SALUS FC6000-M 0-10V Thermostat Instruction Manual

June 6, 2024
SALUS

SALUS FC6000-M 0-10V Thermostat

Introduction

The FC600-M 0-10V module is dedicated to fan coils or trench heaters con- trolled by 0 … 10V signal. It is a supplement to the main thermostat SALUS FC600. The module smoothly adjust fan speed via controling 0V…10V voltage. In addition, device can control two electric actuators (heating and cooling valve).

Principle of operation
The module recognizes input signals from SALUS FC600 for three different voltage fan levels and accordingly sets the 0V…10V output voltage. Voltage values f or each levels and time of voltage incrase on output are settable by buttons and displayed on LCD. Settings are saved to the device memory. The module smoothly changes the voltage value at startup and during switching between fan speed mode. Additionally this module recognizes the input signals for the heating valve and a cooling valve. Accordingly which signal will be received, module will send +24V voltage at the output for the heating/cooling valve.

Safety Information

  • Use in accordance with national and local regulations of the country and in EU territory.
  • Indoor use only. Keep your equipment completely dry.
  • The installation must be carried out by a qualified person in accordance with the rules of the country and in the EU.
  • Before install, repair, maintenance or during any connection work disconnect power supply from the module and make sure the terminals and wires are free of voltage.
  • The electrical installation where module works should be secured with a fuse, specially selected to the applied loads.
  • The device can not be used with the damaged case.
  • Under no circumstances dont’t modify the module construction.
  • Do not allow access to the module to people who didn’t read this manual. Do not install the device under voltage.
  • A short circuit at the output may damage the unit.
  • It is forbidden to operate a defective device or repaired by unauthorized service.

Terminals description

Electrical diagram

Display description and button functions

  1. Double-digit, 7-segment LED display
    • displays parameters: F1, F1, F3, t and voltage and time values
  2.  Entering the menu, selecting the parameter, increasing the value
  3. Confirmation of parameter selection, reduce the value

DIN rail mounting

Setting voltage thresholds for fan speed

The voltage threshold settings are limited by the module:

  • F1 – range from 0V to setpoint in F2
  • F2 – range from the setpoint in F1 to the setpoint in F3
  • F3 – range from setpoint in F2 to 10V

The total voltage value for the F1-F3 thresholds is limited to 0 … 10V range.

Setting the increase/decrease time of the output voltage
Time of voltage increase at the output when module starts-up and switches voltage tresholds is expressed by the parameter t. This parameter is limited to the range from 0 to 50 s. The module provides a smooth voltage increase at the output for thresholds depending on t parameter, according to the following characteristic.

Replacing the fuse

A fuse is located inside the device casing. It protects module and the devices connected to it.

NOTE: Before opening the casing disconnect the power supply the terminals of FC600-M 0-10V module and FC600 controller.

To open the casing of the module, you need to pry all the hooks (with a flat screwdriver) and then carefully remove its upper part.

NOTE: In the module should be used porcelain, slow blow 5×20 mm fuses with nominal burnout current of 8A / 230V.

Using a flat screwdriver, pry the fuse holder, replace the fuse, put the holder back in place and then snap the upper housing of the module.