DMP 2W-BLX Addressable Smoke Detector Installation Guide
- June 6, 2024
- DMP
Table of Contents
2W-BLX/2WT-BLX ADDRESSABLE
SMOKE DETECTOR
Installation Guide
DESCRIPTION
Models 2W-BLX and 2WT-BLX are addressable photoelectric smoke detectors. Both
models incorporate a state-of-the-art optical sensing chamber and an advanced
microprocessor. These smoke detectors include an addressable single-point
module for connection to the LX-Bus ™ of XR150/XR550 Series panels.
Compatibility
- XR150/XR550 Series Panels
What is Included?
- One 2W-BLX or 2WT-BLX smoke detector
- 4-wire harness
- Hardware pack
ADDRESS THE DETECTOR
Set the two onboard rotary switches to match the last two-zone number digits.
Example: On an XR550 panel, to set the detector to zone number 569 on LX-
Bus 500, set the left rotary switch (TENS) to 6 and the right rotary switch
(ONES) to 9. See Figure 2.
INSTALL THE DETECTOR
The detector has a tamper-resistant feature that prevents removal from the
mounting base without the use of a tool.
To engage, cut the small plastic tab located on the mounting base (Figure 3),
and then install the detector.
To remove the detector head, use a small screwdriver to depress the square
tamper release tab on the skirt of the mounting base and turn the detector
counterclockwise.
SELECT A LOCATION
Mount the Base:
The detector can be mounted to any of the following surfaces:
- A single gang box
- A 3.5- or 4-inch octagonal box
- A 4-inch square box with a plaster ring
- A ceiling using drywall fasteners
Do Not Install the Detector:
- Where particles of combustion are normally present such as in kitchens or garages (vehicle exhaust) or near furnaces, hot water heaters, or gas space heaters.
- In very cold or very hot areas.
- In wet or excessively humid areas or next to bathrooms with showers.
- In dusty, dirty, or insect-infested areas.
- Near fresh air inlets or returns or excessively drafty areas.
These can drive smoke away from the detector.
MOUNT THE DETECTOR
Wiring the Detector
- Pull wire through the electrical box, then through the detector’s mounting base center opening.
- Connect the 4-wire harness to the 4-pin header according to the wiring diagram in Figure 4.
Note: Tie the red wire (smoke power) to the smoke terminal (SMK) of the panel. The other wires go to the LX-Bus™ for addressing.
Mounting the Detector
-
Place the detector on the base and rotate clockwise.
The detector will drop into the base and lock into place with a click. See Figure 5. -
After all the detectors have been installed, apply power to the control panel.
TEST THE DETECTOR
Detectors must be tested after installation and following maintenance. After power-up, allow 80 seconds for the detector to stabilize before testing.
Sensitivity Test Switch
- Insert a small screwdriver or Allen wrench (0.18” max.) into the test switch opening located on the detector housing. Push and hold (See Figure 6).
- If the detector is within the listed sensitivity limits, the detector’s Red LED should turn on within five seconds.
- To measure the detector’s sensitivity, use the System Sensor I 3 Series Model SENS-RDR Infrared Sensitivity Reader® tool.
Smoke Entry Test
Hold a smoldering stick or cotton wick at the side of the detector and gently
blow through the detector until it alarms.
Caution: Be sure to properly extinguish the smoke source after testing.
Direct Heat Method (Model 2WT-BLX only)
Direct the heat of a 1000-1500 watt hair dryer toward either of the
thermistors. Thermistors are located on each side of the screen/sensing
chamber. Hold the heat source about 12 inches from the detector to avoid
damage to the plastic.
Note: For the above tests, the detector will reset only after a Sensor
Reset is performed.
If the detector fails any of the above tests, check the wiring and clean the
detector as outlined in the Maintenance Section. If the detector still fails,
it should be replaced.
ADDITIONAL INFORMATION
Location Advice
Consult the Local Authority Having Jurisdiction (AHJ) and NFPA 72 for specific
installation information about smoke detector spacing, placement, location,
and special applications.
Maintenance and Cleaning
This detector must be tested and maintained regularly following NFPA 72
requirements. At a minimum, cleaning should be performed annually.
Before performing maintenance on the detector, notify the proper authorities
that maintenance is being performed and the system will be temporarily out of
service. Disable the circuit undergoing maintenance to prevent any unwanted
alarms. Power must be removed from the detector before performing maintenance
of any kind.
- Remove the detector cover by turning counterclockwise.
- Vacuum the cover or use canned air to remove any dust or debris.
- Remove the top half of the screen/sensing chamber by lifting straight up (See Figure 7.)
- Vacuum or use canned air to remove any dust particles that are present on both chamber halves.
- Replace the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing chamber with the arrow on the housing. Press down firmly until the screen/ sensing chamber is fully seated.
- Replace the detector cover by placing it over the screen/sensing chamber and turning it clockwise until it snaps into place.
- Reinstall the detector and test. (See Test the Detector.)
Wiring Specifications
When planning an LX-Bus installation, keep in mind the following
specifications:
- DMP recommends using 18-gauge unshielded wire for all LX-Bus circuits. Do Not use twisted pair or shielded wire for LX-Bus circuits. To maintain auxiliary power integrity when using 18-gauge wire do not exceed 1,000 feet. To increase the wire length or to add devices, install an additional power supply.
- The maximum distance for anyone circuit (length of wire) is 2,500 feet regardless of the wire gauge. This distance can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500 feet. As the wire distance from the panel increases, DC voltage on the wire decreases.
- The maximum number of devices per 2,500 feet circuit is 40.
- The maximum voltage drop between the panel (or auxiliary power supply) and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is too low, the devices cannot operate properly.
For additional information refer to the 710 Installation Sheet (LT-0310) and/or the LX-Bus/Keypad Bus Wiring Application Note (LT-2031).
Single Point Addressable
A factory-mounted, addressable single-point zone expander is integrated in the
base of the smoke detector. The included 4-wire harness allows a direct
connection to the LX-Bus of XR150/XR550 Series panels. The integrated zone
expander reports to the panel as a single zone. See Addressing the 2W-BLX and
2WT-BLX.
A Green LED is included on the integrated zone expander PCB which flashes
every 2 seconds to confirm device polling.
Fixed Temperature Thermal Detector
The Model 2WT-BLX features a restorable, built-in, fixed temperature thermal
detector and is capable of sensing a temperature higher than 135°F. If the
detector senses a higher temperature than 135 °F, the Red LED latches on, and
an alarm condition is sent to the control panel.
Built-In Drift Compensation
The detector automatically adjusts its sensitivity back to the factory setting
when it becomes more sensitive due to contaminants settling in its chamber. In
order for this feature to work properly, the chamber must never be opened
while power is applied to the smoke detector. This includes cleaning,
maintenance, or screen replacement.
LED Operation
After power-up has been completed and the detector is functioning normally
within its listed sensitivity range, the Green LED blinks once every five
seconds.
If the detector needs maintenance because its sensitivity has shifted outside
the limits, the Red LED blinks once every five seconds. See Table 1.
The LED indication must not be used in lieu of the tests specified under
Testing.
| GREEN LED| RED LED
---|---|---
Power-Up| Blink 10 seconds| Blink 10 seconds
Normal (Standby)| Blink 5 seconds| —
Out of Sensitivity| —| Blink 5 seconds
Alarm| —| Solid
Table 1: Detector LED Modes
2W-BLX/2WT-BLX ADDRESSABLE SMOKE DETECTOR
Specifications
Operating Voltage | 12 Vdc (Nominal) |
---|---|
Standby Current | 11 mA |
Alarm Current | 31 mA |
Maximum Ripple | 30% (V) peak to peak |
Operating Temperature (Ambient Room)
2W-BLX| 32°F to 120°F
2WT-BLX| 32°F to 100°F
Operating Humidity Range| 0 to 95% RH non-condensing
Heat Sensor (2WT-BLX Only)| 135°F
Power Up Time| 80 seconds
Sensitivity Photoelectric| 1-4%/ft. max.
Detector Dimensions
Diameter| 5.3 inches
Height| 2.0 inches
Weight| 6.3 ounces
Ordering Information
2W-BLX/10 | Photoelectric smoke detector |
---|---|
2WT-BLX/10 | Photoelectric smoke detector with a fixed-temperature thermal |
detector
Certifications
California State Fire Marshal (CSFM)
Underwriters Laboratories (UL) Listed
ANSI/UL 268 Smoke-Automatic Fire Detectors
Designed, engineered, and manufactured in Springfield, MO using the U.S. and
global components.
LT-1364 1.01 20442
INTRUSION • FIRE • ACCESS • NETWORKS
2500 North Partnership Boulevard
Springfield, Missouri 65803-8877
800.641.4282 | DMP.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>