SENECA R-KEY-LT Compact Industrial ModBUS Gateway Instruction Manual
- June 6, 2024
- SENECA
Table of Contents
INSTALLATION MANUAL
R-KEY-LT R-KEY-LT-P
MI00472-3-EN
INSTALLATION MANUAL
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol **indicates conditions or actions that put the user’s safety at risk. The word ATTENTION preceded by the symbol **indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
**** Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection center authorized to recycle electrical and electronic waste.
http://www.seneca.it/products/r-key-lt
http://www.seneca.it/products/r-key-lt-p
CONTACT INFORMATION
Technical support
support@seneca.it
Product information
sales@seneca.it
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorized.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.
MODULE LAYOUT
Weight: 80g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | On | The device is powered with assigned IP |
Flashing | IP not assigned | |
TX | Flashing | Data transmission on port RS232/RS485 |
RX | Flashing | Data receipt on port RS2321RS485 |
ETH ACT (Yellow) | Flashing | Packet transit on Ethernet port |
ETH LNK (Green) | Flashing | Ethernet port connected |
COM (R-KEY-LT-P version only) | Flashing | Profinet communication active |
Off | No Profinet communication | |
COM+PWR (R-KEY-LT-P version only) | Flashing | Webserver active / Profinet not |
active
DEVICE CONFIGURATION
The device can be fully set up via an integrated webserver. The product programming and/or configuration tools, as well as all the manuals, can be downloaded using the QR-CODE from the web address: For further information, refer to the USER MANUAL.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101
WEB SERVER AND PROFINET MODE (R-KEY-LT-P)
The device is normally in Profinet mode; in Profinet mode the device can be
configured only through the Easy Setup 2 software.
In order to access the internal webserver, it is necessary to put the device
in Webserver mode using the Easy Setup2 or Seneca Device Discovery software.
It is also possible to change the operating mode by pressing the side button
following the procedure:
To force webserver mode:
- Keep the “REBOOT / MODE” button pressed until all the LEDs flash quickly
- Release the button
- The device restarts and the PWR and COM LEDs flash slowly to indicate webserver mode To force Profinet mode:
- Keep the “REBOOT / MODE” button pressed until all the LEDs flash quickly
- Release the button
- The device restarts and the PWR and COM LEDs stop flashing slowly to indicate Profinet mode
WEBSERVER
To access the maintenance Web Server with the factory IP address above, use the following credentials: Username: admin; Password: admin
N.B.: For the R-KEY-LT-P version it is first necessary to activate webserver mode
CAUTION
DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
CERTIFICATIONS|
https://www.seneca.it/products/r-key-It/doc/CE_declaration
---|---
INSULATION|
POWER SUPPLY| Voltage: 11 + 40Vdc; 19 + 28Vac; 50 + 60 Hz, max
absorption: 1W
ENVIRONMENTAL
CONDITIONS| Temperature: -25°C + +65°C
Humidity: 30% + 90% non condensing Storage temperature: -30°C + + 85°C Protection rating: IP20 (not rated by UL)
ASSEMBLY| DIN rail 35mm IEC EN60715, wall or panel with screws.
CPU| ARM 32 bit
OPERATING SYSTEM| Real-time multitasking
CONFIGURATION| Configuration and FW update via webserver; Via DIP –
SWITCH
Via EASY SETUP 2 configuration software
CONNECTIONS| Removable 7-way screw terminals, 5 mm pitch, cable section
up to 2.5 mm2 Removable 2-way screw terminals, 5 mm pitch, cable section up to
2.5 mm2 RJ45 connector for Ethernet cable
COMMUNICATION| RS2321RS485 on 1-7 terminal; maximum Baud rate 115k
ETHERNET PORTS| 1 x 100Mbit Ethernet port with auto switch
DIP – SWITCH SETTINGS
WARNING
The DIP-switch settings are read-only at boot time. At each change, perform a
restart.
SW1 DIP-SWITCH:
Through DIP-SWITCH-SW1 it is possible to set the polarization of the bus
relative to the RS485 port:
DESCRIPTION
| DIP 1| DIP 2
---|---|---
To polarize the bus on RS485, both SW1 DIP switch selectors must be set to ON|
|
NOT to polarize the bus on RS485, both SW1 DIP switch selectors must be set to
OFF
SW2 DIP-SWITCH:
Through DIP-SWITCH-SW2 it is possible to set the IP configuration of the
device:
DESCRIPTION | DIP 1 | DIP 2 |
---|
To obtain the configuration from the Flash memory, both SW1 DIP switch
selectors must be set to OFF| |
To reset the device to factory settings both SW1 DIP switches must be set to
ON
To force the device’s IP address to the standard value of SENECA Ethernet
products: 192.168.90.101
Reserved
ELECTRICAL CONNECTIONS
CAUTION
Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations
(transformers, inverters, motors, etc…).
CAUTION
Use only copper or copper-coated aluminum or AL-CU or CU-AL conductors
POWER SUPPLY | RS485 SERIAL PORT | RS232 SERIAL PORT |
---|
The power supply source must be protected from any module malfunctions using appropriately-sized safety fuses.
| |
CAUTION
The device can only be powered by a power supply with a limited energy circuit
40Vdc / 28Vac max in the output according to CAN/CSA-C22.2 No.61010-1-12 / UL
Std.No.61010-1 (3rd Edition) chapter 6.3.1/6.3.2 and 9.4 or class 2 according
to CSA 223/UL1310.
CAUTION
These are open-type devices intended for installation in a final casing/panel
that offers mechanical protection and protection against the spread of fire.
MI00472-3-EN