Parameter

Supply voltage AC100~240V;50–60Hz
Power consumption 1W Max (Wi-Fi 3W Max)
Temp. setting range 5~95°C
Floor limited range 20.90°C
On/off deviation 0.5~10°C, Factory setting ± 1°C
Ambient temperature -5,–50°C
Protection level
Shell material Anti-Flammable PC

Product Overview

This series of thermostats has Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.

Version System mode Model Application

Floor
heating| Heating| E P

Weekly programming

| Built-in & floor sensor, floor limit sensor +
WP| An NC/NO dual-output + Weekly programming
WP B| An NC/NO dual-output + Weekly programming+ Potential-free output
Fan Coil| Heating /Cooling / Ventilation| Ac2| Timer task + 2-pipe system
Ac2

485

| Timer task + 2-pipe system + 485Modbus (optional)
Ac4| Timer task + 4-pipe system + 485Modbus (optional)
Integrated| Heating / Cooling / Ventilation/Floor heating / Floor heating + Heating| AW y| Floor heating & fan coil, weekly programming + Potential-free output + Timer task + 485Modbus (optional) + Door card (optional)

Display Symbols

Temperature Control Mode(Floor Heating/Integrated)

Auto Mode Weekly-circled program, up to 6 heating events can be set per day. Heating events, workdays, and temperatures can be separately customized based on personal routines.
Manual Mode Thermostat works based on manually-set temperature, disconnecting from auto mode.
Temporary Mode Thermostat works based on manually-set temperature temporarily and then shifts back to auto mode till the next event.
User Operation
Power off Press “ ” shortly to turn on/off the thermostat.
Temp setting: Rotate handwheel” “to change the set temperature by 0.5°C.
System node: Press “ ” shortly to switch cooling/heating/ventilation. (Fan Coil)
Press ” ” shortly to switch cooling/heating/ventilation/floor heating/ floor heating + heating. (Integrated)
Enter menu: Press “  ” enter the menu interface.
Temp control mode: Press ” ” shortly to switch manual/auto mode. (Floor heating)
Press ” ” shortly to switch manual/auto mode. (Integrated, floor heating)
Child-lock Press ” M ” + ” for 3 seconds to activate child-lock.

Auto-mode Setting

When device is off, press ” ” to enter menu page, choose “period setting” to set parameters, then press “  ” to save and exit.

Events Time Temperature
Default value Modify Default value
Workdays Sunrise 0 6
Morning 0 8 : 0 0
Nooning 11     : 30
Afternoon 12 : 30
Evening 17 : 00
Night 22 : 00
Weekends Sunrise 06 :
Night 22 : 00

Advanced Setting (Usually for Professional Technicians)
Choose “advanced setting” on the menu page and put in password 123456 to enter the advanced setting page, set parameters then press “ ” to save and exit.

Meaning Rotate handwheel Default value
Sensor Mode Built-in Sensor

Floor Sensor

Built-in Control&Floor Limitation

| IN
Buit4n Sensor Calibration| –5-5°C| —3°C
Buit-in Max Setting Value| 5-95°C| 50°C
Floor Max Setting Value| 10-95°C| 50°C
Limitation Value| 20-95°C| 35°C
Output Jitter Control| 0-5°C| 1*C
Anti-Freeze Protection| ON/OFF| OFF
Linkage Mode| Noninverting

Inverting Inverting Inverting and Anti-Freeze closed

| Noninverting
Linkage Time Delay| 0-5Min| 0Min
Weekday Mode| Monday to Friday/Monday to Saturday /Monday to Sunday/| 2-d a y
Boot Type| Function Off/Functon On/Function Saved| 0 F F
Temperature Unit| F/QC| QC
Child Lock Type| None

Lock All

All but power

| None
Control Mode| All/Air/Floor| Floor
Cloud Region| CN/US/EU| CN
Reset All Settings| /| /

RGB Colorful LCD Screen Smart Thermostat

Sensor failure
Please select the work mode of sensors correctly. When it shows EO/E1 error, the thermostat will stay power-off till the error is eliminated.EO: the built- in sensor is short-circuited or disconnected. El: floor sensor is short- circuited or disconnected.

Timer Task Setting (Fan Coil/Integrated)
Press” “to enter the menu. Turn the knob” “, choose “Auto Mode”, and then choose “Schedule”. Set the parameters by turning the knob, then press ” 8r to save and exit to the home page

Mounting Steps
The thermostat adopts a pre-guide and limited snap-fit design. It is easy to mount.

  1.  Release the front cover by inserting a head screwdriver into the bottom crack.

  2. Insert the wires and then fix these wires with screws. The suggested wire-stripping length is 7-9mm.

  3.  Mount backing plate into wall-cassette, put screws, and then fix the thermostat. Make sure that the thermostat is fixed without deformation. Suggested torque is 0.2-0.4N.m (2.0-4. lkgf.cm).

  4.  Re-mount the front cover via a snap-fit connection.

Installation instructions

Connecting Diagram
The thermostat operates in full capacity in areas with an altitude of less than 2500 above sea level. The power rating of external load should be less than or equal to 80% rated power of the thermostat in areas with an altitude of 2500m to 4200m.