SALUS KL06 230V 6 Zones Underfloor Wiring Centre User Manual
- June 6, 2024
- SALUS
Table of Contents
Wiring centre (6 zones) 230 V
Model: KL06
ManualVI 2020
Wiring centre description
- Cartridge fuse 5 x 20 mm 2 A
- Power Supply
- Diodes
- NSB (Night Set Back reduction) function
- Thermostats connection
Actuators connection
7A. PL06 – pump (or boiler) control module
7B. PL07 – pump and boiler control module
8. Serial connector for PL06 and PL07 modules
Introduction
Wired KL06 230V wiring centre allows easy and quick connection of thermostats
and actuators. It has a serial connector for additional modules (sold
separately):
• PL06 Pump or boiler control module
• PL07 Pump and boiler control module The KL06 230V wiring centre is adapted
to work with NC type actuators (normally closed) and maximum 6 thermostats.
Product Compliance
This product complies with the essential requirements and other relevant
provisions of the following EU Directives: EMC 2014/30/EU, Low Voltage
Directive LVD 2014/35/EU, RoHS directive 2011/65/EU. The full text of the EU
Declaration of Conformity is available at the following internet address:
www.saluslegal.com.
Safety information
Use in accordance to national and EU regulations. Use the device as intended,
keeping it in dry condition. Product for indoor use only. Installation must be
carried out by a qualified person in accordance to national and EU
regulations.
Before any of operations releated to the power supply (connecting wires,
installing the device, etc.), make sure that KL06 is not connected to any
power source. Installation must be carried out by a qualified person.
Incorrect connection of the wires may cause damage to the wiring centre. The
KL06 can not be used in conditions of water vapor condensation or exposed to
water.
Technical Information
Power Supply | 230 V AC 50 Hz |
---|---|
Max load | 2 (1) A |
Outputs | Terminals for actuators (230 V) |
Dimensions [mm] | 300 x 86 x 63 |
1. Fuse
Note: Replace the fuse only when the wiring centre is disconnected from power
supply (230 V ~).
Main fuse is located under the housing cover next to power supply terminals
and secures the wiring centre and the devices connected to it. Use cartridge
fuses (5×20 mm) with nominal max current 2 A. To replace fuse remove the fuse
holder with a flat screwdriver and pull out the fuse.
Power Supply
DelayOverrun Power supply for the wiring centre is 230 V ~ 50Hz.
3. LED diodes
green LED diode indicates power supply connection (230 V AC)
orange LED diode indicates NSB function being activated fuse
NSB (Night Set Back reduction) function
NSB function is activated in non-programmable Salus thermostats of the Expert
NSB, HTR, BTR series via external signal. NSB 230 V signal (night-time
temperature reduction) is sent via an external timer or programmable
thermostat connected to the KL06 wiring centre. Non-programmable thermostats
are receiving NSB signal and reducing setpoint temperature (by switching to
eco-mode). All thermostats have to be connected using a 4-wire cable (min. 4 x
0,75 mm 2 , max. 4 x 1,5 mm 2 ).
Thermostats connection
• Connecting EXPERT NSB, HTR or BTR series thermostats with NSB
function
• Connecting a 230 V thermostat to the KL08NSB wiring centre (e.g. RT200)
• Connecting ON/OFF battery-powered thermostat with voltage-free COM / NO output contacts (e.g. 091FL, RT310, RT510)
Note: In NSB, HTR, ERT, BTR product series follow interchangeable signifying:
↑= SL
= NSB
Actuators connection
The actuator wires should be secured with the self locking connectors in the
appropriate zone. Up to 6 actuators with a load of up to 2 Watts each can be
connected to a single zone. Should more than 6 actuators be required in a zone
use an additional relay to relieve the output.
A. PL06 – pump (or boiler) control module
PL06 module is used to control the pump (or boiler) using volt-free NC/COM/NO contacts. When any of thermostats connected to the KL06 230 V reports heat demand, COM/NO contacts are closing. COM/NO contacts are opening, when thermostats connected to the wiring centre will stop sending signal for heating.
Jumpers 0-15
These are used to set in minutes the delay time (overrun time). Default
setting is „0”
0-15 values specify the time in minutes. E.g. when jumper is set to value „0”,
COM/NO output will turn off as soon as the thermostats stop calling for heat.
If jumper will be set to the value „10”, the module will turn off 10 min after
the thermostats stop calling for heat.
Jumpers P,1,2,3,4,5,6
They are used to select the zone which turns on the module. The default
setting is „P”.
****P – all zones start the module 1, 2, 3, 4, 5, 6 – select the specific zone which turns on the module.
PUMP CONTROL
BOILER CONTROL
Power Supply | from the KL06 wiring centre fuse |
---|---|
Max load | 5 (2) A |
Outputs | NO/COM/NC relay |
Dimensions [mm] | 60 x 80 x 20 |
7 B. PL07 – pump and boiler control module
PL07 module is used to control the pump and the boiler using volt-free COM/NO
contacts. When any of thermostats connected to the KL06 230V reports heat
demand, OM/NO contacts are closing. COM/NO contacts are opening, when
thermostats connected to the wiring centre will stop sending signal for
heating.
ON-OFF Delay jumper
Is used to activate the delay output for the pump and boiler. Default is „ON”.
• „ON” position activates the pump and boiler outputs with a delay of 3 minutes after the heating signal is supplied from any of the thermostats connected
to the wiring centre. • „OFF” position causes immediate activation of the pump and boiler outputs.
ON-OFF Overrun jumper
Is used to activate the delay output for the pump when heating is satisfied.
Default is „ON”.
• „ON” position turns OFF the pump output with a delay of 3 minutes when all
thermostats stop calling for heat.
• „OFF” position immediately turns OFF the pump output when all thermostats
stop calling for heat.
PUMP AND BOILER CONTROL![SALUS KL06 230V 6 Zones Underfloor Wiring Centre
- PUMP AND BOILER CONTROL](https://manuals.plus/wp-content/uploads/2021/12 /SALUS-KL06-230V-6-Zones-Underfloor-Wiring-Centre-PUMP-AND-BOILER-CONTROL- 300x263.png)
Power Supply | from the KL06 wiring centre |
---|---|
Max load | 5(2) A |
Outputs | 2 x NO/COM relay |
Dimesions [mm] | 70 x 80 x 20 |
8. Serial connector for PL06 and PL07 modules.
It provides communication between the KL06 wiring centre and the PL06/PL07
modules. KL06 wiring centre + PL06/PL07 module increases functionality and
additionally makes possible to control pump and/or boiler. PL06/PL07 module is
powered from the wiring centre.
INSTALLATION
Set includes supplementary accessories (to support installation proces).
Head Office:
SALUS Controls Plc
Units 8-10 Northfield Business Park
Forge Way, Parkgate, Rotherham
S60 1SD, United Kingdom
T: +44 (0) 1226 323961
E: sales@salus-tech.com
www.salus-controls.com
SALUS Controls is a member of the Computime Group. Maintaining a policy of
continuous product development SALUS Controls plc reserve the right to change
specification, design and materials of products listed in this brochure
without prior notice.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>