BROAN VTTOUCHW Advanced Touchscreen Control User Guide

June 6, 2024
Broan

BROAN VTTOUCHW Advanced Touchscreen Control

INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS
The illustrations in this document are generic; your control appearance may be slightly different from the ones shown.

WARNING

Electrical wiring must be done by qualified personnel in accordance with all applicable codes and standards. Before connecting wires, unplug the unit or switch power off at service panel and lock service disconnecting means to prevent power from being switched on accidentally. Always wear safety glasses and gloves while performing these instructions.

CAUTION

Failure to comply with the following can cause erratic operation of the control and/or unit:

  • Never install more than one main wall control per ventilation unit.
  •  Keep control low voltage wiring at least 1 foot (305 mm) away from motors, lighting balast, light dimming circuit and power distribution panel. Do not route control wiring alongside house power wiring.
  •  Ensure the wires are securely connected.

CAUTION

If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts to prevent condensation formation inside and outside ducts, which could cause material damage and/or mold growth. Moreover, if fresh air to building duct and/or stale air from building duct goes/go through an unconditioned space, the unit must be set to operate continuously in cold conditions (below 10°C/50°F). Continuous air movement inside ducts will prevent condensation formation. The unit can be stopped temporarily for maintenance and/or repair purposes in such conditions. (Refer to section 2.2 from unit User and Installer Manual for more details.)

INSTALLATION

This control is compatible with all AI series units.

  1. Unplug the ventilation unit.

  2. Unscrew the screw located on the underside of the wall control. Separate the front module from the mounting plate by lifting its bottom part. NOTE: If the control is to be installed in an electric box, do not perform steps 3 and 4.

  3. Using the mounting plate, mark the hole opening and screw locations at the desired height on the wall.

  4. Cut the hole opening using the mark previously drawn (1/8″ outside the mark is recommended). Drill both screw holes (3/16″ Ø) in wall and insert the wall anchors (included).

  5. Fix the mounting plate to the wall using the screws provided

  6. Strip the end of the cable to access the 4 wires (about 3″). Strip the end of each wire (about 1/4″). Connect the wires to the terminals, regardless of the wire color. Note which wire color has been chosen for each terminal. CAUTION
    Be careful not to pinch wires when reinstalling the front module on the mounting plate.

  7. Install the front module on the mounting plate. Fix both parts by screwing the screw on the underside of the wall control. 

  8. Perform the electrical connection to the terminal connector of the unit, as shown below. For more details, refer to the installation manual of the ventilation unit.

  9. BROAN VTTOUCHW Advanced Touchscreen Control fig 7NOTE: To avoid miswiring, refer to the notes taken at step  to match the wire color with the right terminal.
    Plug the ventilation unit in power source.

PRELIMINARY SETTINGS

BROAN VTTOUCHW Advanced Touchscreen Control fig 8

AVAILABLE MODES

BROAN VTTOUCHW Advanced Touchscreen Control fig 9

  • The SMART mode uses indoor relative humidity level and outdoor temperature to manage the air exchange with the outdoors, in order to enhance comfort in the house. See graph below.

NOTES: Some features may not be available on all units. The temperature displayed on ADVANCED TOUCHSCREEN wall control may vary by 5ºC (9ºF) (more or less) compared to the outside temperature since the temperature sensor is located inside the unit to ensure a reading that optimizes Virtuo Air TechnologyTM algorithms.

NAVIGATION KEYS BROAN VTTOUCHW Advanced Touchscreen Control fig
10

TROUBLESHOOTING

P ROBLEM| P OSSIBLE  CAUSE ( S )| S OLUTION ( S )
---|---|---
The screen is not powered| The ventilation unit is not powered| Plug the ventilation unit
Miswiring/Damaged wire/Contact between wires| Check wall control wiring
The connector J15a is not connected properly| Check J15a connector connection
The wall control is not operational or defective| Check if it uses the same isolated power circuit as the unit on the electronic board
Replace the electronic assembly
The screen is powered but displays error E50| Miswiring/Broken wire| Check wall control wiring
The touch screen does not work for all the keys| Defective control| Replace the electronic assembly

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Broan User Manuals

Related Manuals