Installation Manua
S-240-P4G
Read this first!
Before operating this device, please read this manual thoroughly and retain this manual for future reference! This device may only be installed and put into operation by qualified personnel. If damage or malfunction should occur during operation, immediately turn the power off and send the device to the factory for inspection. The device does not contain serviceable parts. The information presented in this document is believed to be accurate and reliable and may change without notice. For any clarifications, the English translation will be used.
WARNING
Risk of electrical shock, fire, personal injury, or death:
– Turn the power off before working on the device. Protect against inadvertent
re-powering.
– Do not open, modify or repair the device.
– Use caution to prevent any foreign objects from entering the housing.
– Do not use in wet locations or in areas where moisture or condensation can
be expected
– Do not touch during power-on and immediately after power-off. Hot surfaces
may cause burns.
Product Description
The PS-240-P4G is a DIN-rail mountable single-phase-input power supply, which provides power for Power over Ethernet (PoE and PoE+) applications. It injects power to 4 individual PoE channels (IEEE 802.3at) via RJ45 Ethernet ports. In addition, it also provides a DC output voltage for external loads.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control, monitoring, and measurement equipment or the like. The device is suitable for indoor applications. Outdoor applications are also allowed as long as all requirements specified in this manual (enclosure, controlled environment, condensation, …) are met. Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional appropriate safety devices, that are suited for the end application. If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
Installation Instructions
Install a device in an enclosure providing protection against electrical,
mechanical, and fire hazards. Install the device onto a DIN-rail according to
EN 60715 with the input terminals on the bottom of the device.
Make sure that the wiring is correct by following all local and national
codes. Use appropriate copper cables that are designed for a minimum operating
temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +60°C, and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Use
ferrules for wires on the input terminals. Unused screw terminals should be
securely tightened. Use shielded twisted-pair Ethernet cables specified for
usage in IEEE 802.3at.
The device is designed for pollution degree 2 areas in controlled
environments. No condensation or frost is allowed. The enclosure of the device
provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids. The device is designed for overvoltage
category III zones. The device is designed as Class of Protection I”
equipment according to IEC 61140. Do not use without a proper PE (Protective
Earth) connection. The device is suitable to be supplied from TN, TT r IT
mains networks. The voltage between the input terminal and the PE potential
must not exceed 264Vac. The input can also be powered from batteries or
similar DC sources. The continuous voltage between the supply voltage and the
PE/ground potential must not exceed 180Vdc. A disconnecting means shall be
provided for the input of the device. The device is designed for convection
cooling and does not require an external fan. Do not obstruct airflow and do
not cover the ventilation grid! The device is designed for altitudes up to
2000m (6560ft). Keep the following minimum installation clearances: 40mm on
top, 20mm on the bottom, 5mm on left and right sides. Increase the 5mm to
15mm in case the adjacent device is a heat source. When the device is
permanently loaded with less than 50%, the 5mm can be reduced to zero. The
device is designed, tested, and approved for branch circuits up to 20A without
an additional protection device. If an external fuse is utilized, do not use
circuit breakers smaller than 6A B- or C-Characteristic to avoid a nuisance
tripping of the circuit breaker. The maximum surrounding air temperature is
+70°C (+158°F). The operational temperature is the same as the ambient or
surrounding air temperature and is defined as 2cm below the device. The device
is designed to operate in areas between 5% and 95% relative humidity. Do not
plug or unplug the device as long as the input voltage is present. Do not
unplug the input connectors and the connector for the external loads (53V)
more often than 20 times in total.
Functional Description
The output is electronically protected against no-load, overload, and short
circuits and can supply any kind of load according to IEEE 802.3at.
Do not apply return voltages from the load to the output terminals higher than
56V.
The green DC OK LED reports an output voltage above 48V of a running device.
The DC OK relay monitors the output voltage and the contact is closed when the
DC OK LED is on. Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for
resistive loads. In order to fulfill the IEEE 802.3AT requirements, external
equipment and wiring connected to the DC OK contact need to have a minimum
isolation strength of 1500Vac to ground. The device is equipped with over-
current protection for each PoE output channel. If the current exceeds the
output current limitation value, the affected PoE channel will be switched
off. Unplug the affected channel for at least 2s. If the over-current is
cleared, the device will operate normally again. The device is equipped with
over-temperature protection. In case of a high temperature, the output shuts
down and starts automatically again after cooling off. In case of an internal
defect, a redundant circuit limits the maximum output voltage to 60V. The
output shuts down and automatically attempts to restart. The device detects
connected PoE loads automatically and will not power connected non-PoE devices
according to IEEE 802.3at. External equipment and wiring connected to the DC
output need to have a minimum isolation strength
of 1500Vac to ground.
Technical Data
All values are typical figures specified at 230Vac 50Hz input voltage, 53V 4x 30W output load (PoE), 120W external load, 25°C ambient temperature and after a 5 minutes run-in time unless otherwise noted.
Output voltage Adjustment range | DC 53V – | Nominal Not adjustable |
---|
DC output for external load
Current limitation| 120W
90W 2.26A
1.7A
5.5A| Below +60°C ambient At +70°C ambient
Below +60°C ambient At +70°C ambient
PoE Power outputs Current limitation| 4x 30W
4x 15.4W
0.63A
0.33A| PoE+ Applications PoE Applications PoE+ Applications PoE Applications
Total output power| 240W
182W| Nominal. the sum for external and PoE+ loads
Nominal. the sum for external and PoE loads
Input voltage AC Mains frequency Input current AC Power factor| AC 100 – 240V
50 — 60Hz
2.18 / 1.14A
0.99 / 0.97| -15% / +10%
±6%
At 120 / 230Vac
At 120 / 230Vac
Input voltage DC
Input current DC| DC 110 – 150V 2.35A| ±20%
At 110Vdc
Input inrush current| 6 / 9A plc| At 40°C, 120 / 230Vac
Efficiency Power losses| 92.6 / 94.1%
19.2 / 15.0W| At 120 / 230Vac
At 120 / 230Vac
Hold-up time| 37 / 37ms| At 120 / 230Vac
Temperature range| -25 to +60°C
-25 to +70°C| PoE+ Applications PoE Applications
Max. wire size (lift wire) Max. wire size with ferrules Wire size AWG
Maximum wire diameter Wire stripping length| 2.5mm’ 1.5mm’ AWG 24-12 2.3mm
10mm / 0.4inch| Power terminals Power terminals Power terminals Power
terminals Power terminals
Max. wire size (lift wire) Wire size AWG
Maximal wire diameter Wire stripping length Tightening torque| 1.5mm’
AWG 24-16
1.8 mm
6mm / 0.25inch 0.8Nm / 71b.inch| DC OK terminals DC OK terminals DC OK
terminals DC OK terminals DC OK terminals
Size (WxHxD) Weight| 77x128x117mm 9608 / 2.12Ib| Without DIN-rail