BROAN BLP150E75NS-PC Fresh Air Systems Owner’s Manual
- May 15, 2024
- Broan
Table of Contents
Fresh Air Systems – 150 CFM
Owner’s Manual
BLP150E75NS-PC Fresh Air Systems
Part no. BLP150E75NS-HW (Hardwired)
For plug connected applications, refer to BLP150E75NS-PC
35 to 146 CFM @ 0.4 in. w.g.
Parts/Motor/ERV Core
Visit Broan-NuTone.com for complete warranty text.
The industry’s most versatile and advanced fresh air system, created to simplify the design, specification and installation process while delivering superior air quality in a compact design.
- Quickest installation in its category saving the installer up to 20 minutes per unit, thanks to the auto-balancing and self-adjusting VIRTUO™ technology*
- Airflow configuration can be swapped with the flip of an integrated selection switch** , eliminating the need for specifying different models to accommodate mirrored floor plans and providing simplicity throughout the design and installation processes
- Horizontal and wall mount options provide location flexibility to accommodate various application needs
- Integrated LCD screen provides intuitive CFM selection in 1 CFM increments throughout the airflow range providing real-time CFM and watt usage values
- Equipped with PMSM ECM motors for reliable and energy efficient operation
- Fault indicator display (FID) responding to filter maintenance, low airflow condition, and system sensor failures while providing real-time airflow and power usage.
*US Patent No. 11168916 – Canadian patent pending
**Patent pending
Optional Controls
There are 4 optional main controls and 2 optional auxiliary controls
available. Refer to Wall Control specification sheet for more information.
***Speed selector control available only in the US.
Product Specifications subject to change without notice.
Unit Attributes
- SRE of 84% at 32°F (0°C) (36 CFM)
- Ports size: 6″
- Fan Efficacy: 2.1 CFM/Watt (64 CFM)
- Defrost operation will automatically activate to manage recovery core frost.
- Corrosion resistant galvanized steel door and cabinet
- One-piece molded insulation shell (expanded polystyrene; UL 94 HF-1 certified)
- VIRTUO™ constant airflow and auto-balancing device
- Integrated motorized dampers within both supply and exhaust air stream (no additional backdraft dampers required).
- No condensate drain required
- Unit electrical characteristics: Volt:120/1 60 Hz, MCA: 2.4 A, MCOP: 15 A, Watts: 170
Recovery Core
- ERV polypropylene crossflow core and plastic covers, impact resistant, non washable
Dimensions: 12″ x 24″ x 8.5″ (30.5 cm x 61 cm x 21.6 cm)
Filtration
- MERV 8 grade washable standard filter (included)
- Optional 2″ thick MERV13 grade filter (disposable)
Exterior Termination Options
- Compatible with Tandem Terminations (part no. VTYIK1 and V14695) (airflow setting should be adjusted in accordance with application requirements)
Dimensions
Fan Curves with VIRTUO™
Thanks to VIRTUO™ technology, no need to balance the unit manually. Both PMSM
ECM motors are controlled by an artificial intelligence performing 120
readings per minute then processing this information to maintain the requested
airflow.
For typical installation, VIRTUO™ will ensure a balanced ventilation at every
selected speed regardless of the weather conditions, the type of connection,
the variable speed furnace/AHU, the stack effect, the filter clogging and so
on. This results in peace of mind for installers and users knowing that the
unit will always remain balanced and that it will maintain its maximum
heat/energy recovery efficiency.
Static Pressure (pa)| Static Pressure
(in. w.g.)| Net Supply Airflow (L/s)| Net Supply Airflow (cfm)| Gross Airflow
Supply (L/s)| Gross Airflow Supply (cfm)| Gross Airflow
Exhaust (L/s)| Gross Airflow
Exhaust (cfm)
---|---|---|---|---|---|---|---
25| 0.1| 75| 159| 76| 161| 76| 161
50| 0.2| 73| 155| 74| 157| 74| 157
75| 0.3| 71| 150| 72| 153| 72| 153
100| 0.4| 69| 146| 70| 148| 70| 148
125| 0.5| 67| 142| 68| 144| 68| 144
150| 0.6| 65| 138| 66| 140| 66| 140
175| 0.7| 63| 133| 64| 136| 64| 136
200| 0.8| 61| 129| 62| 131| 62| 131
225| 0.9| 58| 123| 59| 125| 59| 125
250| 1.0| 56| 119| 57| 121| 57| 121
Energy Performance
Supply Temperature| Net Airflow| Power Consumed Watts| Sensible Recovery
Efficiency| Adjusted Sensible Recovery Efficiency| Apparent Sensible
Effectiveness*| Total Recovery Efficiency| Adjusted Total Recovery Efficiency|
Latent Recovery / Moisture Transfer
---|---|---|---|---|---|---|---|---
°C| °F| L/S| CFM
Heating| | | | | | | | |
0| 32| 17| 36| 17| 84%| 87%| 88%| –| –| 0.72
0| 32| 30| 64| 31| 78%| 81%| 82%| –| –| 0.65
0| 32| 52| 110| 70| 70%| 73%| 74%| –| –| 0.57
Cooling| | |
35| 95| 17| 36| 20| –| –| 82%| 72%| 75%| 0.71
35| 95| 30| 64| 32| –| –| 74%| 65%| 68%| 0.63
35| 95| 52| 110| 75| –| –| 65%| 55%| 58%| 0.55
*Data not certified by HVI.
Fan Efficacy
The following data are not certified by HVI but come from measurement in accordance with CSA C439-18.
Airflow (CFM) 1| Airflow (L/s) 1| Power (watts)| Fan Efficacy
(CFM/W) 2| Fan Efficacy (L/s/W) 2
---|---|---|---|---
35| 17| 16.5| 2.1| 1.00
40| 19| 18.6| 2.1| 1.01
45| 21| 20.8| 2.1| 1.02
50| 24| 23.0| 2.1| 1.03
55| 26| 25.3| 2.1| 1.03
60| 28| 27.7| 2.1| 1.02
65| 31| 30.2| 2.1| 1.02
70| 33| 32.9| 2.1| 1.00
75| 35| 35.8| 2.1| 0.99
80| 38| 39.0| 2.0| 0.97
85| 40| 42.4| 2.0| 0.95
90| 42| 46.1| 1.9| 0.92
95| 45| 50.1| 1.9| 0.90
100| 47| 54.4| 1.8| 0.87
105| 50| 59.1| 1.8| 0.84
110| 52| 64.2| 1.7| 0.81
115| 54| 69.8| 1.7| 0.78
120| 57| 75.8| 1.6| 0.75
125| 59| 82.3| 1.5| 0.72
130| 61| 89.3| 1.5| 0.69
135| 64| 96.9| 1.4| 0.66
140| 66| 105.0| 1.3| 0.63
145| 68| 113.7| 1.3| 0.60
150| 71| 123.1| 1.2| 0.58
155| 73| 133.1| 1.2| 0.55
- Gross airflow measured at 70°F/21°C sea level, supply and exhaust stream balanced and equivalent external differential pressure of 0.2″ w.g. 50 Pa applied to each stream.
- Fan efficacy calculated from balanced gross airflow divided by measured power then rounded to one decimal for I-P units (CFM/W) or 2 decimals for SI units (L/s/W).
Requirements and Standards
- UL 1812 compliant (safety)
- Performance tested in accordance with CSA C439 Standard
- Compliant with Prop 65
- Can be used to comply with ASHRAE standard 62.2
- Can be used to comply with ASHRAE 90.1-2019 requirements
- Can be used to comply with International Energy Conservation Code (IECC) requirements
- Can be used to comply with California Title 24 2019 Part 6 Fault Indicator Display Requirements
- Can be used to earn WA energy code credits
- HVI certified
Project: | Remarks |
---|---|
Location: |
Part no.:
Qty.:
Submitted by: ——— Date: ———