SENECA R-KEY-MBUS Converter of M-BUS to ModBUS RTU/TCP-IP protocol Instruction Manual
SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 – 8705359 – Fax +39.049.8706287
For manuals in other languages and the configuration software,visit:
www.seneca.it/products/r-key-mbus
MODULE LAYOUT
SIGNALS VIA LED ON FRONT PANEL
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol indicates conditions or actions
that put the user’s safety at risk.
The word ATTENTION preceded by the symbol indicates conditions or actions
that might damage the instrument or the connected equipment. The warranty
shall become null and void in the event of improper use or tampering with the
module or devices supplied by the manufacturer as necessary for its correct
operation, and if the instructions contained in this manual are not followed.
TECHNICAL SPECIFICATIONS
Restart button:
The button is located between the SW1 DIP-switch and the Ethernet port.
To reboot the device, just keep the button pressed for 5 seconds.
Release it when all the LEDs light up.
DEVICE CONFIGURATION
R-KEY-MBUS can be fully set up via integrated web server. The product programming and/or configuration tools, as well as all the manuals, can be downloaded using the QR-CODE on the cover. For further information, refer to the USER manual.
FIRST STARTUP AND IP CONFIGURATION
At the first startup the IP address is configured in static mode with address
192.168.90.101 By default the SW2 DIP-switch selectors are set to OFF. In the
case of configuration with an IP address obtained from DHCP, and if a DHCP
server is not present in your network, the device, after 5 minutes from
startup, will initialize with the IP address: 169.254.x.y where the x and
y values are the last two MAC address digits (see product side label).
N.B. : through the software for the SDD (SENECA Discovery Device)
Windows PC, downloadable for free from the
www.seneca.it/prodotti/sdd site, it is
possible to easily identify the device on the network and view / change the IP
address in a few steps (see USER manual for details).
WEB SERVER
To access the maintenance Web Server with the factory IP address above, use the following credentials: Account User: admin ; Password: admin
SW1 DIP-SWITCH SETTINGS
Through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:
The DIP-switch settings are read only at boot time. At each change, perform a restart.
ELECTRICAL CONNECTIONS
CAUTION
On first start-up the module must be supplied without any interruptions for at
least 72 hours to charge the internal batteries. Switch the module off with
the PS1 button before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
– use shielded signal cables;
– connect the shield to a preferential instrumentation earth system;
– separate shielded cables from other cables used for power installations
(transformers, inverters, motors, etc…).
CONNECTION STANDARDS
MeterBUS is a non-polarized bus.
For the connection it is possible to use a two-wire shielded telephone cable
or an unshielded duplex cable following the indications in the table.
If a shielded cable is used, this must be connected to earth only from the R
-KEY-MBUS side.
INSTALLATION ON DIN-IEC EN 60715 RAIL
Installation : Position the device on the OMEGA rail resting the upper
teeth from top to bottom. Push the lower part towards the rail until the
locking system engages.
Removal : Turn off the module, with the help of a slotted screwdriver
unlock the locking system.
WALL MOUNTING
Installation : The device is provided with a hole for wall-mounting.
Install the device after having prepared the dowel and relative screw on the
wall.
Removal : Turn off the module, exert a slight upward pressure and move
the product away from the wall.
WARNING
The device must be installed at a maximum height of 2 meters from the floor
CONTACT INFORMATION
This document is the property of SENECA srl. Copies and reproduction are
prohibited unless authorised.
The content of this document corresponds to the described products and
technologies.
Stated data may be modified or supplemented for technical and/or sales
purposes.