Aprilaire E100C 100 Pint Professional-Grade Dehumidifier User Manual
- June 6, 2024
- Aprilaire
Table of Contents
- SAFETY INSTRUCTIONS
- SPECIFICATIONS
- **** REMOVE SHIPPING BRACKET
- LOCATION CONSIDERATIONS
- LEVELING
- DRAIN INSTALLATION
- SETTING THE DESIRED HUMIDITY LEVEL
- MAINTENANCE
- CHECK THE DRAIN
- REINSTALLING THE DRAIN COVER
- DUCT COLLAR INSTALLATION
- CONTROL LOCATION
- DUCTING
- TROUBLESHOOTING
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Model E100C Dehumidifier
Installation and Operating Manual
SAFETY INSTRUCTIONS
WARNING
- 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power disconnected until installation/service is completed.
- Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions. 3. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling ductwork.
CAUTION
- Read all instructions before beginning installation.
- Improper installation may cause property damage or injury. Read instructions before installation, service or maintenance.
- Do not use in pool applications. Pool chemicals can damage the dehumidifier.
- Do not use solvents or cleaners on or near the circuit board. Chemicals can damage circuit board components.
- Wait 24 hours before running the unit if it was not shipped or stored in the upright position
- Do not use dehumidification to prevent window condensation in the winter. To address window condensation, use ventilation to lower indoor humidity in the winter.
- This appliance is not intended for use by persons(including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of this appliance by a person responsible for their safety.
- Children should be supervised to ensure that they do not play with the appliance.
- If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
SPECIFICATIONS
Unit Weight | MODEL E100C 64 lbs. |
---|---|
Stefl,g Weight | 82 lbs. |
Wady 801.60% RH Conditions | 100 pints per day @.,’ 280 CFM |
Power 115 VAC. Single Phase. 60Hz | 6.9A operating current |
Dehumidifier Inlet Air Conditions | Dehumidification: 501: – 104°F. 40’F dew |
point minimum
Filter| MERV 8. washable
Airflow| EXTERNAL STATIC PRESSURE (“w.c.)| AIRFLOW (CFM)
0.0| 280
0.2| 245
0.4| 210
0.6′| 175
*Maximum design external static pressure.
Note Rated capacity and current draw measured at 80°F/60% RH inlet
conditions at 0.0 external static pressure.
**** REMOVE SHIPPING BRACKET
IMPORTANT: Cut the strap securing the compressor shipping support bracket and remove the strap, shipping bracket screws, and bracket See FIGURE 1
LOCATION CONSIDERATIONS
- Allow sufficient clearance for filter removal and to prevent airflow obstruction
- Electrical service access will require the removal of the side panel shown Allow sufficient space for service on this side of the unit
- Always install the dehumidifier in a condensate pan when locating in, or over a finished space Adhere to local codes regarding draining of the condensate pan
LEVELING
A level surface is required to ensure proper drainage from the dehumidifier Refer to top-mounted bubble level and adjust the position until the bubble is within the outer circle
DRAIN INSTALLATION
**CAUTION
Do not damage the drain cover. The drain cover is a critical feature of the
dehumidifier drain management system.
****WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.
The drain outlet on the dehumidifier can be hard piped using a 3/4″ PVC Slip x
3/4″ MNPT fitting and 3/4″ nominal drain tubing or the provided 3/4″ MNPT x
3/4″ hose barb fitting and 3/4″ clear PVC tubing can be used to drain the
dehumidifier Always maintain a constant downward slope from the dehumidifier
to the drain and do not allow soft tubing to curl up which may result in
airlock
Note:** PTFE thread seal tape is recommended for the threaded connection
and hand tighten only If the hard pipe is used, PVC primer and cement is
recommended for the slip fit connection Remove drain insert before priming and
gluing in the PVC fitting Replace drain insert after PVC glue has fully dried
CONDENSATE PUMP AND FLOAT SWITCH
If a condensate pump is needed, install it in the condensate pan if installed
Install a condensate overflow safety switch (ie float switch) in the
condensate pan, remove the factory-installed jumper wire between the Float
Switch terminals on the control, and wire the float switch to the dehumidifier
as shown in FIGURE 4 Overflow safety switches on condensate pumps can be wired
to the Float Switch terminals in a similar fashion
SETTING THE DESIRED HUMIDITY LEVEL
-
Plugin a dehumidifier and turn on/off switch ON See FIGURE 5
-
Press the ON/OFF button to turn the dehumidifier control ON The display will show the current setting, and the dehumidifier blower will turn on to start sampling the air
-
The and buttons allow the humidity level to be set from 40% to 80% relative humidity Use the ON/OFF button to turn the dehumidifier ON or OFF Set the control at 55%RH when first installed Allow the dehumidifier to run until it reaches the setting before deciding if you want to change the setting See FIGURE 6
· If you prefer the air to be drier, decrease the humidity setting
· If you prefer the air to be less dry, increase the humidity setting -
After three (3) minutes of sampling, the measured humidity will be compared to the setting:
a. If the humidity is above the setting, the dehumidifier compressor turns on, and “AIR SAMPLING” will be replaced by “DEHUMIDIFYING” The compressor remains on until the measured humidity falls 3% RH below the setting See FIGURE 7
b. If the measured humidity is below the setting, the blowers turn off and the display returns to showing the RH setting -
The dehumidifier will sample again every 60 minutes, or at any time if the humidity setting is lowered
Your comfort is the best measure of how to adjust your setting When first
installed, your the dehumidifier has to remove all the moisture that is
initially in your home The home acts like a sponge so the moisture in the
materials of your home is at the same level as the air After drying the air,
the materials of the home will release moisture back into the air until they
are again at the same level As a result, it is not uncommon for the
dehumidifier to operate for an extended period when first installed Your
dehumidifier is equipped with two features that protect against unwanted
energy consumption Defrost is a normal operating mode that helps to prevent
significant ice formation on the refrigeration system coil, The dehumidifier
display will show “DEFROSTING” when operating in this mode can occur when
there is not enough air moving through the a dehumidifier or if the
temperature and/or humidity of the incoming air is too low The second
protection feature is the E8 code E8 on the dehumidifier display indicates
that the air entering the dehumidifier is below 50°F or above 104°F, or the
dew point of the incoming air is below 40°F There would be a significant
reduction in dehumidifier efficiency if the dehumidifier operated outside of
these conditions Low dew point conditions can be seen in some basements or
crawl spaces and usually occur in the Winter and Spring months The
dehumidifier continues to monitor the incoming air and when the conditions are
within the operating range, E8 will be removed from the display and
dehumidification will begin as needed
ENERGY SAVINGS TIPS
Energy Savings Tip #1 : Adjust the humidity setting to be as high as is
comfortable to reduce dehumidifier run time If it feels clammy or “smells
musty”, lower the humidity setting To save energy, turn the dehumidifier to
OFF when you open your windows, just as you would with air conditioning
Energy Savings Tip #2 : If vacating your home for an extended period in
the summer, set the RH at 55% and set your thermostat as high as you are
comfortable setting it to in the cooling mode Consult with appropriate
professionals regarding the highest temperature that is safe for your pets or
possessions This will keep the humidity at a controlled level while minimizing
the amount of cooling energy used
MAINTENANCE
CLEAN OR REPLACE THE AIR FILTER
After initial installation, the air filter should be checked and cleaned
every 6 months The CLEAN FILTER service reminder will display on the on-board
control screen every 6 months To clear the service message, press the and
buttons simultaneously for 3 seconds
FILTER CLEANING PROCEDURE
- At the UI control, select the ON/OFF button and switch to OFF mode
- Remove the filter access door from either side of the dehumidifier 90-1854
- Slide the filter out of the dehumidifier
- Flush the filter with warm water and a mild detergent solution
- Shake off the excess water from the filter “
- When inserting the filter, make sure the filter is secured in the top and bottom filter rails Safety clips are located along with the filter frame and will compress within the filter frame as the filter is installed If the filter doesn’t insert completely check for the presence and proper placement of drain cover (see page 8)
- Replace the filter access door
- At the UI control, select the ON/OFF button and switch to ON mode
- Press the and buttons simultaneously for 3 seconds to clear the service message
IMPORTANT! The drain cover is a critical feature of the dehumidifier
drain management system This component is required for the dehumidifier to run
properly If the drain cover is not installed, you will not be able to
reinstall the air filter The air filter is equipped with a safety mechanism
that prevents you from fully inserting the filter without the drain cover
installed
WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.
CHECK THE DRAIN
The drain and drain pan cover should be checked annually to ensure there are
no blockages or airlock in the drain system
IMPORTANT! The drain cover is a critical feature of the dehumidifier
drain management system This component is required for the dehumidifier to run
properly If the drain cover is not installed, you will not be able to
reinstall the air filter The air filter is equipped with a safety mechanism
that prevents you from fully inserting the filter without the drain cover
installed
WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.
REMOVING THE DRAIN PAN COVER
- Turn the ON/OFF switch OFF
- Remove the filter access door from the drain side of the dehumidifier
- Remove the filter from the dehumidifier to access the drain cover
- Locate the drain cover which is located over the drain opening
- Remove the drain cover by hooking your finger into the finger loop and gently lifting the cover-up and out of the drain pan
- Clean the drain cover with warm water and mild detergent solution
REINSTALLING THE DRAIN COVER
- Reinstall the drain cover by inserting your forefinger into the finger loop and grasping the outer edge of the finger loop with your thumb
- Gently insert the drain cover tip into the drain opening and tilt the cover downwards into place
- Ensure the drain cover is seated properly by checking the top surface of the drain cover is the same surface height as the filter guide channel
- Turn the ON/OFF switch ON
- At the UI control, select the ON/OFF button and switch to ON mode
CAUTION
Do not use spray solvents or cleaners on or near the inlet side of the
dehumidifier. If desired, apply cleaner to a cloth and use to clean the
cabinet.
DUCT COLLAR INSTALLATION
HORIZONTAL DISCHARGE:
- Use the screws in the parts bag to attach the duct collars to the inlet and outlet of the dehumidifier The outlet collar has a backflow damper
- The outlet duct collar may be attached to the top or end of the unit Move the outlet cover to the location not being used See FIGURE 9
- Make sure there are no bends in the ductwork coming off the outlet for a minimum of 4″ This will ensure that the ductwork will not interfere with the backflow damper function
VERTICAL DISCHARGE:
Use the screws provided in the parts bag to attach the duct collars:
· When the dehumidifier requires a ducted vertical discharge, remove the top
access panel and remount on the outlet of the unit Install the outlet duct
collar with backflow damper on top of the unit See FIGURE 9
CONTROL LOCATION
The on-board control can be located on the top of the dehumidifier or can be
relocated to the front of the dehumidifier if the control cannot be
seen/accessed in the top orientation It may also be rotated 180 degrees in
either orientation as shown in FIGURE 11
TO MOVE THE CONTROL:
- Remove the front control panel cover
- Remove the filter access door and filter
- Detach the on-board control by removing the four (4) screws around the control Note: Use one hand to support the bottom of the on-board control when removing
- Keep the control in the unit and relocate to the front access hole
- Secure the control with the same four screws used to attach the control to the top of the unit
- Secure the control panel cover to the top of the unit
DUCTING
DUCTING IN BASEMENT
The dehumidifier can be ducted to pull air from and return dehumidified air to
the HVAC return duct This installation will ensure warm, dehumidified air is
thoroughly mixed with the HVAC system air before being discharged into the
living space Alternatively, the dehumidifier can be ducted to discharge to the
supply duct, but the external static pressure of the HVAC system must not
exceed 06″ wc
REQUIRED COMPONENT: · 10″ Ductwork
DUCTING NOTES:
- Use insulated duct when the discharge is ducted to the supply side of the HVAC system
- Use a minimum of 12″ of flex duct at the dehumidifier inlet and outlet to prevent vibration noise transmission
- When ducting return to return (preferred), the dehumidifier must be wired to turn on the HVAC fan when operating
- When ducting return to supply, allow adequate space before the first branch duct to ensure the warm dehumidified air is thoroughly mixed with the HVAC system air
DUCTING TO HVAC SYSTEM IN MECHANICAL CLOSET
The dehumidifier in these applications is typically installed under or next to the HVAC equipment See Figure 11 The dehumidifier is ducted to the HVAC supply duct using the outlet on the top of the unit The supply side external static pressure of the HVAC system must not exceed 06″ wc
CAUTION
When installing the dehumidifier as part of a combustion type furnace (gas,
oil, propane, etc.) HVAC system located in a closet, duct or locate the
dehumidifier inlet and outlet and seal as needed to separate the circulation
air from the combustion and ventilation air. Follow all local and national
building and safety codes when installing or modifying any HVAC system.
REQUIRED COMPONENT:
· 10″ Ductwork
DUCTING TO WHOLE HOME WITHOUT AN AIR HANDLER
In this installation, the dehumidifier is not ducted to the HVAC system
REQUIRED COMPONENTS:
- 10″ Ductwork
- Grilles with 10″ Duct Collars
TROUBLESHOOTING
Technical Support is available Monday through Friday, 7:00 am to 5:00 pm CST,
at 800-334-6011 Use the guides on the
following pages to identify and correct system faults Contact Technical
Support before replacing the unit or any components and for additional
troubleshooting
DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be
displayed on the control screen
TABLE 1 DIAGNOSTIC CODES
Diagnostic
Code| Failure Mode| Action| Reset
---|---|---|---
El| TerrEserature Sensor Open or Shaded| L Cycle power to clear error code.
2. If error code reoccurs replace User Interface. Part No. 5445.| Cycle Power
E2| High Refrigeration Pressure| 1.Verify that the fan works. and that there
ts nothing restricting air flow.
2.If the fault persists. call Technical Support.| Cycle Power
E3| Model 76
Remote Control Communication Loss| 1.Check connections between Model 76 and
dehumidifier control board. Terminals should be fully inserted and secured in
the control board and Model 76 control terminals.
2.If connections are correct and secure. turn off the dehumidifier and remove
the Model 76. Use a short section of 4-wire cable to reconnect the Model 76 to
the control board. Turn the dehumidifier back on and increase the dryness
level setting on Model 76. If the dehumidifier turns on. the problem is with
the wiring between the dehumidifier and control.
3.If the dehumidifier does not turn on. call Technical Support.| Self-
Correcting
-2| l’IS1.17.:It| 1. Check the frost sensor connection at the power board. The terminal should be fully seated on the power board pins.
2. Remove the side access panel and verify that the sensor is secured to the
suction line.
3. If the sensor is connected and secured to the refrigeration line proceed
to the next step.
4. Reset the fault by cycling power to the dehumidifier.
5. Turn the humidity setting down (below room/home humidity level) to make a
dehumidification call.
6. Allow the fan and compressor town for approximately 1045 minutes and then
enter diagnostic test mode by simultaneously pressing the A and MODE buttons
for 3 seconds. The LCD will display the temperature measured by the internal
sensor while also displaying AIR SAMPLING and ON, the humidity measured by the
internal sensor while also displaying %RH and ON., and the frost sensor
temperature while also displaying ON. Scroll through these values and by using
the and brand buttons.
7. Record values and call Technical Support.| Cycle Power
ES| High-Temperature Thermistor Failure| 1. Check the high-temperature sensor
connection at the power board. The terminal should be fully seated on the
power board pins.
2. Remove the side access panel and verify the sensor is not damaged and
connected to the refrigeration line coming from the compressor.
3. If the sensor is connected and secured to the refrigeration line. it may
need to be replaced with Part No. 5456 — contact Technical Support to
confirm.| Cycle Power
E6| Low TemperatureThermistor Failure| 1. Check the low-temperature sensor
connection at the power board.
2. Remove the side access panel and verify the sensor is not damaged and
connected to the suction Ithe.
3.If the sensor is connected and secured to the refrigeration line. it may
need to be replaced with Part No. 5455 — contact Technical Support to
confirm.| Cycle Power
E7| Float Switch Open| 1. Empty the condensate pan
2. Check the float switch connection at the control board
3. If not using a float switch, verify jumper is between float switch
terminals on dehumidifier control board
4. If the problem persists, replace the float switch| Self-Correcting
---|---|---|---
E8| Inlet Air
Temperature Out of
50°F – 104°F range,
or dew point below
40°F| 1. If the temperature is out of range, no action, normal operation
2. If air temperature is between 50°F – 104°F with a dewpoint above 40°F,
contact Technical Support| Self-Correcting
TABLE 2 – TROUBLESHOOTING GUIDE
Symptom | Possible Reason | Troubleshooting Procedure |
---|---|---|
Dehumidifier does not turn on/run. | No power to unit. | •Check that the |
dehumidifier is plugged in.
•Check that the power switch is turned ON.
•Check that the control is turned ON.
•Check that the circuit breaker has not tripped.
The dehumidifier blower is running but with little or no airflow.| Pressure
drop across dehumidifier is hg her than 0.6″ w.c.| •Check dehumidifier air
filter and wash or replace.
•Check for blocked ductwork and clear.
•Verify that the outlet collar with backflow damper is installed on the outlet
side of the dehumidifier.
•Check if the backflow damper is blocked or stuck and remove the obstruction
The dehumidifier blower is running but the compressor is not.| Float switch
open.| •If float switch installed, check connections at the control board and
empty condensate pan.
•If no float switch is installed check that the jumper is installed at the
float switch terminals on the control board.
Coil frosting.| •Lack of or reduced airflow. Check dehumidifier air filter and
wash or replace.
•Check that there is nothing blocking the inlet or outlet of the dehumidifier.
•Inlet air conditions below 60°F. Increase the humidity setting.
Inlet air temperature is outside of the 50*F -104°F range or the dew point is
below 40°F and there is a demand for dehumidification.| •Verify all ductwork
is properly sealed.
•No action. The compressor will not run if inlet conditions are out of range.
A dehumidifier is not draining progeny.| Drain line blocked or unit not
level.| •Verify that the unit is level.
•Check the drain line blockages and for a continuous downward slope.
•Verify the presence and condition of the drain cover. The clean following
procedure under Maintenance or replace with part number 5885 if missing or
damaged.
A dehumidifier is producing hot air.| Normal function.| •Air is reheated
across the condenser coil, resulting in a temperature rise between inlet and
outlet.
The HVAC fan turns on unexpectedly.| sampling. Dehumidifier is| •The
dehumidifier will turn on the HVAC fan during air sampling or as needed to
meet the ventilation time.
SERVICE PARTS
No. | Part Description | Part No. |
---|---|---|
1 | EZK Filter. 13.5″ x 11.875′ x 0.875″ | 5881 |
2 | Internal Control Board, Deh | 5444 |
3 | User Interface Assembly. Deh | 5445 |
4 | Wiring Access Door. AA Deh | 5446 |
5 | Hole Cover. UI Ctrl, Deh | 5447 |
6 | Door. Filter Access. AA Deh | 5882 |
7 | Outlet Duct Panel. Deh | 5449 |
8 | Backflow Damper. 10″, Deh | 5450 |
9 | Inlet Duct Panel. AA Deh | 5451 |
No. | Part Description | Part No. |
10 | Cover, Outlet. AA Deh | 5452 |
11 | Fan. 10Opt Deh, with 12MFD Capacitor | 5886 |
12 | Wire Harness, Power, Deli | 5884 |
13 | Sensor, Low Temperature, Deh | 5455 |
14 | Sensor, High Temperature. Deh | 5456 |
15 | Capacitor, Run, 50uF | 5594 |
16 | Capacitor, 12MFD. 450VAC. 10Opt Deh | 5468 |
17 | Drain Insert | 5885 |
18 | Drain Tube + Fitting | 5692 |
LIMITED WARRANTY
Your Research Products Corporation Aprilaire® Dehumidifier is expressly
warranted for five (5) years from date of installation to be free from defects
in materials or workmanship Research Products Corporation’s exclusive
obligation under this warranty shall be to supply, without charge, a
replacement for any component which is found to be defective within such five
(5) year period and which is returned not later than thirty (30) days after
said five (5) year period by you to either your original supplier or to
Research Products Corporation, Madison, Wisconsin 53701, together with the
model number and installation date of the dehumidifier THIS WARRANTY SHALL NOT
OBLIGATE RESEARCH PRODUCTS CORPORATION FOR ANY LABOR COSTS AND SHALL NOT APPLY
TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS
CONTRASTED TO DEFECTS IN THE DEHUMIDIFIER ITSELF IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN
DURATION TO THE AFORESAID FIVE YEAR PERIOD RESEARCH PRODUCTS CORPORATION’S
LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR
PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED
WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED
WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED
BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR IF THE LIMITED WARRANTY
IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF
IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION Some states do not
allow limitations on how long an implied warranty lasts or the exclusion or
limitation of incidental or consequential damages so the above exclusion or
limitations may not apply to you This warranty gives you specific legal rights
and you may also have other rights which vary from state to state
WARRANTY REGISTRATION
Visit us online at www.aprilaire.com to register your Aprilaire product If you
do not have online access, please mail a postcard with your name, address,
phone number, email address, product purchased, model number, date of
purchase, and dealer name and address to: Research Products Corporation, PO
Box 1467, Madison, WI 53701 Your warranty registration information will not be
sold or shared outside of this company.
AprilairePartners.com
P.O. Box 1467 Madison,
WI 53701-1467 800.334.6011
F: 608.257.4357
Printed in USA ©2021
Aprilaire Division of Research
Products Corporation
10015490B2209224A1.21
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>