GOODWE ET Series Hybrid Inverter Installation Guide
- June 6, 2024
- GOODWE
Table of Contents
- GOODWE ET Series Hybrid Inverter Installation Guide
- Safety Precautions
- Safety Disclaimer
- WARNING
- AC Side:
- Check Before Power On
- EU Declaration of Conformity
- 02 Product Introduction
- Dimension
- 03 Inverter Installation
- Space Requirements
- Angle Requirements
- Inverter Installation
- 04 Electrical Connection
- AC Cable (ON-GRID&BACKUP) Connection
- DC Cable (PV) Connection
- Battery Cable (BAT) Connection
- 05 Communication Connection
- Smart Meter & BMS Connection
- 06 Wiring System
- 07 Commissioning and Monitoring
- Monitoring via SEMS Portal
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
GOODWE ET Series Hybrid Inverter Installation Guide
Safety Precautions
General Disclaimer
- The information in this quick installation guide is subject to change due to product updates or other reasons. This guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All descriptions here are for guidance only.
- Before installations, read through the quick installation guide and the user manual to learn about the product and the precautions.
- All installations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations.
- Check the deliverables for correct model, complete contents, and intact appearance. Contact the manufacturer if any damage is found or any component is missing.
- Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal safety. Wear anti-static gloves, clothes, and wrist strip when touching electron devices to protect the inverter from damage. The manufacturer shall not be liable for any damage caused by static.
- Strictly follow the installation, operation, and configuration instructions in this guide and user manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://en.goodwe.com/ warranty.asp.
Safety Disclaimer
WARNING
DC Side:
- Ensure the component frames and the bracket system are securely grounded.
- Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for the damage if other connectors are used.
- Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may cause poor contacts or high impedances, and damage the inverter.
- Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and extremely high voltage.
- Ensure the minimum isolation resistance of the PV string to the ground exceeds 19.33kΩ to avoid shock hazards.
- Keep the battery off, and the inverter disconnects with PV panels and other AC power before connecting the battery and the inverter. The rated voltage of the battery should meet specifications of the inverter.
- The PV modules used with the inverter must have an IEC61730 class A rating.
AC Side:
- The voltage and frequency at the connecting point should meet the on-grid requirements.
- An additional protective device like the circuit breaker is recommended on the AC side. Specification of the protective device should be at least 1.25 times the AC output rated current.
- PE cable of the inverter must be connected firmly.
- You are recommended to use copper cables as AC output cables. Contact the manufacturer if you want to use aluminum cables.
Inverter:
- Terminals at the bottom of the inverter cannot bear much load. Otherwise, the terminals will be damaged.
- All labels and warning marks should be clear after the installation. Do not scrawl, damage, or cover any label on the device.
- Do not touch the running equipment to avoid being hurt as its temperature may exceed 60℃. Do not install the equipment at a place within children’s reach.
- Unauthorized dismantling or modification may damage the equipment, the damage is not covered under the warranty.
- Connect the BACKUP terminals before connecting the ON-GRID terminals. Do not start the BACKUP function if the inverter is not connected to the battery.
- Warning labels on the inverter are as follows.
Check Before Power On
No. | Check Item |
---|---|
1 | The inverter is firmly installed at a clean place where is well-ventilated |
and easy-to-
operate.
2| The PE cable, DC input cable, AC output cable, and communication cable are
connected correctly and securely.
3| Cable ties are routed properly and evenly, and no burrs.
4| Unused ports and terminals are sealed.
5| The voltage and frequency at the connection point meet the on-grid
requirements.
EU Declaration of Conformity
The inverters sold in the European market meets the following directives and requirements:
- Electromagnetic compatibility Directive 2014/30/EU (EMC)
- Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
- Radio Equipment Directive 2014/53/EU (RED)
- Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
- Waste Electrical and Electronic Equipment 2012/19/EU
- Registation,Evaluation,Authorisation and Restriction of Chemicals (EC)No 1907/2006 (REACH) For more detailed declarations of conformity, visit https://en.goodwe.com.
02 Product Introduction
-
DC Switch [1]
-
PV Input Terminal (PV+/PV-)[2]
-
Battery Terminal(BAT+/BAT-)
-
Communication Module Port (WiFi or Bluetooth)
-
COM Terminal
-
METER Communication Port
-
BMS Communication Port
-
AC Terminal (ONGRID and BACKUP)
-
WiFi Reset
-
Indicator
-
PE Terminal
-
Mounting Plate
[1] GW5KL-ET, GW6KL-ET, GW8KL-ET,GW10KL-ET: optional.
[2] GW8KL-ET and GW10KL-ET: 2 x PV+/PV-.
Dimension
03 Inverter Installation
Space Requirements
Angle Requirements
Inverter Installation
Avoid the water pipes and cables buried in the wall when drilling holes.
04 Electrical Connection
PE Cable Connection
AC Cable (ON-GRID&BACKUP) Connection
DC Cable (PV) Connection
Crimp contact and PV connectors are various depending on different inverters. The actual deliverables may differ.
Battery Cable (BAT) Connection
05 Communication Connection
Smart Meter & BMS Connection
06 Wiring System
LED Explanation
07 Commissioning and Monitoring
Commissioning via PV Master APP
Monitoring via SEMS Portal
For more detailed instructions, scan the QR code below to see the user
manual.
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>