Anybus RS232 Communicator Serial CAN Converters Gateways Instruction Manual

June 6, 2024
Anybus

Anybus logo

Anybus RS232 Communicator Serial CAN Converters Gateways

Anybus RS232 Communicator Serial CAN Converters
Gateways

General Safety Instructions

Caution

  • This equipment contains parts that can be damaged by electrostatic discharge (ESD). Use ESD prevention measures to avoid damage.
  • To avoid system damage, the equipment should be connected to ground.
  • If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

Intended Use
The intended use of this equipment is as a communication interface and gateway. The equipment receives and transmits data on various physical layers and connection types.

Model Identification

Hardware description Model ID
Serial to Ethernet. With rotary switches 40-SER-ETH-A
Serial to Ethernet. Without rotary switches 40-SER-ETH-B
Serial to Profibus. With rotary switches 40-SER-PDP-A
Serial to Profibus. Without rotary switches 40-SER-PDP-B
Ethernet to Ethernet. With rotary switches 40-ETH-ETH-A, 40-ETH-ETH-A-60*
Ethernet to Ethernet. Without rotary switches 40-ETH-ETH-B, 40-ETH-ETH-B-60*
  • Other CPU mount option.

Installation

Make sure that you have all the necessary information about the capabilities and restrictions of your local network environment before installation.

  • Tightening torque for 3-pin and 7-pin connector: 0.5-0.8 Nm.
  • Use minimum 90 °C copper (Cu) wire only.
  • Equipment to be supplied by Class 2 Power Source in accordance with the NEC.
  • The equipment is considered as open type and shall be installed in a suitable end enclosure providing mechanical protection.
  • Use in Overvoltage Category I Pollution Degree 2 Environment conforming to EN 60664-1.
  • This equipment is designed to comply as Class III equipment according to 61010-2- 201.

Technical Specifications

Model identification| 40-SER-ETH-A

40-SER-ETH-B

| 40-SER-PDP-A

40-SER-PDP-B

| 40-ETH-ETH-A

40-ETH-ETH-B

40-ETH-ETH-A-60

40-ETH-ETH-B-60

---|---|---|---
Configuration connector| RJ45
Upper connector| 7-pin screw connector| RJ45x2
Lower connector| RJ45x2| 9-pin D-sub| RJ45x2
Power connector| 3-pin screw connector
Power supply| 12-30 VDC

Reverse voltage protection and short circuit protection

Power consumption| Typical: 160 mA @ 24 V

Max: 400 mA @ 12 V

Storage temperature| -40 to +85 °C
Operating temperature| -25 to +70 °C
Humidity| EN 600068-2-78: Damp heat, +40°C, 93% humidity for 4 days EN 60068-2-30: Damp heat, +25°C – +55°C, 95% RH, 2 cycles
Vibration| See datasheet
Housing material| Plastic

See datasheet for details

Protection class| IP20
Product weight| 150 g
Dimensions| 27 x 144 x 98 mm (H x W x D) with connectors included
Mounting| DIN-rail

Additional technical data and information related to the installation and use of this product can be found at www.anybus.com/support

CE Compliance
This product is in compliance with the EMC Directive 2014/30/EU and the RoHS Directive 2011/65/EU with amendment 2015/863 through conformance with applicable standards. The full text of the Declaration of Conformity is available at www.anybus.com/support

Disposal and recycling
You must dispose of this equipment properly according to local laws and regulations. Because this equipment contains electronic components, it must be disposed of separately from household waste. When this equipment reaches its end of life, contact local authorities to learn about disposal and recycling options, or return the equipment to HMS.
For more information, see www.hms-networks.com

UL Ordinary Locations (OrdLoc)
This equipment is certified for use in ordinary locations in compliance with the following standards:

  • UL 61010-1 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 1: GENERAL REQUIREMENTS – Edition 3
  • UL 61010-2-201 STANDARD FOR SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 2-201: PARTICULAR REQUIREMENTS FOR CONTROL EQUIPMENT – Edition 2
  • CSA C22.2 NO. 61010-1 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT FOR MEASUREMENT, CONTROL, AND LABORATORY USE. PT. 1, GENERAL REQUIREMENTS – Edition 3
  • CSA C22.2 NO. 61010-2-201 SAFETY REQUIREMENTS FOR ELECTRICAL EQUIPMENT
    FOR MEASUREMENT, CONTROL, AND LABORATORY USE – PART 2-201: PARTICULAR REQUIREMENTS FOR CONTROL EQUIPMENT – Edition 2

The certification number of Anybus Communicator certified modules according to OrdLoc certification is: E214107
According to the standards listed above, Anybus Communicator modules are certified with the following marking:

image

7-pin

7-pin


| Pin| Data
---|---|---
1| RS232 Rx Input
2| RS232 Tx Output
3| Functional Earth (FE)
4| Signal GND
5| RS485+ B
6| RS485- A
7| +5 V OUT

RJ45

| Pin| Data| Pin| Data
---|---|---|---|---
1| TD+| 5|
2| TD-| 6| RD-
3| RD+| 7|
4|  | 8|

3-pin

| Pin| Data
---|---|---
1| 12-30 VDC
2| Ground (GND)
3| Functional Earth (FE)

9-pin D-sub

9-pin D-sub


| Pin| Data
---|---|---
1| Shield
3| B-line
4| Request to Send (RTS)
5| GND bus
6| +5 V bus cut
8| A-line
2, 7, 9| NC

© 2021 HMS Industrial Networks
Box 4126, 300 04 Halmstad, Sweden
SP2802 1.10 / 2021-10-08 / 23560

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals