BEOK R8C.723 RGB Colorful LCD Screen Smart Thermostat Instruction Manual
- June 6, 2024
- BEOK
Table of Contents
BEOK R8C.723 RGB Colorful LCD Screen Smart Thermostat
Product Overview
This series of thermostats have Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.
Version | System mode | Model | Application |
---|
Floor heating
|
Heating
| EP| Built-in & floor sensor, floor limit sensor + Weekly programming
WP| A NC/NO dual-output + Weekly programming
WPB| A NC/NO dual-output + Weekly programming+ Potential-free output
Fan Coil
| Heating /Cooling / Ventilation| Ac2| Timer task + 2-pipe system
Ac2-
485
| Timer task + 2-pipe system + 485Modbus (optional)
Ac4| Timer task + 4-pipe system + 485Modbus (optional)
Integrated
| Heating / Cooling / Ventilation/Floor heating / Floor heating + Heating|
AWY
| Floor heating & fan coil, weekly programming + Potential-free output + Timer task + 485Modbus (optional) + Door card (optional)
Display Symbols
Temperature Control Mode(Floor Heating/Integrated)
-
Auto Mode
In the weekly-circled program, up to 6 heating events can be set per day. Heating events, workdays, and temperature can be separately customized based on personal routines. -
Manual Mode
The thermostat works based on manually-set temperature, disconnecting from auto mode. -
Temporary Mode
The thermostat works based on manually-set temperature temporarily and then shifts back to auto mode till the next event.
User Operation
- Power on/off :
- Temp setting:
- System mode:
- Press “ ” shortly to switch manual/auto mode. (Floor heating)
- Press “ ” shortly to switch manual/auto mode. (Integrated, floor heating)
- Temp control mode:
- Child-lock:
- Long press “ ” to turn on/off the thermostat.
- Rotate handwheel“ ”to change the setting temperature by 0.5°C.
- Press “ ” shortly to switch cooling/heating/ventilation. (Fan Coil)
- Press “ ” shortly to switch cooling/heating/ventilation/floor heating/floor
- heating + heating. (Integrated)
- Enter menu: Press “ ” enter the menu interface.
- Press “ ” + “ ” for 3 seconds to activate child-lock.
Auto-mode Setting
When the device is off, press “ ” to enter the menu page, choose “period setting” to set parameters, then press “ ” to save and exit.
Events
| Time| Temperature
---|---|---
Default value| Modify| Default value| Modify
Workdays
| Sunrise| 06: 00|
Rotate handwheel
| 20℃| Rotate handwheel
Morning| 08: 00| 15 ℃
Nooning| 11: 30| 15 ℃
Afternoon| 12: 30| 15 ℃
Evening| 17: 00| 22 ℃
Night| 22: 00| 15 ℃
Weekends| Sunrise| 06: 00| 20℃
Night| 22: 00| 15 ℃
Advanced Setting
Choose “advanced setting” on the menu page and put in password 123456 to enter the advanced setting page, set parameters then press “ ” to save and exit.
Meaning | Rotate handwheel | Default value |
---|
Sensor Mode
| Built-in Sensor Floor Sensor
Built-in Control&Floor Limitation
|
IN
Buit-in Sensor Calibration| -5~5℃| -3℃
Buit-in Max Setting Value| 5~95℃| 50℃
Floor Max Setting Value| 10~95℃| 50℃
Limitation Value| 20~95℃| 35℃
Output Jitter Control| 0~5℃| 1℃
Anti-Freeze Protection| ON/OFF| OFF
Linkage Mode
| Noninverting Inverting Inverting
Inverting and Anti-Freeze closed
|
Noninverting
Linkage Time Delay| 0~5Min| 0Min
Weekday Mode
| Monday to Friday/Monday to Saturday
/Monday to Sunday/
|
2-day
Boot Type| Function Off/Function On/Function Saved| O F F
Temperature Unit| ℉/℃| ℃
Child Lock Type
| None Lock All
All but power
|
None
Control Mode| All/Air/Floor| Floor
Cloud Region| CN/US/EU| CN
Reset All Settings| /| /
Sensor failure
Please select the work mode of sensors correctly. When it shows E0/E1 error, the thermostat will stay power-off till the error is eliminated.E0: the built- in sensor is short-circuited or disconnected. E1: floor sensor is short- circuited or disconnected.
Timer Task Setting (Fan Coil/Integrated)
Press“ ”to enter the menu page. Turn theknob“ ”, choose “Auto Mode”, and then
choose “Schedule”. Set the parameters by turning the knob, then press “Home”
to save and exit to home page.
Dimensions (Unit: mm)
Mounting Steps
- The thermostat adopts the pre-guide and limited snap-fit design. It is easy to mount. 1)Release the front cover by inserting a head screw-driver into the bottom crack.
- Insert the wires and then fix these wires with screws. The suggested wire-stripping length is 7-9mm.
- Mount backing plate into wall-cassette, put screws, and then fix thermostat. Make sure that the thermostat is fixed without deformation. Suggested torque is 0.2~0.4N.m (2.0~4. 1kgf.cm).
Connecting Diagram
The thermostat operates at full capacity in areas with an altitude of less than 2500 above sea level. The power rating of external load should be less than or equal to 80%rated power of the thermostat in areas with an altitude of 2500m to 4200m.
Floor Heating
Documents / Resources
| BEOK
R8C.723 RGB Colorful LCD Screen Smart
Thermostat
[pdf] Instruction Manual
R8C.723, RGB Colorful LCD Screen Smart Thermostat, R8C.723 RGB Colorful LCD
Screen Smart Thermostat
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>