Aprilaire E100C 100 Pint Professional-Grade Dehumidifier User Manual

June 6, 2024
Aprilaire

Model E100C Dehumidifier
Installation and Operating Manual

SAFETY INSTRUCTIONS

WARNING

  1. 120 Volts may cause serious injury from electric shock. Disconnect electrical power before starting installation or servicing. Leave power disconnected until installation/service is completed.
  2. Dropping may cause personal injury or equipment damage. Handle with care and follow installation instructions. 3. Sharp edges may cause serious injury from cuts. Use care when cutting plenum openings and handling ductwork.

CAUTION

  1.  Read all instructions before beginning installation.
  2. Improper installation may cause property damage or injury. Read instructions before installation, service or maintenance.
  3. Do not use in pool applications. Pool chemicals can damage the dehumidifier.
  4. Do not use solvents or cleaners on or near the circuit board. Chemicals can damage circuit board components.
  5. Wait 24 hours before running the unit if it was not shipped or stored in the upright position
  6. Do not use dehumidification to prevent window condensation in the winter. To address window condensation, use ventilation to lower indoor humidity in the winter.
  7. This appliance is not intended for use by persons(including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of this appliance by a person responsible for their safety.
  8. Children should be supervised to ensure that they do not play with the appliance.
  9. If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.

SPECIFICATIONS

Unit Weight MODEL E100C 64 lbs.
Stefl,g Weight 82 lbs.
Wady 801.60% RH Conditions 100 pints per day @.,’ 280 CFM
Power 115 VAC. Single Phase. 60Hz 6.9A operating current
Dehumidifier Inlet Air Conditions Dehumidification: 501: – 104°F. 40’F dew

point minimum
Filter| MERV 8. washable
Airflow| EXTERNAL STATIC PRESSURE (“w.c.)| AIRFLOW (CFM)
0.0| 280
0.2| 245
0.4| 210
0.6′| 175

*Maximum design external static pressure.
Note Rated capacity and current draw measured at 80°F/60% RH inlet conditions at 0.0 external static pressure.

**** REMOVE SHIPPING BRACKET

IMPORTANT: Cut the strap securing the compressor shipping support bracket and remove the strap, shipping bracket screws, and bracket See FIGURE 1

LOCATION CONSIDERATIONS

  • Allow sufficient clearance for filter removal and to prevent airflow obstruction
  • Electrical service access will require the removal of the side panel shown Allow sufficient space for service on this side of the unit
  • Always install the dehumidifier in a condensate pan when locating in, or over a finished space Adhere to local codes regarding draining of the condensate pan

LEVELING

A level surface is required to ensure proper drainage from the dehumidifier Refer to top-mounted bubble level and adjust the position until the bubble is within the outer circle

DRAIN INSTALLATION

**CAUTION
Do not damage the drain cover. The drain cover is a critical feature of the dehumidifier drain management system.
****
WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.
The drain outlet on the dehumidifier can be hard piped using a 3/4″ PVC Slip x 3/4″ MNPT fitting and 3/4″ nominal drain tubing or the provided 3/4″ MNPT x 3/4″ hose barb fitting and 3/4″ clear PVC tubing can be used to drain the dehumidifier Always maintain a constant downward slope from the dehumidifier to the drain and do not allow soft tubing to curl up which may result in airlock
Note:** PTFE thread seal tape is recommended for the threaded connection and hand tighten only If the hard pipe is used, PVC primer and cement is recommended for the slip fit connection Remove drain insert before priming and gluing in the PVC fitting Replace drain insert after PVC glue has fully dried

CONDENSATE PUMP AND FLOAT SWITCH
If a condensate pump is needed, install it in the condensate pan if installed Install a condensate overflow safety switch (ie float switch) in the condensate pan, remove the factory-installed jumper wire between the Float Switch terminals on the control, and wire the float switch to the dehumidifier as shown in FIGURE 4 Overflow safety switches on condensate pumps can be wired to the Float Switch terminals in a similar fashion

SETTING THE DESIRED HUMIDITY LEVEL

  1. Plugin a dehumidifier and turn on/off switch ON See FIGURE 5

  2. Press the ON/OFF button to turn the dehumidifier control ON The display will show the current setting, and the dehumidifier blower will turn on to start sampling the air

  3. The and buttons allow the humidity level to be set from 40% to 80% relative humidity Use the ON/OFF button to turn the dehumidifier ON or OFF Set the control at 55%RH when first installed Allow the dehumidifier to run until it reaches the setting before deciding if you want to change the setting See FIGURE 6
    · If you prefer the air to be drier, decrease the humidity setting
    · If you prefer the air to be less dry, increase the humidity setting

  4. After three (3) minutes of sampling, the measured humidity will be compared to the setting:
    a. If the humidity is above the setting, the dehumidifier compressor turns on, and “AIR SAMPLING” will be replaced by “DEHUMIDIFYING” The compressor remains on until the measured humidity falls 3% RH below the setting See FIGURE 7
    b. If the measured humidity is below the setting, the blowers turn off and the display returns to showing the RH setting

  5. The dehumidifier will sample again every 60 minutes, or at any time if the humidity setting is lowered

Your comfort is the best measure of how to adjust your setting When first installed, your the dehumidifier has to remove all the moisture that is initially in your home The home acts like a sponge so the moisture in the materials of your home is at the same level as the air After drying the air, the materials of the home will release moisture back into the air until they are again at the same level As a result, it is not uncommon for the dehumidifier to operate for an extended period when first installed Your dehumidifier is equipped with two features that protect against unwanted energy consumption Defrost is a normal operating mode that helps to prevent significant ice formation on the refrigeration system coil, The dehumidifier display will show “DEFROSTING” when operating in this mode can occur when there is not enough air moving through the a dehumidifier or if the temperature and/or humidity of the incoming air is too low The second protection feature is the E8 code E8 on the dehumidifier display indicates that the air entering the dehumidifier is below 50°F or above 104°F, or the dew point of the incoming air is below 40°F There would be a significant reduction in dehumidifier efficiency if the dehumidifier operated outside of these conditions Low dew point conditions can be seen in some basements or crawl spaces and usually occur in the Winter and Spring months The dehumidifier continues to monitor the incoming air and when the conditions are within the operating range, E8 will be removed from the display and dehumidification will begin as needed
ENERGY SAVINGS TIPS
Energy Savings Tip #1 : Adjust the humidity setting to be as high as is comfortable to reduce dehumidifier run time If it feels clammy or “smells musty”, lower the humidity setting To save energy, turn the dehumidifier to OFF when you open your windows, just as you would with air conditioning
Energy Savings Tip #2 : If vacating your home for an extended period in the summer, set the RH at 55% and set your thermostat as high as you are comfortable setting it to in the cooling mode Consult with appropriate professionals regarding the highest temperature that is safe for your pets or possessions This will keep the humidity at a controlled level while minimizing the amount of cooling energy used

MAINTENANCE

CLEAN OR REPLACE THE AIR FILTER
After initial installation, the air filter should be checked and cleaned every 6 months The CLEAN FILTER service reminder will display on the on-board control screen every 6 months To clear the service message, press the and buttons simultaneously for 3 seconds
FILTER CLEANING PROCEDURE

  1. At the UI control, select the ON/OFF button and switch to OFF mode
  2. Remove the filter access door from either side of the dehumidifier 90-1854
  3. Slide the filter out of the dehumidifier
  4. Flush the filter with warm water and a mild detergent solution
  5. Shake off the excess water from the filter “
  6. When inserting the filter, make sure the filter is secured in the top and bottom filter rails Safety clips are located along with the filter frame and will compress within the filter frame as the filter is installed If the filter doesn’t insert completely check for the presence and proper placement of drain cover (see page 8)
  7.  Replace the filter access door
  8. At the UI control, select the ON/OFF button and switch to ON mode
  9. Press the and buttons simultaneously for 3 seconds to clear the service message

IMPORTANT! The drain cover is a critical feature of the dehumidifier drain management system This component is required for the dehumidifier to run properly If the drain cover is not installed, you will not be able to reinstall the air filter The air filter is equipped with a safety mechanism that prevents you from fully inserting the filter without the drain cover installed
WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.

CHECK THE DRAIN

The drain and drain pan cover should be checked annually to ensure there are no blockages or airlock in the drain system
IMPORTANT! The drain cover is a critical feature of the dehumidifier drain management system This component is required for the dehumidifier to run properly If the drain cover is not installed, you will not be able to reinstall the air filter The air filter is equipped with a safety mechanism that prevents you from fully inserting the filter without the drain cover installed
WARNING
Running the dehumidifier without the drain cover can lead to condensate leaks.
REMOVING THE DRAIN PAN COVER

  1. Turn the ON/OFF switch OFF
  2. Remove the filter access door from the drain side of the dehumidifier
  3. Remove the filter from the dehumidifier to access the drain cover
  4. Locate the drain cover which is located over the drain opening
  5. Remove the drain cover by hooking your finger into the finger loop and gently lifting the cover-up and out of the drain pan
  6. Clean the drain cover with warm water and mild detergent solution

REINSTALLING THE DRAIN COVER

  1. Reinstall the drain cover by inserting your forefinger into the finger loop and grasping the outer edge of the finger loop with your thumb
  2. Gently insert the drain cover tip into the drain opening and tilt the cover downwards into place
  3. Ensure the drain cover is seated properly by checking the top surface of the drain cover is the same surface height as the filter guide channel
  4. Turn the ON/OFF switch ON
  5. At the UI control, select the ON/OFF button and switch to ON mode

CAUTION
Do not use spray solvents or cleaners on or near the inlet side of the dehumidifier. If desired, apply cleaner to a cloth and use to clean the cabinet.

DUCT COLLAR INSTALLATION

HORIZONTAL DISCHARGE:

  • Use the screws in the parts bag to attach the duct collars to the inlet and outlet of the dehumidifier The outlet collar has a backflow damper
  • The outlet duct collar may be attached to the top or end of the unit Move the outlet cover to the location not being used See FIGURE 9
  • Make sure there are no bends in the ductwork coming off the outlet for a minimum of 4″ This will ensure that the ductwork will not interfere with the backflow damper function

VERTICAL DISCHARGE:
Use the screws provided in the parts bag to attach the duct collars:
· When the dehumidifier requires a ducted vertical discharge, remove the top access panel and remount on the outlet of the unit Install the outlet duct collar with backflow damper on top of the unit See FIGURE 9

CONTROL LOCATION

The on-board control can be located on the top of the dehumidifier or can be relocated to the front of the dehumidifier if the control cannot be seen/accessed in the top orientation It may also be rotated 180 degrees in either orientation as shown in FIGURE 11
TO MOVE THE CONTROL:

  1. Remove the front control panel cover
  2. Remove the filter access door and filter
  3. Detach the on-board control by removing the four (4) screws around the control Note: Use one hand to support the bottom of the on-board control when removing
  4. Keep the control in the unit and relocate to the front access hole
  5. Secure the control with the same four screws used to attach the control to the top of the unit
  6. Secure the control panel cover to the top of the unit

DUCTING

DUCTING IN BASEMENT
The dehumidifier can be ducted to pull air from and return dehumidified air to the HVAC return duct This installation will ensure warm, dehumidified air is thoroughly mixed with the HVAC system air before being discharged into the living space Alternatively, the dehumidifier can be ducted to discharge to the supply duct, but the external static pressure of the HVAC system must not exceed 06″ wc
REQUIRED COMPONENT: · 10″ Ductwork

DUCTING NOTES:

  • Use insulated duct when the discharge is ducted to the supply side of the HVAC system
  • Use a minimum of 12″ of flex duct at the dehumidifier inlet and outlet to prevent vibration noise transmission
  • When ducting return to return (preferred), the dehumidifier must be wired to turn on the HVAC fan when operating
  • When ducting return to supply, allow adequate space before the first branch duct to ensure the warm dehumidified air is thoroughly mixed with the HVAC system air

DUCTING TO HVAC SYSTEM IN MECHANICAL CLOSET

The dehumidifier in these applications is typically installed under or next to the HVAC equipment See Figure 11 The dehumidifier is ducted to the HVAC supply duct using the outlet on the top of the unit The supply side external static pressure of the HVAC system must not exceed 06″ wc

CAUTION
When installing the dehumidifier as part of a combustion type furnace (gas, oil, propane, etc.) HVAC system located in a closet, duct or locate the dehumidifier inlet and outlet and seal as needed to separate the circulation air from the combustion and ventilation air. Follow all local and national building and safety codes when installing or modifying any HVAC system.
REQUIRED COMPONENT:
· 10″ Ductwork
DUCTING TO WHOLE HOME WITHOUT AN AIR HANDLER
In this installation, the dehumidifier is not ducted to the HVAC system

REQUIRED COMPONENTS:

  • 10″ Ductwork
  • Grilles with 10″ Duct Collars

TROUBLESHOOTING

Technical Support is available Monday through Friday, 7:00 am to 5:00 pm CST, at 800-334-6011 Use the guides on the following pages to identify and correct system faults Contact Technical Support before replacing the unit or any components and for additional troubleshooting
DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE REQUIRED will be displayed on the control screen
TABLE 1 ­ DIAGNOSTIC CODES

Diagnostic
Code| Failure Mode| Action| Reset
---|---|---|---
El| TerrEserature Sensor Open or Shaded| L Cycle power to clear error code.
2. If error code reoccurs replace User Interface. Part No. 5445.| Cycle Power
E2| High Refrigeration Pressure| 1.Verify that the fan works. and that there ts nothing restricting air flow.
2.If the fault persists. call Technical Support.| Cycle Power
E3| Model 76
Remote Control Communication Loss| 1.Check connections between Model 76 and dehumidifier control board. Terminals should be fully inserted and secured in the control board and Model 76 control terminals.
2.If connections are correct and secure. turn off the dehumidifier and remove the Model 76. Use a short section of 4-wire cable to reconnect the Model 76 to the control board. Turn the dehumidifier back on and increase the dryness level setting on Model 76. If the dehumidifier turns on. the problem is with the wiring between the dehumidifier and control.
3.If the dehumidifier does not turn on. call Technical Support.| Self- Correcting
-2| l’IS1.17.:It| 1. Check the frost sensor connection at the power board. The terminal should be fully seated on the power board pins.
2. Remove the side access panel and verify that the sensor is secured to the suction line.
3. If the sensor is connected and secured to the refrigeration line proceed to the next step.
4. Reset the fault by cycling power to the dehumidifier.
5. Turn the humidity setting down (below room/home humidity level) to make a dehumidification call.
6. Allow the fan and compressor town for approximately 1045 minutes and then enter diagnostic test mode by simultaneously pressing the A and MODE buttons for 3 seconds. The LCD will display the temperature measured by the internal sensor while also displaying AIR SAMPLING and ON, the humidity measured by the internal sensor while also displaying %RH and ON., and the frost sensor temperature while also displaying ON. Scroll through these values and by using the and brand buttons.
7. Record values and call Technical Support.| Cycle Power
ES| High-Temperature Thermistor Failure| 1. Check the high-temperature sensor connection at the power board. The terminal should be fully seated on the power board pins.
2. Remove the side access panel and verify the sensor is not damaged and connected to the refrigeration line coming from the compressor.
3. If the sensor is connected and secured to the refrigeration line. it may need to be replaced with Part No. 5456 — contact Technical Support to confirm.| Cycle Power
E6| Low TemperatureThermistor Failure| 1. Check the low-temperature sensor connection at the power board.
2. Remove the side access panel and verify the sensor is not damaged and connected to the suction Ithe.
3.If the sensor is connected and secured to the refrigeration line. it may need to be replaced with Part No. 5455 — contact Technical Support to confirm.| Cycle Power
E7| Float Switch Open| 1. Empty the condensate pan
2. Check the float switch connection at the control board
3. If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board
4. If the problem persists, replace the float switch| Self-Correcting
---|---|---|---
E8| Inlet Air
Temperature Out of
50°F – 104°F range,
or dew point below
40°F| 1. If the temperature is out of range, no action, normal operation
2. If air temperature is between 50°F – 104°F with a dewpoint above 40°F, contact Technical Support| Self-Correcting

TABLE 2 – TROUBLESHOOTING GUIDE

Symptom Possible Reason Troubleshooting Procedure
Dehumidifier does not turn on/run. No power to unit. •Check that the

dehumidifier is plugged in.
•Check that the power switch is turned ON.
•Check that the control is turned ON.
•Check that the circuit breaker has not tripped.
The dehumidifier blower is running but with little or no airflow.| Pressure drop across dehumidifier is hg her than 0.6″ w.c.| •Check dehumidifier air filter and wash or replace.
•Check for blocked ductwork and clear.
•Verify that the outlet collar with backflow damper is installed on the outlet side of the dehumidifier.
•Check if the backflow damper is blocked or stuck and remove the obstruction
The dehumidifier blower is running but the compressor is not.| Float switch open.| •If float switch installed, check connections at the control board and empty condensate pan.
•If no float switch is installed check that the jumper is installed at the float switch terminals on the control board.
Coil frosting.| •Lack of or reduced airflow. Check dehumidifier air filter and wash or replace.
•Check that there is nothing blocking the inlet or outlet of the dehumidifier.
•Inlet air conditions below 60°F. Increase the humidity setting.
Inlet air temperature is outside of the 50*F -104°F range or the dew point is below 40°F and there is a demand for dehumidification.| •Verify all ductwork is properly sealed.
•No action. The compressor will not run if inlet conditions are out of range.
A dehumidifier is not draining progeny.| Drain line blocked or unit not level.| •Verify that the unit is level.
•Check the drain line blockages and for a continuous downward slope.
•Verify the presence and condition of the drain cover. The clean following procedure under Maintenance or replace with part number 5885 if missing or damaged.
A dehumidifier is producing hot air.| Normal function.| •Air is reheated across the condenser coil, resulting in a temperature rise between inlet and outlet.
The HVAC fan turns on unexpectedly.| sampling. Dehumidifier is| •The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the ventilation time.

SERVICE PARTS

No. Part Description Part No.
1 EZK Filter. 13.5″ x 11.875′ x 0.875″ 5881
2 Internal Control Board, Deh 5444
3 User Interface Assembly. Deh 5445
4 Wiring Access Door. AA Deh 5446
5 Hole Cover. UI Ctrl, Deh 5447
6 Door. Filter Access. AA Deh 5882
7 Outlet Duct Panel. Deh 5449
8 Backflow Damper. 10″, Deh 5450
9 Inlet Duct Panel. AA Deh 5451
No. Part Description Part No.
10 Cover, Outlet. AA Deh 5452
11 Fan. 10Opt Deh, with 12MFD Capacitor 5886
12 Wire Harness, Power, Deli 5884
13 Sensor, Low Temperature, Deh 5455
14 Sensor, High Temperature. Deh 5456
15 Capacitor, Run, 50uF 5594
16 Capacitor, 12MFD. 450VAC. 10Opt Deh 5468
17 Drain Insert 5885
18 Drain Tube + Fitting 5692

LIMITED WARRANTY
Your Research Products Corporation Aprilaire® Dehumidifier is expressly warranted for five (5) years from date of installation to be free from defects in materials or workmanship Research Products Corporation’s exclusive obligation under this warranty shall be to supply, without charge, a replacement for any component which is found to be defective within such five (5) year period and which is returned not later than thirty (30) days after said five (5) year period by you to either your original supplier or to Research Products Corporation, Madison, Wisconsin 53701, together with the model number and installation date of the dehumidifier THIS WARRANTY SHALL NOT OBLIGATE RESEARCH PRODUCTS CORPORATION FOR ANY LABOR COSTS AND SHALL NOT APPLY TO DEFECTS IN WORKMANSHIP OR MATERIALS FURNISHED BY YOUR INSTALLER AS CONTRASTED TO DEFECTS IN THE DEHUMIDIFIER ITSELF IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL BE LIMITED IN DURATION TO THE AFORESAID FIVE YEAR PERIOD RESEARCH PRODUCTS CORPORATION’S LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES, OTHER THAN DAMAGES FOR PERSONAL INJURIES, RESULTING FROM ANY BREACH OF THE AFORESAID IMPLIED WARRANTIES OR THE ABOVE LIMITED WARRANTY IS EXPRESSLY EXCLUDED THIS LIMITED WARRANTY IS VOID IF DEFECT(S) RESULT FROM FAILURE TO HAVE THIS UNIT INSTALLED BY A QUALIFIED HEATING AND AIR CONDITIONING CONTRACTOR IF THE LIMITED WARRANTY IS VOID DUE TO FAILURE TO USE A QUALIFIED CONTRACTOR, ALL DISCLAIMERS OF IMPLIED WARRANTIES SHALL BE EFFECTIVE UPON INSTALLATION Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages so the above exclusion or limitations may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state
WARRANTY REGISTRATION
Visit us online at www.aprilaire.com to register your Aprilaire product If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: Research Products Corporation, PO Box 1467, Madison, WI 53701 Your warranty registration information will not be sold or shared outside of this company.

AprilairePartners.com
P.O. Box 1467 Madison,
WI 53701-1467 800.334.6011
F: 608.257.4357
Printed in USA ©2021
Aprilaire ­ Division of Research
Products Corporation
10015490B2209224A1.21

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals