DMP 1100x Series Wireless Receiver Installation Guide

June 6, 2024
DMP

DMP 1100x Series Wireless Receiver Installation Guide
DMP 1100x Series Wireless Receiver

DESCRIPTION

The 1100X Series Wireless Receiver provides up to 100 wireless zones for XR150 Series panels and up to 500 wireless zones for XR550 Series panels. The 1100XE features 128-bit AES encryption.

The 1100X also provides two-way communication using 900 MHz frequency hopping- spreadspectrum technology.

The 1100X is equipped with a case and wall tamper.

Compatibility

  • XR150/XR550 Series Panels
  • Encryption requires panel Version 183 or higher
  • 1100T Translator requires receiver firmware Version 207/301 or higher

What is Included?

  • 1100X Wireless Receiver
  • Model 300 Harness
  • Hardware Pack

PROGRAM THE PANEL

Refer to the panel programming guide as needed.

  1. Reset the panel.
  2. At a keypad, enter 6653 (PROG) to access the PROGRAMMER menu.
  3. In SYSTEM OPTIONS, program a HOUSE CODE between 1 and 50. See House Code Explained for more information.
  4. (1100XE only) At the 1100 ENCRYPTION prompt, select ALL to only add encrypted wireless devices to the system. Select BOTH to allow both encrypted and non-encrypted wireless devices to be programmed.
  5. (1100XE only) The default passphrase appears at ENTER PASSPHRASE. Press CMD to keep the default. Press any select key or area to change the passphrase and enter an 8-character hexadecimal string (0-9, A-F).
  6. Press CMD until STOP displays. Press a top row select key or area to save programming.

SELECT A LOCATION

The receiver should be centrally located between the DMP panel and the 1100 Series transmitters used in the installation based on the wiring specifications below. Use an 1106 Series Universal Wireless Transmitter to perform an LED survey.

  1. With the cover removed, hold the transmitter in the desired location.
  2. Press the tamper switch to send data to the panel and determine if communication is confirmed or faulty.

Confirmed: If communication is confirmed, for each press or release of the tamper switch, the LED blinks immediately on and immediately off.
Faulty: If communication is faulty, the LED remains on for about 8 seconds or flashes multiple times in quick succession. Relocate the receiver until the LED confirms clear communication.

MOUNT THE 1100X

  1. Remove the cover from the plastic housing.

  2. Use the included #6 screws to secure the 1100X to the wall.
    See Figure 2 for mounting hole locations.

  3. Use one of the provided screws to secure the wall tamper.
    See Figure 2 for tamper location.

MOUNT THE 1100X
Figure 1:
Inside of the 1100X Housing

WIRE THE RECEIVER

The panel immediately recognizes the 1100X if the panel is programmed with a house code. Do not use shielded wire between the panel and receiver.

  1. Connect the red, yellow, green, and black wires to the PANEL terminal on the 1100X.
  2. Connect the other end of the wires to the XBUS on the panel.
    Snap the cover back on to the base.
    Note: The receiver can’t operate if it’s connected to the keypad bus.


Figure 2:
Wire the 1100X to the Panel

ADDITIONAL INFORMATION

Wiring Specifications for X-Bus

  1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do Not use twisted pair or shielded wire for LX-Bus and Keypad Bus data circuits. To maintain auxiliary power integrity when using 22-gauge wire do not exceed 500 feet. When using 18-gauge wire do not exceed 1,000 feet. Install an additional power supply to increase the wire length or add devices.
  2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As wire distance from the panel increases, DC voltage on the wire decreases.
  3. Maximum number of devices per 2,500 feet circuit is 40.
  4. Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly. Refer to the panel installation guide and LX-Bus/Keypad Bus Wiring Application Note (LT-2031).

Programming Zones

Refer to the panel XR150/XR550 Series Programming Guide (LT-1232) for complete wireless programming information. When any wireless input zone for a particular address is programmed, the 1100XH responds to the panel for this address. Other devices, such as keypads or hardwired zone expanders, cannot use this address. Zones connected directly to the panel cannot be wireless. See Table 1 for designated zone numbers.

DMP PANEL

|

AVAILABLE ZONES

|

ZONE RANGES

---|---|---

XR150 (1100X Series)

|

100

|

500 – 599

XR550 (1100X Series)

|

500

|

500 – 999

Table 1: Zone Number Designations

1100X LED Operation
The six labeled LEDs on the 1100X PCB display wireless receiver operation and activity.
See Table 2 for LED locations and Table 1 for LED indications.

House Code Explained
The house code identifies the panel, receiver, and transmitters to each other. The 1100X automatically sends the specified house code to wireless transmitters when transmitter serial numbers are programmed into the panel. The 1100X only listens for transmissions using the specified house code or the programmed transmitters’ serial numbers.

LED

|

INDICATIONS

---|---

RF RX

|

Flashing yellow indicates data is being received from a transmitter.

RF TX

|

Flashing green indicates data is being sent to a transmitter.

PANEL RX

| Flashing yellow indicates data is being received from a panel.

PANEL TX

|

Flashing green indicates data is being sent to the panel.

STATUS

|

Solid red indicates memory is being uploaded. Turns off when complete.

PWR

|

Solid green indicates there is power to the wireless receiver.

Table 2: LED Indications

Transmitter Supervision Time
For listed installations, program the transmitter supervision time in panel zone programming as listed in the following table. Refer to the panel programming guide for complete wireless programming information.

UL Listing

|

Listed Accessories

|

Supervision Time

---|---|---
UL 268 Smoke-Automatic Fire Detectors| 1164 Synchronized Smoke Detector 1164NS
Smoke Detector with No Sounder 1168
Smoke/CO/Low Temp Detector|

3

UL 365 Police Station Connected Burglar Accessory| 1103 Universal Transmitter| 60
UL 521 Heat Detectors for Fire Protective Signaling Systems| 1183-135F, 1183-135R Heat Detector| 3
UL 609 Local Burglar Alarm Units and System Accessory| 1103 Universal Transmitter|

60

UL 634 Connections and Switches for use with Burglar Alarm Systems Accessory| 1101, 1102, 1103, 1106 Universal Transmitters| 60
UL 636 Holdup Alarm Units and Systems Accessory| 1142 Two-Button Holdup Transmitter| 60
UL 639 Intrusion Detection Units Accessory| 1127W, 1127C PIR Motion Detectors| 60
UL 864 Fire Protective Signaling Systems| 1103 Universal Transmitter| 3
UL 985 Household Fire Warning System Accessory| 1135 Siren
9060, 9063, 9862 Wireless Keypads|

240

UL 1023 Household Burglary System Units Accessory|

1101, 1102, 1103, 1106 Universal Transmitters 1127W, 1127C PIR Motion Detectors
1135 Siren
1142 Two-Button Holdup Transmitter 9060, 9063, 9862 Wireless Keypads

|

60

UL 1076 Proprietary Burglar Alarm Units Accessory| 1103 Universal Transmitter
9862 Wireless Graphic Touchscreen Keypad|

60

UL 1610 Central Station Burglar Alarm Units Accessory| 1103 Universal Transmitter
1135 Siren
9060, 9063, 9862 Wireless Keypads|

60

UL 2075 Gas and Vapor Detectors and Sensors| 1184 Wireless Carbon Monoxide Detector 1168 Wireless Smoke/CO/Low Temp Detector|

240

Table 3: Wireless Transmitter Supervision Times

Note: The 1100R Wireless Repeater and 1100T Wireless Translator follow the Receiver Supervision times for Listed Accessories.

LISTED COMPLIANCE SPECIFICATIONS

For applications that must conform to a National Recognized Testing Laboratory certified system, read the information below for additional information.

Commercial Fire
Transmitters must be programmed as supervised. Refer to Table 3 for specific supervision times. The maximum line impedance of the 4-wire bus is 16.2 Ohms for 1,000 feet (305 meters). The recommended wire gauge for panel to receiver connection is 22 AWG.
After all transmitters are in position, the WLS option of the panel’s Walk Test must be operated and all transmitters programmed for Fire (FI) or Supervisory (SV) must show that their check-in message was received. Refer to the panel programming guide for Trip Counter for DMP Wireless Check-in Test (WLS) which describes that both numbers of the counter must match. If not and a failed wireless zone is displayed at END, decrease that transmitter’s range with the receiver and perform the Wireless Walk Test again.

FCC INFORMATION

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

The antenna used for this transmitter must be installed to provide a separation distance of at least 20cm (7.874 in.) from all persons. It must not be located or operated in conjunction with any other antenna or transmitter. Changes or modifications made by the user and not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  1. Reorient or relocate the receiving antenna.
  2. Increase the separation between the equipment and receiver.
  3. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  4. Consult the dealer or an experienced radio/TV technician for help.

INDUSTRY CANADA INFORMATION
This device complies with Industry Canada Licence-exempt RSS standard(s). Operation is subject to the following two conditions:

  1. This device may not cause interference, and
  2. this device must accept any interference, including interference that may cause undesired operation of the device.

This system has been evaluated for RF Exposure per RSS-102 and is in compliance with the limits specified by Health Canada Safety Code 6. The system must be installed at a minimum separation distance from the antenna to a general bystander of 7.87 inches (20 cm) to maintain compliance with the General Population limits.

1100X SERIES WIRELESS RECEIVER
WIRELESS RECEIVER

Specifications

Operating Voltage: 12 VDC Nominal
Current Draw: 25 mA (average), 35 mA (peak)
Frequency Range: 905-924 MHz
Housing Dimensions: 5.5”W x 3.75”L x 1”H
Housing Color: White
Housing Material: Flame Retardant ABS

Patents
U.S. Patent Number: 7, 239, 236

Ordering Information
1100X-W Standard Wireless Receiver
1100XE-W Encrypted Wireless Receiver

Certifications
California State Fire Marshal (CSFM)
New York City (FDNY)
FCC Part 15: CCKPC0114R6
Industry Canada: 5251A-PCO114R6

Underwriters Laboratory (UL) Listed

  • ANSI/UL 365 Police Station Connected Burglar
  • ANSI/UL 609 Local Burglar Alarm Unites and Systems
  • ANSI/UL 1023 Household Burglar Alarm System Units
  • ANSI/UL 1076 Proprietary Burglar Alarm Units
  • ANSI/UL 1610 Central Station Burglar Alarm Units
  • ANSI/UL 864 Fire Protective Signaling Systems
  • ANSI/UL 985 Household Fire Warning System

Compatible With Devices Listed for:

  • ANSI/UL 268 Smoke Detectors for Fire Alarm Signaling Systems
  • ANSI/UL 634 Connections and Switches for use with Burglar Alarm Systems Accessory
  • ANSI/UL 636 Safety Holdup Alarm Units and Systems
  • ANSI/UL 639 Intrusion Detections Units Accessory
  • ANSI/UL 2075 Gas and Vapor Detectors and Sensors

Designed, engineered, and
manufactured in Springfield, MO
using U.S. and global components.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals