Anybus E300-MBTCP E300 Communication Module for Modbus TCP User Guide
- June 6, 2024
- Anybus
Table of Contents
STARTUP GUIDE
Anybus-E300-MBTCP
E300 Communication Module for Modbus TCP
Important User Information
Disclaimer
The information in this document is for informational purposes only. Please
inform HMS Networks of any inaccuracies or omissions found in this document.
HMS Networks disclaims any responsibility or liability for any errors that may
appear in this document.
HMS Networks reserves the right to modify its products in line with its policy
of continuous product development. The information in this document shall
therefore not be construed as a commitment on the part of HMS Networks and is
subject to change without notice. HMS Networks makes no commitment to update
or keep current the information in this document.
The data, examples, and illustrations found in this document are included for
illustrative purposes and are only intended to help improve understanding of
the functionality and handling of the product. In view of the wide range of
possible applications of the product, and because of the many variables and
requirements associated with any particular implementation, HMS Networks
cannot assume responsibility or liability for actual use based on the data,
examples or illustrations included in this document nor for any damages
incurred during the installation of the product. Those responsible for the use
of the product must acquire sufficient knowledge in order to ensure that the
product is used correctly in their specific application and that the
application meets all performance and safety requirements including any
applicable laws, regulations, codes, and standards. Further, HMS Networks will
under no circumstances assume liability or responsibility for any problems
that may arise as a result of the use of undocumented features or functional
side effects found outside the documented scope of the product. The effects
caused by any direct or indirect use of such aspects of the product are
undefined and may include e.g. compatibility issues and stability issues.
Preface
About This Document
This manual describes the installation of the Anybus-E300-MB TCP.
For information on how to configure the Anybus-E300-MBTCP, refer to the user
manuals for the Anybus-E300-MBTCP and the E300 Electronic Overload Relay.
Please visit www.anybus.com/support and
www.rockwellautomation.com/support.
Document Conventions
Numbered lists indicate tasks that should be carried out in sequence:
- First, do this
- Then do this
Bulleted lists are used for:
- Tasks that can be carried out in any order
- Itemized information
► An action → and a result
User interaction elements (buttons etc.) are indicated with bold text.
Program code and script examples
Cross-reference within this document: Document Conventions, p. 1
External link (URL): www.hms-networks.com
WARNING
Instruction must be followed to avoid a risk of death or serious injury.
Caution
Instruction must be followed to avoid a risk of personal injury.
Instruction that must be followed to avoid a risk of reduced functionality
and/or damage to the equipment, or to avoid a network security risk.
Additional information which may
facilitate installation and/or operation.
Trademarks
Anybus® is a registered trademark of HMS Networks AB.
All other trademarks are the property of their respective holders.
Safety
Intended Use
The intended use of this equipment is as a communication interface. The
communication module allows an E300 Relay to be integrated into an automation
system.
The communication module has two RJ45 connectors that function as a switch.
If this equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
General Safety
WARNING
To prevent electrical shock, disconnect from the power source before
installing or servicing. Follow NFPA 70E requirements. Install in a suitable
enclosure. Keep free from contaminants.
WARNING
Installation, adjustments, putting into service, use, assembly, disassembly,
and maintenance shall be carried out by suitably trained personnel in
accordance with the applicable code of practice.
WARNING
In case of malfunction or damage, no attempts at repair should be made. The
product should be returned to the manufacturer for repair. Do not dismantle
the product.
Preparation
Support and Resources
For additional documentation and technical support, please visit
www.anybus.com/support and
www.rockwellautomation.com/support.
Recommended Ethernet Cables
1585J-M8TBJM-2| RJ45 Straight Male to RJ45 Straight Male, Teal
Robotic TPE, Weld Splatter, Flex Rated, 2 m
---|---
1585J-M8TBJM-2| RJ45 Straight Male to RJ45 Straight Male, Teal PVC, 600V
Rated, 2 m
Custom lengths are available up to 99 meters.
E300 Communication Module Network Information
Label with Network Information: MAC Id, Serial Number, and Firmware Revision.
Installation
Attach the E300 Communication Module
- Pull out the locking tab located on the upper left side of theE300 Relay Control Module.
- Attach the E300 Communication Module to the E300 Relay Control Module.
- To lock the modules, push in the locking tab located on the upper left side of the E300 Relay Control Module.
Connecting to Ground
Motor protection function:
Ground Fault – zero-sequence method (50 N)
► Connect the Green Wire to Functional Earth (Ground).
Connecting to Modbus TCP Network
The E300 Communication Module has two RJ45 ports that act as an Ethernet
switch.
The E300 Communication Module listens for incoming Modbus TCP connections on
TCP port 502.
Up to four simultaneous Modbus TCP connections are supported.
IP Address Setting Via Rotary Switches
Node Address | Function |
---|---|
001 – 254 | Set IP Address to 192.168.1.xxx |
255 – 887
889 – 999| Configure the module to “Use configured settings”, values from
nonvolatile storage.
888| Reset to factory defaults
000| Configure the module to “Use configured settings”, values from
nonvolatile storage.
Enter Administration mode
► A power cycle is required for the changes to take effect.
LED Guide
E300 Communication Module LED Indicators
Position | LED Indicator |
---|---|
A | Link 1 Status and RJ45 Port G status |
B | Link 2 Status and RJ45 Port H status |
C | Network Status |
D | Power |
Position | LED Indicator |
--- | --- |
E | TRIP/WARN |
F | Module Status |
Test/Reset
Test: Ensure that the E300 Relay is untripped. To open the trip relay contact:
Press the Test/Reset button for 2 seconds.
Reset: Ensure that the E300 Relay is tripped. To close the trip relay contact:
Press and immediately release the Test/Reset button.