Anybus E300-MBTCP E300 Communication Module for Modbus TCP User Guide

June 6, 2024
Anybus

Anybus logo STARTUP GUIDE
Anybus-E300-MBTCP
E300 Communication Module for Modbus TCP

Important User Information

Disclaimer
The information in this document is for informational purposes only. Please inform HMS Networks of any inaccuracies or omissions found in this document. HMS Networks disclaims any responsibility or liability for any errors that may appear in this document.
HMS Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Networks and is subject to change without notice. HMS Networks makes no commitment to update or keep current the information in this document.
The data, examples, and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Networks cannot assume responsibility or liability for actual use based on the data, examples or illustrations included in this document nor for any damages incurred during the installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes, and standards. Further, HMS Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result of the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Preface

About This Document
This manual describes the installation of the Anybus-E300-MB TCP.
For information on how to configure the Anybus-E300-MBTCP, refer to the user manuals for the Anybus-E300-MBTCP and the E300 Electronic Overload Relay.
Please visit www.anybus.com/support and
www.rockwellautomation.com/support.

Document Conventions

Numbered lists indicate tasks that should be carried out in sequence:

  1.  First, do this
  2. Then do this

Bulleted lists are used for:

  • Tasks that can be carried out in any order
  • Itemized information
    ► An action → and a result

User interaction elements (buttons etc.) are indicated with bold text.
Program code and script examples
Cross-reference within this document: Document Conventions, p. 1
External link (URL): www.hms-networks.com

WARNING
Instruction must be followed to avoid a risk of death or serious injury.
Caution
Instruction must be followed to avoid a risk of personal injury.
Instruction that must be followed to avoid a risk of reduced functionality and/or damage to the equipment, or to avoid a network security risk.
important 1Additional information which may facilitate installation and/or operation.

Trademarks

Anybus® is a registered trademark of HMS Networks AB.
All other trademarks are the property of their respective holders.

Safety

Intended Use
The intended use of this equipment is as a communication interface. The communication module allows an E300 Relay to be integrated into an automation system.
The communication module has two RJ45 connectors that function as a switch.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

General Safety

WARNING
To prevent electrical shock, disconnect from the power source before installing or servicing. Follow NFPA 70E requirements. Install in a suitable enclosure. Keep free from contaminants.
WARNING
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with the applicable code of practice.
WARNING
In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.

Preparation

Support and Resources
For additional documentation and technical support, please visit www.anybus.com/support and www.rockwellautomation.com/support.
Recommended Ethernet Cables

1585J-M8TBJM-2| RJ45 Straight Male to RJ45 Straight Male, Teal
Robotic TPE, Weld Splatter, Flex Rated, 2 m
---|---
1585J-M8TBJM-2| RJ45 Straight Male to RJ45 Straight Male, Teal PVC, 600V Rated, 2 m

Custom lengths are available up to 99 meters.

E300 Communication Module Network Information
Label with Network Information: MAC Id, Serial Number, and Firmware Revision.

Installation

Attach the E300 Communication Module

  1. Pull out the locking tab located on the upper left side of theE300 Relay Control Module.Anybus E300-MBTCP E300 Communication Module for Modbus TCP - Installation 1
  2. Attach the E300 Communication Module to the E300 Relay Control Module.Anybus E300-MBTCP E300 Communication Module for Modbus TCP - Installation 3
  3. To lock the modules, push in the locking tab located on the upper left side of the E300 Relay Control Module.Anybus E300-MBTCP E300 Communication Module for Modbus TCP - Installation 2

Connecting to Ground
Motor protection function:
Ground Fault – zero-sequence method (50 N)
► Connect the Green Wire to Functional Earth (Ground).

Anybus E300-MBTCP E300 Communication Module for Modbus TCP -Connecting to
Ground

Connecting to Modbus TCP Network
The E300 Communication Module has two RJ45 ports that act as an Ethernet switch.Anybus E300-MBTCP E300 Communication Module for Modbus TCP -
Connecting to Modbus TCP Network

The E300 Communication Module listens for incoming Modbus TCP connections on TCP port 502.
Up to four simultaneous Modbus TCP connections are supported.

IP Address Setting Via Rotary Switches

Node Address Function
001 – 254 Set IP Address to 192.168.1.xxx

255 – 887
889 – 999| Configure the module to “Use configured settings”, values from nonvolatile storage.
888| Reset to factory defaults
000| Configure the module to “Use configured settings”, values from nonvolatile storage.
Enter Administration mode

► A power cycle is required for the changes to take effect.

LED Guide

Anybus E300-MBTCP E300 Communication Module for Modbus TCP - LED
Guide

E300 Communication Module LED Indicators

Position LED Indicator
A Link 1 Status and RJ45 Port G status
B Link 2 Status and RJ45 Port H status
C Network Status
D Power
Position LED Indicator
--- ---
E TRIP/WARN
F Module Status

Test/Reset

Anybus E300-MBTCP E300 Communication Module for Modbus TCP -
Reset

Test: Ensure that the E300 Relay is untripped. To open the trip relay contact: Press the Test/Reset button for 2 seconds.
Reset: Ensure that the E300 Relay is tripped. To close the trip relay contact: Press and immediately release the Test/Reset button.

connecting device © 2020 HMS Industrial Networks
Box 4126, 300 04 Halmstad, Sweden
SP2873 1.0 / 2020-11-16 / 20639