for the threaded connection
and hand tighten only If hard pipe is used, PVC primer and cement is
recommended for the slip fit connection Remove drain insert before priming and
gluing in the PVC fitting Replace drain insert after PVC glue has fully dried
CAUTION
Do not damage drain cover. The drain cover is a critical feature of the
dehumidifier drain management system.
WARNING
Running the dehumidifier without the drain insert can lead to condensate
leaks. See FIGURE 10.
8
FIGURE 10 DRAIN INSERT
DRAIN INSERT
LEVELING
The feet can be adjusted to level the unit and accommodate drain fittings and
secondary condensate pans as required Refer to top mounted bubble level and
adjust feet until bubble is within the outer circle Leveling is required to
ensure proper drainage from the dehumidifier See FIGURE 11
FIGURE 11 LEVEL THE UNIT
BUBBLE LEVEL
0.38″ MIN 2.00″ MAX
3/4″ DRAIN
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
Always install the dehumidifier in a condensate pan when locating in or above
a finished space Adhere to local codes regarding draining of the condensate
pan If a condensate pump is needed, install it in the condensate pan as well
Install a condensate overflow safety switch (ie float switch) in the
condensate pan, remove the factory installed jumper wire between the Float
Switch terminals on the control and wire the float switch to the dehumidifier
as shown in FIGURE 12 Overflow safety switches on condensate pumps can be
wired to the Float Switch terminals in a similar fashion
FIGURE 12 FLOAT SWITCH WIRING
FLOAT DH DH Switch
NORMALLY CLOSED FLOAT SWITCH
90-2607
90-2592
90-1857
9
DUCTING TO HVAC SYSTEM BASEMENT AND ATTIC INSTALLATIONS
The Preferred Installation is to duct the dehumidifier to pull air from and
return dehumidified air to the HVAC return duct This installation will ensure
warm, dehumidified air is thoroughly mixed with the HVAC system air before
being discharged into the living space Alternatively, the dehumidifier can be
ducted to discharge to the supply duct, but the external static pressure of
the HVAC system must not exceed 04″wc for the E080 and 06″wc for the E100
REQUIRED COMPONENT
· 10″ ductwork
FIGURE 13 PREFERRED BASEMENT INSTALLATION
FIGURE 14 ALTERNATE BASEMENT INSTALLATION
10″ DUCT
AIR IS PULLED
FROM AND
SUPPLIED TO THE
6 ft
RETURN DUCT
MIN
HVAC/FURNACE
MODEL E100 0.6″ w.c. MAX MODEL E080 0.4″ w.c. MAX
AIR IS PULLED FROM RETURN DUCT
AIR IS DISCHARGED TO SUPPLY DUCT
HVAC /FURNACE
DEHUMIDIFIER
90-1886
10″ DUCT
90-1887
FIGURE 15 PREFERRED ATTIC INSTALLATION
AIR HANDLER
PLENUM BOX OR Y-FITTING 6 FT. MIN.
FIGURE 16 ALTERNATE ATTIC INSTALLATION
PLENUM BOX
MODEL E100 0.6″ w.c. MAX.
MODEL E080 0.4″ w.c. MAX.
AIR HANDLER
PLENUM
FILTER 10″ DIA. INSULATED DUCT
BOTH SIDES
90-1888
CONDENSATE PAN
24″ MIN. 10″ DIA. INSULATED DUCT
BOTH SIDES
90-1889
FILTER CONDENSATE PAN
DUCTING NOTES
· Use insulated duct when the dehumidifier is located in an unconditioned
space such as an attic or a garage · Use a minimum of 12″ of flex duct at the
dehumidifier inlet and outlet to prevent vibration noise transmission · When
ducting return to return (preferred), the dehumidifier must be wired to turn
on the HVAC fan when operating (see page 14) · When ducting return to supply,
allow adequate space before the first branch duct to ensure the warm
dehumidified air is thoroughly mixed with the
HVAC system air
10
DUCTING TO HVAC SYSTEM CLOSET INSTALLATIONS
The dehumidifier in these applications is typically installed under or next to
the HVAC equipment In both types of installation, the dehumidifier inlet is
not ducted and pulls from the living space through a grille or louvers in the
HVAC closet door The Preferred Installation is to locate the dehumidifier
under the HVAC equipment and supply dehumidified air through the alternate
outlet on the top of the unit directly to the HVAC return NOTE: The
dehumidifier must be wired to activate the HVAC fan during dehumidifier
operation in this installation In the Alternate Installation the dehumidifier
is located next to the HVAC equipment and ducted to the HVAC supply duct using
the outlet on the top of the unit The supply side external static pressure of
the HVAC system must not exceed 04″wc for the E080 and 06″wc for the E100
CAUTION
When installing the dehumidifier as part of a combustion type furnace (gas,
oil, propane, etc.) HVAC system located in a closet, duct or locate the
dehumidifier inlet and outlet and seal as needed to separate the circulation
air from the combustion and ventilation air. Follow all local and national
building and safety codes when installing or modifying any HVAC system.
OPTIONAL COMPONENT · 10″ Ductwork
FIGURE 17 PREFERRED CLOSET INSTALLATION
FIGURE 18 ALTERNATE CLOSET INSTALLATION
MODEL E100 0.6″ w.c. MAX
MODEL E080 ‘ ¡$ w.c. MAX
HVAC
HVAC
90-1891
90-1890
DUCTING FOR STAND ALONE INSTALLATIONS OR NON-DUCTED INSTALLATIONS
In this installation the dehumidifier is not ducted to the HVAC system and is
used to dehumidify a specific area This installation is typically in basements
or crawl spaces
OPTIONAL COMPONENTS
· 10″ ductwork · Grilles with 10″ duct collars
FIGURE 19 STAND ALONE DUCTED DEHUMIDIFIED AIR IS SUPPLIED TO DUCTED SPACE
DEHUMIDIFIED SPACE
10 FT. MIN
AIR IS PULLED FROM DUCTED SPACE
DEHUMIDIFIER GRILLE WITH 10″ DUCT COLLAR (2 PLACES)
90-1893
11
DUCTING FOR TWO ZONE INSTALLATIONS
NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications
In this installation the dehumidifier controls the humidity in two separate
zones, a Primary and Secondary Zone The dehumidifier will dehumidify the
Primary Zone as the first priority, and will switch to the Secondary Zone
after the dehumidification needs of the Primary Zone have been satisfied
IMPORTANT: Normally Closed dampers must be installed in the ducts serving the
Primary Zone and Normally Open dampers installed in the ducts serving the
Secondary Zone.
REQUIRED COMPONENTS
· 10″ ductwork and fittings
· Grilles with 10″ duct collars
· Drain line
· 2 Aprilaire Model 6510, 10″ Normally Closed damper
· 2 Aprilaire Model 6610, 10″ Normally Open damper
· 24 VAC transformer (40 VA min) for dampers
NOTE: 5442 Basement Kit includes 2 6510 Dampers, 2 6610 Dampers and a 24
VAC (40VA) transformer
FIGURE 20 WHOLE-HOME PRIMARY ZONE INSTALLATION
RETURN FROM SECONDARY
ZONE
TO / FROM PRIMARY ZONE
NORMALLY CLOSED
DAMPERS
RETURN DUCT
6 ft MIN
NORMALLY OPEN DAMPER
FIGURE 21 WHOLE-HOME SECONDARY ZONE INSTALLATION
SUPPLY DUCT
SUPPLY TO SECONDARY
ZONE
NORMALLY OPEN DAMPER
90-1875
RETURN DUCT
TO/FROM SECONDARY ZONE
SUPPLY DUCT
NORMALLY OPEN DAMPER
NORMALLY
RETURN FROM PRIMARY ZONE
OPEN DAMPER
SUPPLY TO PRIMARY ZONE
NORMALLY CLOSED DAMPER
NORMALLY CLOSED DAMPER
90-1895
12
MODEL 76 EXTERNAL CONTROL OR CRAWL SPACE/SEALED ATTIC CONTROL AND WIRING
NOTE: Use 18-22 AWG wire for control wiring
EXTERNAL CONTROL
Used as an external control, the Model 76 is mounted in the space that is to
be dehumidified When the dehumidifier is powered, the display on the
dehumidifier control will show EXTERNAL to indicate that an external control
is being used External controls are recommended when the dehumidifier is
installed in an attic and is ducted to the HVAC system
FIGURE 22 MODEL 76 EXTERNAL CONTROL WIRING NO/NC SWITCH
NC NO
+ – A B ODT VENT DEH Remote Sensor Dampers
FLOAT DH DH Switch
Gh Rf Cf Gs W Y HVAC EQUIP.
The Model 76 uses a normally open (NO), dry contact (ie not a triac or other semiconductor) relay to complete the circuit between the DH terminals of the dehumidifier control If using other controls such as a thermostat with dehumidification outputs, ensure the output is a dry contact type and set the NO/NC switch on the dehumidifier control (see FIGURE 22) to correspond with the control being used The Aprilaire Model 8620 Thermostat or Model 8910 Home Comfort Control are recommended alternate controls and both use normally open contacts
MODEL 76 CONTROL
A B C/R/+ DH DH
If an external control is used in a zoned application, it
must be located in the Primary Zone (refer to the TWO
90-1862
ZONE PRIMARY AND SECONDARY section on page
18 for details)
CRAWL SPACE/SEALED ATTIC CONTROL
FIGURE 23 MODEL 76 CRAWL SPACE/SEALED ATTIC (REMOTE) WIRING
Used as crawl space or sealed attic control (or remote control), the Model 76
is mounted in the living space while the dehumidifier is located in the area
to be dehumidified When the dehumidifier is powered, the display on the
dehumidifier control will show REMOTE to indicate that a remote control is
being used The RH shown on the Model 76 is the RH measured at the dehumidifier
Remote control is typically used for crawl space or sealed attic applications,
but is also recommended when the dehumidifier and the space being dehumidified
are inconvenient or difficult for the homeowner to access Examples of this
type of application include basements that may be inconvenient to access or
storage areas
Gh Rf Cf Gs W Y HVAC EQUIP.
+ – A B ODT Remote Sensor
MODEL 76 CONTROL
A B C/R/+ DH DH
90-1860
13
WIRING THE DEHUMIDIFIER TO THE HVAC SYSTEM AND ZONE DAMPERS
NOTE: Use 18-22 AWG wire for wiring to HVAC system and zone dampers
Pull off the wiring access cover near the dehumidifier control to access the
wiring terminals Snap the wiring access cover back into place after completing
all wiring
FIGURE 24 WIRING TO HVAC SYSTEM
WIRING TO THE HVAC SYSTEM
When the dehumidifier is ducted to the HVAC system, it is recommended that it
also be wired to the HVAC system as shown in FIGURE 24 If ducted to the HVAC
system in return to return configuration, the dehumidifier must be wired to
the HVAC system to prevent short circuiting dehumidified air directly back to
the dehumidifier inlet In return to supply ducting configuration, running the
HVAC fan with the dehumidifier ensures the warm dry air is mixed with room air
before being discharged to the home
OPTIONAL W & Y WIRING
Wire the W and/or Y terminal to the HVAC system when using the ventilation
feature of the dehumidifier (see VENTILATION on page 19)
Wire the dehumidifier Y terminal to the HVAC system if it is desired to
disable the dehumidifier compressor from operating when the air conditioning
is running See DEH W/AC in SYSTEM SET-UP on page 16 for additional set up
steps required to access this feature
+ – A B ODT VENT DEH Remote Sensor Dampers
FLOAT DH DH Switch
Gh Rf Cf Gs W Y HVAC EQUIP.
EXISTING WIRE NEW WIRE
THERMOSTAT OR ZONE
CONTROL BOARD
R C G W Y
HVAC EQUIPMENT
G R C
W Y
OPTIONAL WIRES
90-1859
WIRING TO ZONE DAMPERS
FIGURE 25 TWO ZONE WIRING ON-BOARD CONTROL
+ – A B ODT VENT DEH Remote Sensor Dampers
NOTE: Dehumidifier zoning is not recommended in HVAC zoning applications
FLOAT DH DH Switch
Gh Rf Cf Gs W Y HVAC EQUIP.
(0¢ £A MIN) 24 VAC
(PRIMARY ZONE) NORMALLY CLOSED
(SECONDARY ZONE) NORMALLY OPEN
90-1896
14
SYSTEM SET-UP AND CHECKOUT
If dehumidifier installation does not include ventilation or zoning and will
not be wired to an external control, remote control or the HVAC system,
proceed to INSTALLER TEST MODE section on page 17
1. Check all wiring 2. Make sure the wire access cover has been snapped back
onto the
on-board control 3. Plug unit in and turn power switch to ON 4. The on-board
control screen should display OFF
VENTILATION
If not using the dehumidifier to bring in outdoor air, press MODE to go to
ZONE screen selections
90-1854
If using the dehumidifier for ventilation, enable and press MODE to select
TIMED or AUTO
90-1854
NOTE: If the display backlight is not on, the first button press (any button)
will only turn on the backlight Press the button a second time to achieve
function
5. Hold the MODE button on the on-board control for 3 seconds to enter the
Installer Set-up Menu
6. Navigate through the following screens to set up the dehumidifier for the
installed application
7. Use the or button to select items and use MODE to switch to the next set-
up option To exit installer set-up, all options must be scrolled through using
the MODE button
8. After the installer set up options have been completed, DONE will blink
for 3 seconds and the control will return to the OFF screen
90-1854
90-1854
REMOTE CONTROL CRAWL SPACE/SEALED ATTIC
If not installing in a crawl space or sealed attic with Model 76 remote
control, press MODE to go to VENT screen selections
90-1854
If installing in a crawl space or sealed attic with remote control, Enable and
press MODE The installer set-up is complete, proceed to INSTALLER TEST 90-1854
MODE section on page 17
90-1854
If ventilating based on time only (no outdoor temperature restrictions), press
MODE at the VENT TIMED screen to go to ventilation time selection screen
90-1854
If ventilating with outdoor temperature restrictions, use the button to go
from VENT TIMED to VENT AUTO B and then the or button to select the desired
ventilation mode, B, C, or D Press MODE to go to the ventilation time
selection screen
VENT-AUTO-B: Ventilation prevented when outdoor temperature is below 0°F and
above 100°F Between 0°F 20°F ventilation is only allowed during 90-1854 a
HVAC heat call
VENT-AUTO-C: Ventilation prevented when outdoor temperature is below 0°F and
above 100°F
90-1854
VENT-AUTO-D: Ventilation prevented when outdoor temperature is below 0°F and
above 90°F Between 0°F 40°F ventilation is only allowed during 90-1854 a
HVAC heat call
VENT-AUTO-B, -C, -D modes apply outdoor temperature limits and require an
outdoor temperature sensor to be installed
Press the or button to adjust the ventilation time per hour from 0 to 60
minutes After selecting time, press MODE to go to the ZONE screen selections
90-1854
15
ZONE EXTERNAL CONTROL
If installing the dehumidifier in a single zone application, select DISABLED
and press MODE to go to the EXTERNAL control screen selections
90-1854
If installing the dehumidifier in a two-zone application, use the or button to
select ENABLED and press MODE to go to the EXTERNAL control screen 90-1854
selections
If using the dehumidifier on-board control select DISABLED and press MODE to
go to the dehumidification with air conditioning (DEH W/AC) screen 90-1854
selections
If using a Model 76, Model 8910, or Model 8620 as an external control or other
third-party external control, such as a thermostat with dehumidifier 90-1854
outputs, use the or button to select ENABLED and press MODE to go to the
dehumidification with air conditioning (DEH W/AC) screen selections
DEH W/AC RH OFFSET
To allow dehumidification during active air conditioning, select ENABLED and
press MODE
90-1854
To disable dehumidification when the air conditioning is on, select DISABLED
and press MODE
90-1854
An offset can be applied to the on-board humidity reading to avoid
discrepancies with other humidity measuring devices in the home Use the or
button 90-1854 to select an offset from -5% to 5% Press MODE to exit the
installer set-up screens
16
INSTALLER TEST MODE
If everything is properly wired, the dehumidifier and all of the wired
components will turn on and off during Installer Test Mode to demonstrate that
all are properly operating Installer Test Mode lasts for four (4) minutes If
the ON/OFF button is pressed during test mode, the dehumidifier will exit
Installer Test Mode and return to the OFF screen
DEHUMIDIFICATION ONLY
If the dehumidifier is not already OFF, press the ON/OFF button to turn it off
90-1854
Press and hold the ON/OFF and MODE buttons for 3 seconds The measured
humidity, AIR SAMPLING and TEST will show on the display If wired to the
90-1854 HVAC system, the HVAC blower will turn on and if there is/are
damper(s) wired to the DEH DAMPER terminals of the control, the damper(s) will
energize
After three (3) minutes the dehumidifier compressor will turn on and
DEHUMIDIFYING will replace AIR SAMPLING on the control screen
90-1854
After one minute of compressor operation, all outputs will turn off and DONE
will blink for 3 seconds and then return to the OFF screen
90-1854
ZONING AND/OR VENTILATION
If the dehumidifier has been set up for ventilation, VENTILATING will appear
on the display throughout Installer Test Mode, and the ventilation damper will
be 90-1854 energized
If the dehumidifier has been set up for zoning, PRIMARY ZONE will show on the
display for the first minute of dehumidifier blower operation After one
90-1854 minute, SECONDARY ZONE will show on the display and the zone dampers
will de-energize
90-1854
17
START UP AND SEQUENCE OF OPERATION
SINGLE ZONE WHOLE HOUSE OR STAND ALONE USING THE DEHUMIDIFIER CONTROL
1. Press the ON/OFF button to turn the dehumidifier control ON The display
will show the current setting, and the dehumidifier blower and HVAC blower (if
wired to the HVAC system) will turn on to start sampling the air
The setting will be replaced by the measured humidity and AIR SAMPLING will
show on the display
2. Use the or button to adjust the humidity setting as desired The
recommended initial setting is 59%
3. After three (3) minutes of sampling, the measured humidity will be
compared to the setting:
a. If the humidity is above the setting, the dehumidifier compressor turns on
and AIR SAMPLING will be replaced by DEHUMIDIFYING The compressor remains on
until the measured humidity falls 3% RH below the setting
b. If the measured humidity is below the setting, the blowers turn off and the
display returns to showing the RH setting
4. The dehumidifier will sample again every 60 minutes, or at any time if the
humidity setting is lowered
SINGLE ZONE WHOLE HOUSE OR STAND ALONE USING MODEL 76 EXTERNAL CONTROL
1. Press the ON/OFF button to turn the dehumidifier control ON EXTERNAL will
show on the display to indicate that an external control is wired to the
dehumidifier
2. At the Model 76, press the ON button; the Model 76 will display the
measured RH
3. Use the or button on the Model 76 to adjust the humidity setting as
desired The recommended initial setting is 59%
4. If the RH measured by the Model 76 rises above the setting, the
dehumidifier will turn on as will the HVAC blower (if wired to the HVAC
system) DEHUMIDIFYING will appear on the dehumidifier control display to show
that the Model 76 is calling for dehumidification The dehumidifier and HVAC
blower (if on) will turn off when the RH measured by the Model 76 drops 3% RH
below the setting
CRAWL SPACE OR SEALED ATTIC (REMOTE) CONTROL USING MODEL 76
1. Press the ON/OFF button to turn the dehumidifier control ON REMOTE will
show on the display to indicate that a remote control is wired to the
dehumidifier
2. At the Model 76, press the ON button; the Model 76 will display the RH
measured at the dehumidifier, and the dehumidifier blower will turn on to
start sampling the air
3. Use the or button on the Model 76 to adjust the dryness level as desired
The dryness levels are from 1 to 7, with 1 being least dry and 7 being most
dry; the recommended initial setting is 3
4. After three (3) minutes of sampling, the measured humidity will be
compared to the setting:
a. If the humidity is above the setting, the dehumidifier compressor turns on
and ON flashes on the Model 76 display
b. If the measured humidity is below the setting, the dehumidifier blower
turns off
5. The dehumidifier will sample again every 60 minutes, or at any time if the
dryness level is increased
TWO ZONE PRIMARY AND SECONDARY
1. Press the ON/OFF button to turn the dehumidifier control ON
Dehumidification of the Primary Zone follows the same sequence as described to
the left for Single Zone, with or without a Model 76 external control
installed in the Primary Zone The dehumidifier control display will show
PRIMARY ZONE in addition to that described to the left when sampling or
dehumidifying the Primary Zone The zone dampers are energized when sampling or
dehumidifying the Primary Zone
2. The Secondary Zone uses the humidity setting on the dehumidifier control
During Secondary Zone sampling or dehumidification, the zone dampers are de-
energized and the HVAC blower (if on) stops SECONDARY ZONE will show on the
dehumidifier control display when the Secondary Zone is either sampling or
dehumidifying If the Primary Zone had just finished a dehumidification demand,
the compressor will continue to run during Secondary Zone sampling to prevent
short cycling of the compressor
The Secondary Zone is sampled immediately after the Primary Zone has finished
sampling, or if there is a call for dehumidification from the Primary Zone,
immediately after the call has been satisfied When a Model 76 external control
is installed, the Secondary Zone will be sampled once per hour if there has
not been a call for dehumidification from the Primary Zone Secondary Zone
sampling will also occur whenever the setting on the dehumidifier control is
lowered
18
VENTILATION
The dehumidifier can activate a normally closed damper to bring in outdoor air
through a fresh air intake duct This feature can not be used when a Model 76
has been installed in a Remote Control application, and is not recommended for
two-zone installations
NOTE: for ventilation with 8190FF, see 8190FF Installation Instructions
REQUIRED COMPONENTS
· Aprilaire model 8190FF FreshFlo or 6506, normally closed damper · 6″
insulated duct for fresh air intake duct · 24 VAC transformer (10 VA min) for
ventilation damper · Intake hood · 18-22 AWG wire
OPTIONAL COMPONENT · 8052 Outdoor Temperature Sensor
INSTALLATION AND WIRING
FIGURE 26 SINGLE ZONE, ON-BOARD CONTROL VENTILATION INSTALLATION
AIR IS PULLED FROM OUTSIDE
NORMALLY CLOSED VENT DAMPER
6 ft MIN
HVAC/FURNACE BALANCING DAMPERS
90-1897
FIGURE 27 SINGLE ZONE, EXTERNAL CONTROL VENTILATION INSTALLATION
AIR IS PULLED FROM OUTSIDE
NORMALLY
CLOSED
VENT DAMPER
6 ft MIN
HVAC/FURNACE
90-1898
FIGURE 28 SINGLE ZONE WITH MODEL 8190FF INSTALLED
FIGURE 29 VENTILATION WIRING
AIR IS PULLED FROM OUTSIDE
6 ft MIN
HVAC / FURNACE
+ – A B ODT VENT DEH Remote Sensor Dampers
FLOAT DH DH Switch
Gh Rf Cf Gs W Y HVAC EQUIP.
OPTIONAL OUTDOOR TEMPERATURE SENSOR
HVAC EQUIPMENT THERMOSTAT
(MODEL 8052)
24 VAC (10 VA min)
¤
¤
(
W
G
TRANSFORMER (E100V: USE EXTERNAL
)
)
R
¥
G
24V PORT)
6″ NORMALLY CLOSED
90-2621
DAMPER OR 8190FF
90-2622
19
VENT-AUTO & VENT-TIMED
THE DEHUMIDIFIER CAN VENTILATE IN FOUR MODES VENT-TIMED: Ventilation occurs
based only on time setting; no temperature restrictions VENT-AUTO-B:
Ventilation prevented when outdoor temperature is below 0°F and above 100°F
Between 0°F 20°F ventilation is only allowed
during a HVAC heat call VENT-AUTO-C: Ventilation prevented when outdoor
temperature is below 0°F and above 100°F VENT-AUTO-D: Ventilation prevented
when outdoor temperature is below 0°F and above 90°F Between 0°F 40°F
ventilation is only allowed
during a HVAC heat call VENT-AUTO-B, -C, -D modes apply outdoor temperature
limits and require an outdoor temperature sensor to be installed
OUTDOOR TEMPERATURE SENSOR INSTALLATION
The Outdoor Temperature Sensor should be installed outside in a shaded
location, or in the outdoor air intake duct
FIGURE 30 ODT MOUNTED OUTSIDE
NORTH, EAST OR WEST SIDE OF HOME
OUTDOOR TEMPERATURE
SENSOR
OUTDOOR TEMPERATURE SENSOR
LEADS
ABOVE EXPECTED SNOW LINE
SENSOR SENSOR BRACKET
B2202617-D
FIGURE 31 ODT MOUNTED IN INTAKE DUCT
36” MAX. OUTSIDE WALL
CENTER LINE
B2202617-E
20
DETERMINE VENTILATION REQUIREMENTS
CALCULATING AIRFLOW REQUIREMENT
1. The MINIMUM ventilation requirement is calculated using ASHRAE 622-2010
ASHRAE Airflow in CFM = [House Area in Sq Ft x 001] + [(Number of Bedrooms +1)
x 75] NOTE: Use Number of Bedrooms + 1′ or
Number of Occupants’, whichever
is larger
2. TABLE 1 shows the calculated airflow values to the nearest 5 CFM 3. Record
the required CFM ____
DETERMINE FRESH AIR DELIVERY RATE
TABLE 1 CFM REQUIRED
Number of Bedrooms
House Sq. Ft.
2
3
4
5
6
1000
35
40
50
1500 2000 2500 3000 3500
40
45
55
60
70
45
50
60
65
75
50
55
65
70
80
55
60
70
75
85
75
80
90
1. Measure the negative static pressure of the return system at the location
where the fresh air intake duct enters the return duct or dehumidifier inlet
2. See TABLE 2 for estimated inlet airflow in CFM, based on duct type, length
and available negative pressure Use an airflow measuring device for a more
accurate airflow delivery rate
3. Record the delivered CFM ____
TABLE 2 CFM DELIVERED
Duct Length
10 ft. 20 ft. 30 ft.
0.05
Flex
Pipe
60
65
55
60
50
55
Negative Static Pressure (“w.c.) as Measured for Return Duct or Plenum
0.1
0.15
0.2
0.25
Flex
Pipe
Flex
Pipe
Flex
Pipe
Flex
Pipe
85
90
105
110
120
125
135
140
80
85
100
105
115
120
130
135
75
80
95
100
110
115
125
130
0.3
Flex
Pipe
150
160
140
150
130
140
NOTE: For the table above, 6″ flex duct is laid loose with two, wide 90° bends
and a fully opened damper Rigid pipe values are based on 6″ duct, two 90°
elbows, and a fully open damper In both cases, the air intake is through a
metal vent hood with inlet screen Airflow may need to be adjusted up or down
for variations in duct work
DETERMINE CYCLE TIME
1. Use the Required CFM and Delivered CFM from the above steps to determine
the Cycle Time from TABLE 3 2. The values highlighted in gray cannot be set
due to the maximum 60 minute Cycle Time A second ventilation device (ie,
bigger duct or second
duct) will be required to meet ventilation needs
TABLE 3 CYCLE TIME SETTING (MINUTES) FOR AIRFLOW DELIVERED VS. AIRFLOW REQUIRED FOR 1 HOUR CYCLE
CFM Required
CFM Delivered
20
30
40
50
60
70
80
90
100
60
20
30
40
50
60
70
80
90
100
80
15
25
30
40
45
55
60
70
75
100
15
20
25
30
35
40
50
55
60
120
10
15
20
25
30
35
40
45
50
140
10
15
15
20
25
30
35
40
45
160
10
10
15
20
25
25
30
35
40
21
INSTALLER SETTINGS
With the dehumidifier power switch on, press the ON/OFF button to turn the
dehumidifier off
90-1854
Press and hold the MODE button for 3 seconds to access the installer settings
menu Press and release the MODE button repeatedly until the VENT 90-1854
DISABLED screen appears
Press the or button to ENABLE ventilation, then press the MODE button to set
Timed or Auto ventilation
90-1854
Press the or button to toggle between VENT TIMED, VENT AUTO-B, VENT AUTO-C and
VENT AUTO-D (refer to page 20 for a description of each) 90-1854 Press the
MODE button to select the desired ventilation method and adjust the
ventilation time
Press the or button to set the desired amount of ventilation time per hour
from 0 to 60 minutes
90-1854
To complete, press the MODE button repeatedly until DONE appears on the
display
90-1854
22
SEQUENCE OF OPERATION When wired as shown in FIGURE 28, the ventilation damper
will open whenever there is an HVAC heating (W), cooling (Y) or fan (Gs) call,
allowing fresh air to be brought in when the HVAC blower is running (see
VENTILATION WITH AN EXTERNAL CONTROL section below for exceptions) The
ventilation damper will also open if the dehumidifier is operating VENTILATING
will show on the dehumidifier control when the dehumidifier is actively
ventilating When the HVAC call ends, the dehumidifier stops, or after the set
amount of ventilation time has been met, the ventilation damper will be closed
If the set amount of ventilation time has not been met before the end of the
one-hour cycle, the dehumidifier will turn on the ventilation damper along
with the HVAC blower to ensure the desired ventilation time is satisfied If
the dehumidifier has been set up to operate ventilation with outdoor
temperature restrictions (AUTO-B, AUTO-C or AUTO-D refer to page 20) then
ventilation will be limited as described DEHUMIDIFYING THE FRESH AIR When the
dehumidifier is set up for single zone and there is no external control
installed, the dehumidifier will turn on its blower and measure the RH of the
air entering the dehumidifier during ventilation when ducted as shown in
FIGURE 26 If the relative humidity of the air entering the dehumidifier is
higher than the setting, the dehumidifier compressor will turn to remove
moisture VENTILATION WITH AN EXTERNAL CONTROL When an external control is
installed the dehumidifier will open the ventilation damper only when there is
a cooling call (Y) or when the dehumidifier is operating, unless the
ventilation need has not been met If the set amount of ventilation time has
not been met before the end of the one-hour cycle, the dehumidifier will turn
on the ventilation damper along with the HVAC blower to ensure the desired
ventilation time is satisfied ADJUSTING VENTILATION TIME AFTER INITIAL SET UP
1. Press the or button to access the RH adjustment screen or to turn on the
backlight if using an External Control
90-1854
2. Press the MODE button to toggle to the VENT TIME setting 3. Press the or
button to adjust the ventilation time (minutes) After adjusted, press nothing
else; the
screen will return to home screen after three (3) seconds
90-1854
23
TROUBLESHOOTING
Technical Support is available Monday through Friday, 7:00 am to 5:00 pm CST,
at 800-334-6011 Use the guides on the
following pages to identify and correct system faults Contact Technical
Support before replacing the unit or any components and for additional
troubleshooting
DIAGNOSTIC CODES When an error occurs, the Diagnostic Code along with SERVICE
REQUIRED will be displayed on the control screen
90-1854
TABLE 4 DIAGNOSTIC CODES
Diagnostic Code Failure Mode
Action
Reset
E1
Internal Humidity or 1. Cycle power to clear error code
Temperature Sensor Open or Shorted
2. If error code reoccurs replace User Interface, Part No 5445
Cycle Power
E2
High Refrigeration 1. Verify that the fan works, the backflow damper swings freely and there is no blocked or restricted
Cycle Power
Pressure
ductwork
2. If the fault persists, call Technical Support
E3
Model 76
1. Check connections between Model 76 and dehumidifier control board Terminals should be fully
Self-Correcting
Remote Control
inserted and secured in the control board and Model 76 control terminals
Communication Loss 2. If connections are correct and secure, turn off the dehumidifier and remove the Model 76 Use a short
section of 4-wire cable to reconnect the Model 76 to the control board Turn the dehumidifier back on
and increase the dryness level setting on the Model 76 If the dehumidifier turns on, the problem is
with the wiring between the dehumidifier and control
3. If the dehumidifier does not turn on, call Technical Support
E4
Insufficient Capacity 1. Check the frost sensor connection at the power board Terminal should be fully seated on the power Cycle Power
board pins
2. Remove the side access panel and verify that the sensor is secured to the suction line
3. If the sensor is connected and secured to the refrigeration line proceed to the next step
4. Reset the fault by cycling power to the dehumidifier
5. Turn the humidity setting down (below room/home humidity level) to make a dehumidification call
6. Allow the fan and compressor to run for approximately 10-15 minutes and then enter diagnostic test mode by simultaneously pressing the and MODE buttons for 3 seconds The LCD will display the temperature measured by the internal sensor while also displaying AIR SAMPLING and ON, the humidity measured by the internal sensor while also displaying %RH and ON, and the frost sensor temperature while also displaying ON Scroll through these values and by using the or button
7. Record values and call Technical Support
E5
High Temperature 1. Check the high temperature sensor connection at the power board Terminal should be fully seated
Cycle Power
Thermistor Failure
on the power board pins
2. Remove the side access panel and verify the sensor is not damaged and connected to the refrigeration line coming from the compressor
3. If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No 5456 contact Technical Support to confirm
E6
Low Temperature 1. Check the low temperature sensor connection at the power board
Thermistor Failure 2. Remove the side access panel and verify the sensor is not damaged and connected to the suction
line
Cycle Power
3. If the sensor is connected and secured to the refrigeration line, it may need to be replaced with Part No 5455 contact Technical Support to confirm
24
TABLE 4 DIAGNOSTIC CODES
Diagnostic Code Failure Mode
Action
E7
Float Switch Open 1. Empty the condensate pan
2. Check the float switch connection at the control board
3. If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board
4. If the problem persists, replace the float switch
E8
Inlet Air
1. Verify all ductwork is properly sealed
Temperature Out of 50°F 104°F Range,
2. If no signs of leak points, contact Technical Support
or Dew Point Below
40°F
E9
Outdoor
1. Check the sensor connection at the power board
Temperature Sensor Open or Shorted
2. Remove the wires from the terminals and measure the resistance A short circuit will have a resistance
very close to 0 Ohms and an open circuit will have a
very high resistance The table at right can be used
to approximate the resistance based on outdoor
temperature
3. If the sensor is not reading correctly, replace the sensor, Part No 8052
Outdoor Temperature
0°F 20°F 40°F 60°F 80°F 100°F
Resistance 84,500 Ohms 46,000 Ohms 26,000 Ohms 15,500 Ohms 9,500 Ohms 6,000 Ohms
Reset Self-Correcting
Self-Correcting Self-Correcting
25
TABLE 5 TROUBLESHOOTING GUIDE
Symptom
Possible Reason
Dehumidifier does not turn on/run
No power to unit
Dehumidifier blower is running but with little or no airflow
Pressure drop across dehumidifier is higher than 04″wc for Model E080 or 06″wc for Model E100/E100H
Dehumidifier blower is running but compressor is not
Float switch open
Coil frosting
When zoned, the dehumidifier damper does not open in INSTALLER TEST mode
Inlet air temperature is outside of the 50°F 104°F range or the dew point is
below 40°F and there is a demand for dehumidification
Incorrect damper wiring or bad connection
The ventilation damper does not open when the HVAC fan is active
Cycle time has been met
ODT error or outdoor air outside of ODT range
Troubleshooting Procedure
· Check that the dehumidifier is plugged in · Check that the power switch is
turned ON · Check that the control is turned ON · Check that the circuit
breaker has not tripped
· Check dehumidifier air filter and wash or replace · Check for blocked duct
work and clear · Verify that the outlet collar with backflow damper is
installed on the outlet side of the dehumidifier · Check if backflow damper is
blocked or stuck and remove obstruction
· If float switch installed, check connections at control board and empty
condensate pan · If no float switch installed check that the jumper is
installed at the float switch terminals on the control
board
· Lack of or reduced airflow Check dehumidifier air filter and wash or replace
· Check for blocked duct work · Inlet air conditions below 60°F Increase the
humidity setting
· Verify all ductwork is properly sealed
· Verify wiring between dampers and 24 VAC transformer · If wired for Two Zone
operation, verify that 24 VAC transformer is 40 VA minimum · Check all wiring
connections between dampers and control board · Verify the normally closed
dampers are in the Primary Zone ductwork and the normally open dampers
are in the Secondary Zone ductwork
· The damper will not open if the Ventilation Time has already been met
· Check that the ODT is wired correctly to the dehumidifier control board and
connections are secure
· Check that the ODT is installed in the outdoor air intake according to the
set-up specified in the VENTILATION section beginning on page 19
· Remove the ODT leads from the dehumidifier control board and check the
resistance Compare the reading with the table shown
Outdoor Temperature
0°F 20°F 40°F 60°F 80°F 100°F
Resistance 84,500 Ohms 46,000 Ohms 26,000 Ohms 15,500 Ohms 9,500 Ohms 6,000 Ohms
Dehumidifier is not draining properly
The HVAC fan turns on unexpectedly
Dehumidifier is producing hot air
Drain line blocked or unit not level
· Verify that the unit is level
· Check the drain line blockages and for a continuous downward slope
· Verify presence and condition of drain cover insert See MAINTENANCE in
Owner’s Manual for cleaning procedure, or replace with part number 5885 if
missing or damaged
Dehumidifier is sampling · The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the ventilation
or ventilation in
time
progress
Normal function
· Air is reheated across the condenser coil, resulting in a temperature rise between inlet and outlet
26
SERVICE PARTS
5 9
4 3
10
1 6
13 18
14
2 16 17
11 19
12 15
7
8
90-2595
No. Part Description 1 EZK Filter, 135″ x 11875″ x 0875″ 2 Internal Control
Board, Deh 3 User Interface Assembly, Deh 4 Wiring Access Door, AA Deh 5 Hole
Cover, UI Ctrl, Deh 6 Door, Filter Access, AA Deh 7 Outlet Duct Panel, Deh 8
Backflow Damper, 10”, Deh 9 Inlet Duct Panel, AA Deh 10 Cover, Outlet, AA Deh
Fan, 80pt Deh, with 6MFD Capacitor 11
Fan, 100pt Deh, with 12MFD Capacitor
Part No. 5881 5444 5445 5446 5447 5882 5449 5450 5451 5452 5883 5886
No. Part Description Wire Harness, Power, Deh
12 Wire Harness, Power, Deh w/ Vent*
Part No. 5884 5888
13 Sensor, Low Temperature, Deh
5455
14 Sensor, High Temperature, Deh
5456
15 Leveling Foot, Deh
5457
16 Capacitor, Run, 50µF
5594
Capacitor, 6MFD, 250VAC, 80pt Deh
5582
17
Capacitor, 12MFD, 450VAC, 100pt Deh
5468
18 Drain Insert
5885
19 Drain Tube + Fitting
5692
NOT SHOWN
Wire Harness, 24V Deh w/ Vent*
5914
*Compatible with Model E100V and units equipped with the 8190FF FreshFlo vent kit.
27
AprilairePartners.com P.O. Box 1467 Madison, WI 53701-1467 800.334.6011 F: 608.257.4357 Printed in USA ©2021 Aprilaire Division of Research Products Corporation 10015109B2209062B1.21
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>