PORTOR LIGHTING PT-EML-S PT-EML SERIES Area Light Instruction Manual
- October 27, 2023
- PORTOR LIGHTING
Table of Contents
PORTOR LIGHTING PT-EML-S PT-EML SERIES Area Light
IMPORTANT
Let the battery charge up for at least 24 hours. Then normal operation of
this unit should take effect. To check, press the” TEST “button. The LED lamps
on the unit should tum ON. During an electrical power failure, the led lamps
will automatically come on for a minimum of 90 minutes. In accordance with
NFPA 101, your emergency lighting system must be tested monthly for a minimum
of 30 seconds and annually for 90 minutes. Refer lo your local codes for any
additional requirements that may apply.
READ THESE INSTRUCTIONS COMPLETELY AND CAREFULLY
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE. FOR YOUR PROTECTION, READ AND FOLLOW THESE WARNINGS AND INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR MAINTAINING THIS EQUIPMENT. THESE INSTRUCTIONS DO NOT ATTEMPT TO COVER ALL INSTALLATION AND MAINTENANCE SITUATIONS. IF YOU DO NOT UNDERSTAND THESE INSTRUCTIONS OR ADDITIONAL INFORMATION IS REQUIRED, CONTACT THE MANUFACTURER.
IMPORTANT SAFEGUARDS: WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING:
- Do not use outdoors.
- Equipment should be mounted in locations and at heights where it will not be subject to tampering by unauthorized personnel.
- Do not mount near gas or electric heaters.
- The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
- Do not use this equipment for anything other than its intended use.
- Servicing of this equipment should be performed by qualified personnel.
- Disconnect AC power before servicing.
WARNING
RISK OF FIRE
Lamps are hot. Keep combustible material away from hot parts. Observe lamp
manufacture’s warnings, recommendations and restrictions on lamp operation and
maintenance. Make sure lamps are correctly installed.
WARNING
RISK OF ELECTRIC SHOCK
NEVER CONNECT TO, DISCONNECT FROM, OR SERVICE WHILE EQUIPMENT IS ENERGIZED.
INSTALLATION
(ALWAYS TURN OFF THE POWER SUPPLY FROM MAIN CIRCUIT BREAKER FIRST!)
NOTE:
- Unused wires must be capped using enclosed wire nuts.
INSTALLATION (J-BOX MOUNTING)
- Feed fixture leads through the back plate and connect to AC power supply (Fig A). For 120V use black and white wires and for 277V, use red and white wires.
- Attach back plate to J-Box and secure with screws.
- Complete the battery connection. (Fig. B)
- Align snaps and push housing directly onto the back plate (Fig. C). Apply continuous AC power and press “TEST” button to check light.
INSTALLATION (CONDUIT)
- Secure back plate lo wall surface. Route wires through hole in conduit flange and make conduit connection. For 120V, use black and white wires and for 277V, use red and white wires.
- Complete the battery connection (Fig. B).
- Align snaps and push housing directly onto the back plate (Fig. C). Apply continuous AC power and press “TEST’ button to check light.
OPERATION
- DURING AN ELECTRICAL POWER FAILURE, THE LED LAMPS WILL AUTOMATICALLY COME ON FOR A MINIMUM OF 90 MINUTES.
- TO TEST, DEPRESS THE ”TEST” SWITCH. THE EMERGENCY LED LAMPS WILL ILLUMINATE. WHEN THE SWITCH IS RELEASED THE, LAMPS WILL GO OFF.
NOTE:
Use 18-22 AWG stranded wire to connect remote lamp heads.