westermo MCW-211 Series Industrial Ethernet Media Converter User Guide

June 6, 2024
westermo

www.westermo.com

MCW-211 Series
Industrial Ethernet Media Converter
6645-2204

General information

Legal information The contents of this document are provided “as is”. Except as required by applicable law, no warranties of any kind, either express or implied, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose, are made in relation to the accuracy and reliability or contents of this document. Westermo reserves the right to revise this document or withdraw it at any time without prior notice.
Under no circumstances shall Westermo be responsible for any loss of data or income or any special, incidental, and consequential or indirect damages howsoever caused.

More information about Westermo can be found at www.westermo.com

About This Guide

This guide is intended for installation engineers and users of the Westermo products. It includes information on safety and regulations, a product description, installation instructions and technical specifications.

Safety and Regulations

Warning signs are provided to prevent personal injuries and/or damages to the product.
The following levels are used:

Level of warning| Description| Consequence personal injury| Consequence material damage
---|---|---|---

WARNING| Indicates a potentially
situation| Possible death or major injury| Major damage to the product
CAUTION| Indicates a potentially hazardous situation| Minor or moderate injury| Moderate damage to the product
NOTICE| Provides information in order to avoid misuse of the product, confusion or misunderstanding| No personal injury| Minor damage to the product
NOTE|  Used for highlighting general, but important information| No personal injury| Minor damage to the product

Safety Information

Before installation:
Read this manual completely and gather all information on the product. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this product.

WARNING – SAFETY DURING INSTALLATION The product must be installed and operated by qualified service personnel and installed into an apparatus cabinet or similar, where access is restricted to service personnel only. During installation, ensure a protective earthing conductor is first connected to the protective earthing terminal (only valid for metallic housings). Westermo recommends a crosssectional area of at least 4 mm2. If the product does not have a protective earthing terminal, then the DIN-rail must be connected to protective earth. Upon removal of the product, ensure that the protective earthing conductor, or the connection to earth via the DIN-rail, is disconnected last.

WARNING – HAZARDOUS VOLTAGE
Do not open an energized product. Hazardous voltage may occur when connected to a power supply.
WARNING – PROTECTIVE FUSE
The power supply wiring must be sufficiently fused. It must be possible to disconnect manually from the power supply. Ensure compliance to national installation regulations. Replacing the internal fuse must only be performed by Westermo qualified personell.

WARNING – REDUCE THE RISK OF FIRE
To reduce the risk of fire, use only telecommunication line cords with a cable diameter of AWG 26 or larger. Regarding power cable dimensions, see Interface Specifications.
C AUTION – CLASS 1 LASER PRODUCT
Do not look directly info a fibre optical port or any connected fibre, although the product is designed to meed the Class 1 Laser regulations and complies with 21 CFR 1040.10 and 1040.11.
CAUTION – FIBRE OPTIC HANDLING
Fibre optic equipment need special treatment. It is very sensitive to dust and dirt. If the fibre is disconnected from the product, the protective plugs on the transmitter/receiver must be connected. The protective plugs must be kept on during transportation. The fibre optics cables must be handled the same way.
CAUTION – CORROSIVE GASES
If the product is placed in a corrosive environment, it is important that all unused connector sockets are protected with a suitable plug, in order to avoid corrosion attacks on the gold plated connector pins.
CAUTION – ELECTROSTATIC DISCHARGE (ESD)
Prevent electrostatic discharge damages to internal electronic parts by discharging your body to a grounding point (e.g. use a wrist strap).

Care recommendations

Follow the care recommendations below to maintain full operation of product and to fulfil the warranty obligations:

  • Do not drop, knock or shake the product. Rough handling above the specification may cause damage to internal circuit boards.
  • Use a dry or slightly water-damp cloth to clean the product. Do not use harsh chemicals, cleaning solvents or strong detergents.
  • Do not paint the product. Paint can clog the product and prevent proper operation.

If the product is used in a manner not according to specification, the protection provided by the equipment may be impaired.
If the product is not working properly, contact the place of purchase, nearest Westermo distributor office or Westermo technical support.

Cleaning of the optical connectors
In the event of contamination, the optical connectors should be cleaned by the use of forced nitrogen and some kind of cleaning stick.

Recommended cleaning fluids:

  • Methyl-, ethyl-, isopropyl- or isobutyl-alcohol
  • Hexane
  • Naphtha

Maintenance

No maintenance is required, as long as the product is used as intended within the specified conditions.

Product disposal

This symbol means that the product shall not be treated as unsorted municipal waste when disposing of it. It needs to be handed over to an applicable collection point for recycling electrical and electronic equipment.
By ensuring the product is disposed of correctly, you will help to reduce hazardous substances and prevent potential negative consequences to both environment and human health, which could be caused by inappropriate disposal.

Article number, model and description

Article Model Description
3645-0001 MCW-211-MM-SC2 10/100Base-T/TX: 1 port 100Base-FX: 1 port
3645-0010 MCW-211-MM-ST2 10/100Base-T/TX: 1 port 100Base-FX: 1 port
3645-0020 MCW-211-SM-SC15 10/100Base-T/TX: 1 port 100Base-FX: 1 port
3645-0030 MCW-211-SM-LC15 10/100Base-T/TX: 1 port 100Base-FX: 1 port
3645-0040 MCW-211-SM-LC40 10/100Base-T/TX: 1 port 100Base-FX: 1 port
3645-0050 MCW-211-MM-LC2 10/100Base-T/TX: 1 port 100Base-FX: 1 port

Simplified EU declaration of conformity
Hereby, Westermo declares that the equipment is in compliance with applicable EU directives. The full EU declaration of conformity and other detailed information are available at the respective product page at www.westermo.com/support/product-support.

Agency approvals and standards compliance

Type Approval / Compliance
EMC EN 61000-6-2, Immproducty industrial environments

EN 61000-6-4, Emission industrial environments
Marine| DNV GL rules for classification – Ships and offshore products¹
Note| ¹ Applicable only for 3645-0030, 3645-0040 , 3645-0050

Corrosive environment:

This product has been successfully tested in a corrosion test according to IEC 60068-2-60, method 4. This means that the product meets the requirements to be placed in an environment classified as ISA-S71.04 class G3.

CAUTION – CORROSIVE GASES
If the product is placed in a corrosive environment, it is important that all unused connector sockets are protected with a suitable plug, in
order to avoid corrosion attacks on the gold plated connector pins.

Type tests and environmental conditions

Electromagnetic Compatibility

Phenomena| Test| Description| Level
ESD| EN 61000-4-2| Enclosure contact| ± 4 kV
Enclosure air| ± 8 kV
RF field AM modulated| IEC 61000-4-3| Enclosure| 10 V/m 80% AM (1 kHz), 30 — 2700 MHz
Fast transient| EN 61000-4-4| Signal ports| ± 1 kV
Power ports| ± 2 kV
Surge| EN 61000-4-5| Signal ports balanced| ± 2 kV line to earth, ± 1 kV line to line
Power ports| ± 2 kV line to earth, ± 2 kV line to line
RF conducted| EN 61000-4-6| Signal ports| 10 V 80% AM (1 kHz), 0.15 — 80 MHz
Power ports| 10 V 80% AM (1 kHz), 0.15 — 80 MHz
Voltage dips and interruption| EN 61000-4-29| DC power ports| 10 ms, interruption
10 ms, 30% reduction
10 ms, 60% reduction
+20% above & —20% below rated voltage
Radiated emission| CISPR 16-2-3 ANSI C63.4
(FCC part 15)| Enclosure| Class A
Conducted emission| CISPR 16-2-1| DC power ports| Class A
Dielectric strength| UL 60950-1| Signal port to other isolated ports| 1.5 kVrms 50 Hz 1 min
Power port to other isolated ports| 2 kVrms 50 Hz 1 min
Environmental

Temperature| EN 60068-2-1 EN 60068-2-2| Operating| -25 to +70°C
Maximum surface temperature| 135°C (temperature class T4)
Storage & Transport| -40 to +70°C
Humidity| EN 60068-2-30| Operating| 5 to 95% relative humidity
Storage & Transport| 5 to 95% relative humidity
Altitude| | Operating| 2 000 m / 70 kPa
Service life| | Operating| 10 year
Vibration| IEC 60068-2-6| Operating| 7.5 mm, 5 — 8 Hz
2 g, 8 — 500 Hz
Shock| IEC 60068-2-27| Operating| 15 g, 11 ms
Packaging
Enclosure, MCW-211| UL 94| PC / ABS| Flammability class V-1
Enclosure, MCW-211 Ex| | Cabelec 6141|
Dimension WxHxD| | | 35 x 121 x 119 mm
Weight| | | 0.25 kg
Degree of protection| IEC 529| Enclosure| IP 21
Cooling| | | Convection
Mounting| | | Horizontal on 35 mm DIN-rail

Interface specifications

Power

Rated voltage| 12 to 48 VDC
Operating voltage| 10 to 60 VDC
Rated current| 200 mA @ 12 VDC 100 mA @ 24 VDC 50 mA @ 48 VDC
Rated frequency| DC
Inrush current 12t| 0.03 /Vs @ 12 VDC
Startup current*| 0.75 A peak
Polarity| Reverse polarity protected
Redundant power input| Yes
Isolation to| Ethernet TX
| Ethernet FX
Connection| Detachable screw terminal
Connector size| 0.2 — 2.5 mm, (AWG 24 — 12)
Shielded cable| Not required

  • Direction relative this product

Ethernet TX

Electrical specification| IEEE std 802.3. 2000 Edition
Data rate| 10 Mbit/s or 100 Mbit/s, manual or auto
Duplex| Full or half, manual or auto
Transmission range| 100 m
Isolation to| Power
Connection| RJ-45
Ethernet FX

Optical specification| IEEE std 802.3. 2000 Edition
Data rate| 100 Mbit/s
Duplex| Full or half
Connection| SC, ST or LC

Location of interface ports and LEDs

Fibre optic power budget

Model| MCW-211-MM
xx2| MCW-211-SM
SC15| MCW-211-SM
LC15| MCW-211-SM
LC40
---|---|---|---|---
Transmitted wavelength| 1310 nm| 1310 nm| 1310 nm| 1310 nm
Min. output power, transmitter| -19 dBm| -15 dBm| -15 dBm| -5 dBm
Max. output power,
transmitter| -12 dBm| -8 dBm| -8 dBm| 0 dBm
Input sensitivity, receiver| -31 dBm| -34 dBm| -31 dBm| -34 dBm
MM. power budget| 12 dBm| 19 dBm| 16 dBm| 29 dBm
Max. power budget| 19 dBm| 26 dBm| 23 dBm| 34 dBm
Recommended fibre cable and core / cladding diameter| Multimode
50/125, 62.5/125| Singlemode
9/125. 10/125| Singlemode
9/125, 10/125| Singlemode
9/125, 10/125
Fibre type| Normal attenuation
@ 1310 nm multimode| Normal attenuation
@ 1310 nm singlemode
---|---|---
50/125| 3.0 dBm/km| –
62,5/125| 3.5 dBm/km| –
9/125| –| 0.5 dBm/km
10/125| –| 0.5 dBm/km

Attenuation in connectors / splices

Type Normal attenuation
Connector 0.2 – 0.4 dBm
Fusion splice 0.1 dBm
Mechanical splice 0.2 dBm

LED indicators
LED indicators are available on the front panel and on the RJ-45 TX connector.

LED| Status| Description|
---|---|---|---
PWR| ON| Internal power, initialising OK
| Slow flash| Initialisation progressing
| Fast flash| Initialisation error
LINK TX| OFF| No Ethernet link TX
| ON| Good Ethernet link TX
| Flash| Ethernet data is transmitted or received on TX interface
LINK FX| OFF| No Ethernet link FX
| ON| Good Ethernet link FX
| Flash| Ethernet data is transmitted or received on FX interface
FX DPX| OFF| Half dupex FX interface
| ON| Full duplex FX interface
LFF| OFF| Link fault forward is not active
| ON| Link fault forward is active and has shutdown an interface
LED| Status| Description|
---|---|---|---
SPD| OFF| 10 Mbitls TX interface
| ON| 100 Mbitls TX interface
DPX| OFF| Half duplex TX interface
| ON| Full duplex TX interface

Installation

Mounting / Removal

WARNING – HAZARDOUS VOLTAGE
Do not open an energized product. Hazardous voltage may occur when connected to a power supply.
CAUTION – ELECTROSTATIC DISCHARGE (ESD)
Prevent electrostatic discharge damages to internal electronic parts by discharging your body to a grounding point (e.g. use a wrist strap).

Mounting
This product should be mounted on 35 mm DIN-rail which is horizontally mounted on a wall or cabinet backplate. Snap on mounting, see figure

Cooling
This product uses convection cooling. To avoid obstructing the airflow around the product, use the following spacing rules.
Recommended spacing 25 mm (1.0 inch) above/below and 10 mm

  • Spacing (left/right) recommended for full operating temperature range

Removal Press down the black support at the back of the product, see figure.
Configuration
DIP switches are accessible under the lid on top of the product. DIP switches are used to configure the product.

DIP-switch settings
WARNING – HAZARDOUS VOLTAGE
Do not open an energized product. Hazardous voltage may occur when connected to a power supply.
CAUTION – ELECTROSTATIC DISCHARGE (ESD)
Prevent electrostatic discharge damages to internal electronic parts by discharging your body to a grounding point (e.g. use a wrist strap).

NOTE! DIP- switch alterations are only effective after a power on.

Observe this when the DIP-switches will be configured
Speed and duplex setting only valid when auto-negotiation is disabled.
If auto-negotiation and auto MDI/MDI-X disabled the TX ports supports MDI-X configuration.

TX Port settings

**** Auto-negotiation and auto MDI / MDI-X disabled TX port
**** Auto-negotiation and auto MDI / MDI-X enabled TX port
**** 10 Mbit/s speed selected TX port
**** 100 Mbit/s speed selected TX port
**** Half duplex selected TX port
**** Full duplex selected TX port

FX Port settings

**** Half duplex selected FX port
**** Full duplex selected FX port

Flow control setting

**** Flow control disabled
**** Flow control disabled

Link fault forward settings

| TX → FX Link
fault forward disabled
---|---
| TX → FX Link
fault forward enabled
| FX → TX Link
fault forward disabled
| FX → TX Link
fault forward enabled
Factory settings



Westermo · SE-635 35 Stora Sundby, Sweden
Tel +46 16 42 80 00 Fax +46 16 42 80 01
E-mail: info@westermo.com
www.westermo.com
REV. F 6645-2204 2021-01 Westermo Network Technologies AB, Sweden

Documents / Resources

| westermo MCW-211 Series Industrial Ethernet Media Converter [pdf] User Guide
MCW-211 Series, Industrial Ethernet Media Converter
---|---
| westermo MCW-211 Series Industrial Ethernet Media Converter [pdf] User Manual
MCW-211 Series Industrial Ethernet Media Converter, MCW-211, Series Industrial Ethernet Media Converter, Ethernet Media Converter, Media Converter

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

westermo User Manuals

Related Manuals