SALUS FC600-M 0-10V Thermostat Control Module Instruction Manual

June 6, 2024
SALUS

SALUS FC600-M 0-10V Thermostat Control Module Instruction Manual

Distributor of SALUS Controls:

QL CONTROLS Sp. z o.o., Sp. k.
Rolna 4
43-262 Kobielice,
Poland
salus@salus-controls.pl

Product Compliance

This product complies with essential requirements of the European
Parliament Directive And Of The Council 2012/19 / EU of 4 July 2012 on waste electrical and electronic equipment (WEEE).

Safety Information

Use in accordance with national and local regulations of the country and in EU territory. Indoor use only. Keep your equipment completely dry.
The installation must be carried out by a qualified person in accordance with the rules of the country and in the EU.
Before install, repair, maintenance or during any connection work disconnect power supply from the module and make sure the terminals and wires are free of voltage.
The electrical installation where module works should be secured with a fuse, specially selected to the applied loads.
The device can not be used with the damaged case.
Under no circumstances dont’t modify the module construction.
Do not allow access to the module to people who didn’t read this manual.
Do not install the device under voltage.
A short circuit at the output may damage the unit. It is forbidden to operate a defective device or repaired by unauthorized service.

Terminals description

Electrical diagram

Display description and button functions

  1. Double-digit, 7-segment LED display  displays parameters: F1, F1, F3, t and voltage and time values
  2. Entering the menu, selecting the parameter, increasing the value
  3. Confirmation of parameter selection, reduce the value.

DIN rail mounting

For module covering there is a special installation enclosure for the installation of electrical equipment. This enclosure should prevent user before access to the module wiring terminals. The module is designed to be mounted on a standard 35mm DIN rail. Before sliding the module . onto the DIN rail , slide the hook using the flat screwdriver. When module is mounted on the rail, place the hooks at the original position. Make sure that module is mounted solidly and that it can not be removed from the rail without a tool.
NOTE: The connection wires should be protected against tearing, loosening, or built up in such a way that they can not be exposed to mechanical stress.

Setting voltage thresholds for fan speed

Using button select the appropriate parameter to set:

F1 – for the first voltage threshold
F2 – for the second voltage threshold
F3 – for the third voltage threshold

NOTE: Module starts to supply voltage at the output when any threshold is selected. The current value change causes a fan speed change – this
allows you to check its operation and select adequate speed.
The voltage threshold settings are limited by the module:

F1 – range from 0V to setpoint in F2
F2 – range from the setpoint in F1 to the setpoint in F3
F3 – range from setpoint in F2 to 10V

The total voltage value for the F1-F3 thresholds is limited to 0 … 10V range.

Setting the increase/decrease time of the output Replacing the fuse

voltage

Time of voltage increase at the output when module starts-up and switches voltage tresholds is expressed by the parameter t. This parameter is limited to the range from 0 to 50 s.
The module provides a smooth voltage increase at the output for thresholds depending on t parameter, according to the following characteristic.

DIN rail mounting

For module covering there is a special installation enclosure for the installation of electrical equipment. This enclosure should prevent user before access to the module wiring terminals. The module is designed to be mounted on a standard 35mm DIN rail. Before sliding the module . onto the DIN rail , slide the hook using the flat screwdriver. When module is mounted on the rail, place the hooks at the original position.
Make sure that module is mounted solidly and that it can not be removed from the rail without a tool.
NOTE: Before opening the casing disconnect the power supply from the terminals of FC600-M 0-10V module and FC600 controller.

To open the casing of the module, you need to pry all the hooks (with a flat screwdriver) and then carefully remove its upper part.
NOTE: In the module should be used porcelain, slow blow 5×20 mm fuses with nominal burnout current of 8A / 230V.